Summary
PRCOM20130929
Building Permit - Commercial
Certificate of Occupancy
LANGSFORD DEVELOPMENT INC
CHANGE OF TENANT
CHANGE OF TENANT
05/15/2013
05/28/2013
07/03/2013
Locations
Contacts
ZEHR CONSTRUCTION, Address:5817 MANOR DR, Phone:(816) 935-0412  
A & D HEATING AND COOLING INC, Address:2006 W MAIN ST, Phone:(816) 537-7952  
CROSS ELECTRIC INC, Address:18705 E HIGHLAND DR, Phone:(816) 540-2452  
LEXINGTON PLUMBING & HEATING, Address:1620 TROOST AVE, Phone:(816) 231-2254  
LANGSFORD DEVELOPMENT INC, Address:616 SW 3RD ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 05/28/2013 05/28/2013
Mike Weisenborn
Misc
Corrective Action Required
05/28/2013

The existing restroom does not meet ADA requirements. Any alterations that can be done, such as adding missing grab bars, is appreciated. Action required - This comment is for information purposes.
Misc
Corrective Action Required
05/28/2013

The breakroom sink is required to be accessible. The top of the sink shall be no more than 34" above the finished floor. Action required - To be verified on inspection.
Bldg - Toilet rooms - Walls
Corrective Action Required
05/28/2013

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - This comment is for informatiom purposes. If the walls in the restroom are to be painted, an epoxy paint is required.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
05/28/2013

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - This comment is in regards to a reception desk and is for information purposes. This will be verified on inspection.
Bldg - Doors - Door hardware
Corrective Action Required
05/28/2013

2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate. Action required - This comment is for information purposes and will be verified on inspection.
Licensed Contractors Approved 05/28/2013 05/28/2013
Mike Weisenborn
Fire Plan Review Approved 05/28/2013 05/17/2013
Brian Austerman
Address numbers required
Corrective Action Required
05/17/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on front and rear doors, if not existing
Portable fire extinguishers - general
Corrective Action Required
05/17/2013

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one 2A10B:C fire extinguisher. Verified at inspection
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $65.36 $65.36 Paid 05/28/2013
$65.36
8331507-Sewer Connection Fee $60.00 $60.00 Paid 05/28/2013
$60.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 6/10/2013 6/10/2013 at 12:00 AM 06/10/2013
Above Ceiling Inspection Failed 6/19/2013 (8:00 to 5:00) 6/19/2013 at 12:00 AM 06/19/2013
Misc
Corrective Action Required
06/19/2013
SEISMIC TIE WIRES AT LAY-IN ELECTRICAL LIGHTING LUMINAIRES: PROVIDE TWO SLACK WIRE TIES PER FIXTURE FROM STRUCTURE TO TWO OPPOSITE DIAGONAL CORNERS. TIE BOTH ENDS WITH TWO FULL WRAPS MINIMUM.
Misc
Corrective Action Required
06/19/2013
NEC 314.16; IRC E3905.13 ELECTRICAL BOX FILL: CHECK ALL ELECTRICAL BOXES FOR BOX FILL RESTRICTIONS. EXAMPLE -- CORRIDOR NORTH END
Misc
Corrective Action Required
06/19/2013
UNTERMINATED ELECTRICAL CONDUCTORS. TERMINATE OR CLARIFY.
Misc
Corrective Action Required
06/19/2013
NEC 334-10 SUPPORT OF MC ELECTRICAL CABLE: 6' MAX INTERVALS
Misc
Corrective Action Required
06/19/2013
ARE LIGHTING FIXTURES AT PERMANENT LOCATIONS? SOME ARE AT PARTITIONS.
Misc
Corrective Action Required
06/19/2013
PEX WATER TUBING IN FURNACE ROOM NOT SECURED TO STRUCTURE; ALSO LAYS AGAINST FURNACE EXHAUST VENT PIPE.
Above Ceiling Inspection Passed 6/27/2013 6/27/2013 at 12:00 AM 06/27/2013
Misc
Resolved
06/27/2013
SEISMIC TIE WIRES AT LAY-IN ELECTRICAL LIGHTING LUMINAIRES: PROVIDE TWO SLACK WIRE TIES PER FIXTURE FROM STRUCTURE TO TWO OPPOSITE DIAGONAL CORNERS. TIE BOTH ENDS WITH TWO FULL WRAPS MINIMUM.
Misc
Resolved
06/27/2013
NEC 314.16; IRC E3905.13 ELECTRICAL BOX FILL: CHECK ALL ELECTRICAL BOXES FOR BOX FILL RESTRICTIONS. EXAMPLE -- CORRIDOR NORTH END
Misc
Resolved
06/27/2013
UNTERMINATED ELECTRICAL CONDUCTORS. TERMINATE OR CLARIFY.
Misc
Resolved
06/27/2013
NEC 334-10 SUPPORT OF MC ELECTRICAL CABLE: 6' MAX INTERVALS
Misc
Resolved
06/27/2013
ARE LIGHTING FIXTURES AT PERMANENT LOCATIONS? SOME ARE AT PARTITIONS.
Misc
Resolved
06/27/2013
PEX WATER TUBING IN FURNACE ROOM NOT SECURED TO STRUCTURE; ALSO LAYS AGAINST FURNACE EXHAUST VENT PIPE.
Occupancy Inspection - Fire Passed 7/2/2013 at 12:00 AM 07/02/2013
Occupancy Inspection - Codes Commercial Full C of O 7/2/2013 7/2/2013 at 12:00 AM 07/02/2013
Occupancy Inspection - Codes Commercial Full C of O 07/03/2013
Occupancy Inspection - Fire Passed 07/03/2013
Documents & Images
Date Uploaded File Type Document Name
05/28/2013 Letter Plan Review Conditions
05/28/2013 Letter Building Permit
06/10/2013 Letter Inspection Summary
06/19/2013 Letter Inspection Summary
06/27/2013 Letter Fire Building Plan Review
06/27/2013 Letter Inspection Summary
07/02/2013 Letter Field Certificate of Occupancy
07/03/2013 Letter Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home