Review Type |
Outcome |
Est. Completion Date |
Completed |
Licensed Contractors
|
Approved
|
05/31/2013
|
05/28/2013
|
|
Mike Weisenborn
|
|
License contractors
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances.
Action required - Provide the names of the licensed electrical and plumbing contractors. This information is required for permit approval.
|
|
|
Building Plan Review
|
Approved with Conditions
|
05/22/2013
|
05/21/2013
|
|
Mike Weisenborn
|
|
Mech - Hoods required
2006 IMC 507.2 - Where required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliances under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed.
Action required - Provide specifications on the hood to be installed over the chefs station. Provide details on the installation of the hood.
Mike Weisenborn 04/23/2013 2:34 PM - The information provided does not provide details on the hood or the duct to be installed. Provide additional information.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
Mech - Clearance for Type I hood
Corrective Action Required
2003 IMC 507.9 - Clearance for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm). Exception: Clearance shall not be required from gypsum wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum wallboard over an area extending not less than 18 inches (457 mm) in all directions from the hood.
Action required - To be verified on inspection.
|
|
Misc
Corrective Action Required
2006 IMC Section 506.3 - Ducts serving Type I hoods. Type I exhaust ducts shall be independent of all other exhaust systems except as provided in Section 506.3.5. Commercial kitchen duct systems serving Type I hoods shall be designed, constructed and installed in accordance with Sections 506.3.1 through 506.3.12.3.
Action required - To be verified on inspection.
|
|
Misc
Corrective Action Required
2006 IMC Section 506.5 - Exhaust equipment - Exhaust equipment, including fans and grease reservoirs, shall comply with Sections 506.5.1 through 506.5.5 and shall be of an approved design or shall be listed for the application.
Action required - To be verified on inspection.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
05/22/2013
|
05/17/2013
|
|
Brian Austerman
|
|
Type I hood - Where required
Corrective Action Required
2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Provide specifications on Type 1 hood and show manual pull location on plans. Pull shall be no closer than 10' and no further than 20'
Plans received and approved
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide sprinkler plans for approval
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call 969-1300 to schedule hood testing
|
|
|
Fire Plan Review
|
Rejected
|
04/23/2013
|
04/24/2013
|
|
Brian Austerman
|
|
Type I hood - Where required
Corrective Action Required
2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Provide specifications on Type 1 hood and show manual pull location on plans. Pull shall be no closer than 10' and no further than 20'
|
|
|
Building Plan Review
|
Rejected
|
04/23/2013
|
04/23/2013
|
|
Mike Weisenborn
|
|
Mech - Hoods required
Corrective Action Required
2006 IMC 507.2 - Where required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliances under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed.
Action required - Provide specifications on the hood to be installed over the chefs station. Provide details on the installation of the hood.
Mike Weisenborn 04/23/2013 2:34 PM - The information provided does not provide details on the hood or the duct to be installed. Provide additional information.
|
|
Health Dept Review
For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required - This comment is for information purposes.
Action required - Provide documentation of approval from the Health Department for the alterations.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
|
Building Plan Review
|
Rejected
|
04/08/2013
|
04/05/2013
|
|
Mike Weisenborn
|
|
Mech - Hoods required
Corrective Action Required
2006 IMC 507.2 - Where required. A Type I or Type II hood shall be installed at or above all commercial cooking appliances in accordance with Sections 507.2.1 and 507.2.2. Where any cooking appliances under a single hood requires a Type I hood, a Type I hood shall be installed. Where a Type II hood is required, a Type I or Type II hood shall be installed.
Action required - Provide specifications on the hood to be installed over the chefs station. Provide details on the installation of the hood.
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required - This comment is for information purposes.
Action required - Provide documentation of approval from the Health Department for the alterations.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
|
Fire Plan Review
|
Rejected
|
04/08/2013
|
04/01/2013
|
|
Brian Austerman
|
|
Type I hood - Where required
Corrective Action Required
2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Provide information on the charbroiler, will there be grease laden vapors and if so wubmit plans for a type 1 (protected) hood
|
|
Misc
Corrective Action Required
Provide detail on fuel types to be used for the charbroiler, gas and or solid fuel
|
|
|