Permit Application Status

PRCOM20122337


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20122337
Building Permit - Commercial
Certificate of Occupancy
GALE COMMUNITIES INC
CHANGE OF TENANT
TENANT FINISH FOR OFFICE
10/19/2012
11/07/2012
10/15/2014
12/07/2012
Locations
Contacts
A L HUBER INC, Address:10770 EL MONTE, Phone:(913) 341-4880  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 210, Phone:(816) 645-2336  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
GALE COMMUNITIES INC, Address:400 SW LONGVIEW BLVD STE 105  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 11/26/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
11/26/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received Nov. 21, 2012.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
11/26/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing system shall have documentation of a current annual inspection. Confirmed at final occupancy inspection.
Installation acceptance testing
Corrective Action Required
11/26/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be copmpleted at the final occupancy inspection.
Internal Plan Review (Res) Approved 10/31/2012 10/30/2012
Mike Weisenborn
True
License Tax Codes Approved 10/31/2012 10/30/2012
Mike Weisenborn
Building Plan Review Approved 10/31/2012 10/30/2012
Mike Weisenborn
Fire Plan Review Approved with Conditions 10/31/2012 10/24/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
10/24/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide as built drawings for modifications needed to maintain sprinkler coverage in the space.
Construction documents for fire alarm systems
Corrective Action Required
10/24/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. The location of alarm notification appliances were not shown. Verified at inspection.
Installation acceptance testing
Corrective Action Required
10/24/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Alarm notification appliances will be tested at time of occupancy inspection.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/24/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing sprinkler system shall have documentation of a current annual inspection. Verified at inspection.
Misc
Corrective Action Required
10/24/2012

Provide a suite designation on the door if space is accessed from a public corridor.
Zoning Review Approved 10/31/2012 10/19/2012
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $78.43 $78.43 Paid 11/07/2012
$78.43
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Above Ceiling Inspection Passed 11/26/2012 (8:00 to 5:00) 11/26/2012 at 12:00 AM 11/26/2012
In-wall Inspection Passed 11/26/2012
Occupancy Inspection - Codes Commercial Full C of O 12/7/2012 12/7/2012 at 12:00 AM 12/07/2012
Occupancy Inspection - Fire Passed 12/7/2012 at 12:00 AM 12/07/2012
Misc
Corrective Action Required
12/07/2012
suite was built out as a white box finish, no dividers , furniture, fixtures, or other finishes were in place as per the plans as per plans
Documents & Images
Date Uploaded File Type Document Name
10/30/2012 Letter Plan Review Conditions
11/07/2012 Letter Building Permit
11/26/2012 Letter Fire (Sprinkler) Plan Review
11/26/2012 Letter Inspection Summary
12/07/2012 Letter Field Certificate of Occupancy
12/07/2012 Letter Fire Loss Reduction Form
12/10/2012 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire (Sprinkler) Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home