Permit Application Status

PRCOM20120721


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20120721
Building Permit - Commercial
Certificate of Occupancy
JAMS LEES BUSTER LLC
CHANGE OF TENANT
TENANT FINISH
04/05/2012
05/04/2012
10/15/2012
06/29/2012
Locations
Contacts
VISION RENOVATIONS, Address:906 STONEBROOK LN, Phone:(816) 277-4767  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ABSOLUTE ELECTRIC, Address:3220 S PONCA DR  
SCHOELLER PLUMBING INC, Address:PO BOX 1268, Phone:(816) 628-3848  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
JAMS LEES BUSTER LLC, Address:605 W 47TH ST STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
License Tax Codes Approved 05/11/2012 05/07/2012
Mike Weisenborn
Internal Plan Review (Res) Approved 05/11/2012 05/04/2012
Codes Admin
True
Building Plan Review Approved 05/01/2012 04/30/2012
Mike Weisenborn
Business License
Resolved
04/30/2012

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor prior to permit approval.
License contractors
Resolved
04/30/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the name of the mechanical, electrical and plumbing contractors prior to permit approval.
Bldg - Occupant load calculations - Areas without fixed seats
Resolved
04/30/2012

2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - It has been the practice of the Lee's Summit Codes Administration Department to base the occupant load of a beauty/barber shop on the number of cutting stations plus the number of seats provided in the waiting area. Make needed corrections to the calculated occupant load.
Plumb - Separate facilities
Resolved
04/30/2012

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - As the occupant load is greater than 15 separate men's and women's restrooms are required. Make needed corrections.
Fire Plan Review Approved 05/01/2012 04/30/2012
Brian Austerman
Portable fire extinguishers - general
Corrective Action Required
04/30/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Verified at inspection
Internal Plan Review (Res) Rejected 04/17/2012 04/18/2012
Mike Weisenborn
Fire Plan Review Approved 04/17/2012 04/17/2012
Jim Eden
Portable fire extinguishers - general
Corrective Action Required
04/17/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of 1, 2A:10B:C fire extinguisher in a conspicuous location. Verified at inspection.
Address numbers required
Corrective Action Required
04/17/2012

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Verified at inspection.
Building Plan Review Rejected 04/17/2012 04/13/2012
Mike Weisenborn
Business License
Corrective Action Required
04/13/2012

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor prior to permit approval.
License contractors
Corrective Action Required
04/13/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the name of the mechanical, electrical and plumbing contractors prior to permit approval.
Bldg - Occupant load calculations - Areas without fixed seats
Corrective Action Required
04/13/2012

2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - It has been the practice of the Lee's Summit Codes Administration Department to base the occupant load of a beauty/barber shop on the number of cutting stations plus the number of seats provided in the waiting area. Make needed corrections to the calculated occupant load.
Plumb - Separate facilities
Corrective Action Required
04/13/2012

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - As the occupant load is greater than 15 separate men's and women's restrooms are required. Make needed corrections.
Zoning Review Approved 04/17/2012 04/13/2012
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $224.68 $224.68 Paid 05/04/2012
8331507-Sewer Connection Fee $270.00 $270.00 Paid 05/04/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 5/9/2012 5/9/2012 at 12:00 AM 05/09/2012
Miscellaneous Inspection Partial 5/11/2012 at 12:00 AM 05/11/2012
Misc
Partial Correction
05/11/2012
JB JOBSITE VISIT W/ G.C. TO DISCUSS GROUND RULES AND THE NEED FOR COORDINATION OF SEPARATE PERMITS (ELECT SVC, RTU's...)
In-wall Inspection Failed 5/31/2012 6/25/2012 at 12:00 AM 05/31/2012
Misc
Corrective Action Required
05/31/2012
IPC 305.8 PROTECTION FROM PENETRATION OF PVC PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS. CHECK ALL.
Misc
Corrective Action Required
05/31/2012
ENSURE ALL ELECTRICAL BOX STAND-OFFS CONTACT STRUCTURE FOR BOX SOLIDITY
Misc
Corrective Action Required
05/31/2012
NEC 330.30: MC ELECTRICAL CABLE NOT SECURED WITHIN 12" OF ENTRY TO SOME BOXES -- COLORADO JIM DOES NOT RESIST TUGGING
In-wall Inspection Failed 6/4/2012 6/1/2012 at 12:00 AM 06/01/2012
Misc
Resolved
06/01/2012
IPC 305.8 PROTECTION FROM PENETRATION OF PVC PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS. CHECK ALL.
Misc
Corrective Action Required
05/31/2012
ENSURE ALL ELECTRICAL BOX STAND-OFFS CONTACT STRUCTURE FOR BOX SOLIDITY
Misc
Corrective Action Required
05/31/2012
NEC 330.30: MC ELECTRICAL CABLE NOT SECURED WITHIN 12" OF ENTRY TO SOME BOXES -- COLORADO JIM DOES NOT RESIST TUGGING
In-wall Inspection Passed 6/4/2012 at 12:00 AM 06/04/2012
Misc
Resolved
06/04/2012
ENSURE ALL ELECTRICAL BOX STAND-OFFS CONTACT STRUCTURE FOR BOX SOLIDITY
Misc
Resolved
06/04/2012
NEC 330.30: MC ELECTRICAL CABLE NOT SECURED WITHIN 12" OF ENTRY TO SOME BOXES -- COLORADO JIM DOES NOT RESIST TUGGING
Above Ceiling Inspection Not Ready 6/25/2012 at 12:00 AM 06/25/2012
Above Ceiling Inspection Failed 6/26/2012 6/26/2012 at 12:00 AM 06/26/2012
Misc
Corrective Action Required
06/26/2012
PVC PIPE NOT ALLOWED IN CEILING HVAC PLENUM SPACE
Above Ceiling Inspection Passed 6/27/2012 6/27/2012 at 12:00 AM 06/27/2012
Misc
Resolved
06/27/2012
PVC PIPE NOT ALLOWED IN CEILING HVAC PLENUM SPACE
Miscellaneous Inspection Passed 6/27/2012 at 12:00 AM 06/27/2012
Misc
Resolved
06/27/2012
JB JOBSITE VISIT W/ G.C. TO DISCUSS GROUND RULES AND THE NEED FOR COORDINATION OF SEPARATE PERMITS (ELECT SVC, RTU's...)
Occupancy Inspection - Codes Commercial Temporary C of O 6/28/2012 6/28/2012 at 12:00 AM 06/28/2012
Misc
Corrective Action Required
06/28/2012
NEC 408.4 ELECTRICAL PANEL SCHEDULE / LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
06/28/2012
ALUMINUM/GLASS STROEFRONT MODIFICATIONS IN PROGRESS. ENSURE ALL GLAZING IS ETCHED "TEMPERED"
Misc
Corrective Action Required
06/28/2012
RESOLVE FIRE DEPARTMENT ISSUE(S)
Misc
Corrective Action Required
06/28/2012
SEAL MOP SINK TO WALL AND FLOOR
Occupancy Inspection - Fire Temporary C of O 6/28/2012 at 12:00 AM 06/28/2012
Occupancy Inspection - Fire Passed 6/29/2012 at 12:00 AM 06/29/2012
Corrective Action Required
06/29/2012
all previous violations have been resolved
Occupancy Inspection - Codes Commercial Full C of O 6/29/2012 6/29/2012 at 12:00 AM 06/29/2012
Misc
Resolved
06/29/2012
NEC 408.4 ELECTRICAL PANEL SCHEDULE / LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Resolved
06/29/2012
ALUMINUM/GLASS STROEFRONT MODIFICATIONS IN PROGRESS. ENSURE ALL GLAZING IS ETCHED "TEMPERED"
Misc
Resolved
06/29/2012
RESOLVE FIRE DEPARTMENT ISSUE(S)
Misc
Resolved
06/29/2012
SEAL MOP SINK TO WALL AND FLOOR
Documents & Images
Date Uploaded File Type Document Name
04/18/2012 Letter Plan Review Conditions
05/04/2012 Letter Building Permit
05/09/2012 Letter Inspection Summary
05/31/2012 Letter Inspection Summary
06/01/2012 Letter Inspection Summary
06/04/2012 Letter Inspection Summary
06/04/2012 Letter Inspection Summary
06/04/2012 Letter Inspection Summary
06/26/2012 Letter Inspection Summary
06/27/2012 Letter Inspection Summary
06/28/2012 Letter Temporary Certificate of Occupancy
06/28/2012 Letter Fire Loss Reduction Form
06/29/2012 Letter Fire Loss Reduction Form
06/29/2012 Letter Field Certificate of Occupancy
07/02/2012 Letter Final Certificate of Occupancy
07/19/2012 Drawing DOC071912-07192012152105.pdf
06/25/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
07/02/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home