Permit Application Status

PRCOM20113727


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20113727
Building Permit - Commercial
Certificate of Occupancy
EMERGENT CARE ASSET HOLDINGS LLC
ADDITION COMMERCIAL
BUILDING ADDITION
07/11/2011
08/04/2011
01/21/2012
04/18/2012
Locations
Contacts
THE HOLLIS & MILLER GROUP, Address:1828 WALNUT ST STE 922, Phone:(816) 525-5600  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
CENTRAL PLUMBING HTG & A/C INC, Address:P O BOX 218, Phone:(816) 942-6355  
CITY WIDE HEATING & COOLING INC, Address:2824 ROE LANE, Phone:(913) 384-6006  
A L HUBER INC, Address:10770 EL MONTE, Phone:(913) 341-4880  
EMERGENT CARE ASSET HOLDINGS LLC, Address:3074 SW GRANDSTAND CIR  
EMERGENT CARE ASSET HOLDINGS LLC, Address:2741 NE MCBAINE DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 03/26/2012
Jim Eden
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
03/26/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. The existing system shall have documentation of a current annual inspection.
Construction documents for fire alarm systems
Corrective Action Required
03/26/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Plans received March 22, 2012.
Installation acceptance testing
Corrective Action Required
03/26/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Scheduled for March 27, 2012.
Misc
Corrective Action Required
03/26/2012

Duct detection was shown on the plans. Activation of a duct detector shall bsent a supervisory signal only to the panel without activation of the the interior horn strobes. The signal shall NOT be transmitted to central station as a fire alarm. Verified at inspection.
Internal Plan Review (Res) Approved 08/04/2011 08/03/2011
Mike Weisenborn
Building Plan Review Approved 08/04/2011 08/03/2011
Mike Weisenborn
Misc
Corrective Action Required
08/02/2011

Detailed plans for the retaining wall have not been provided. Action required - Provide two (2) copies of the construction plans for the retaining wall which have been signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit issuance but shall be provided prior to construction of the wall.
Bldg - Toilet rooms - Floor surface and walls
Resolved
08/03/2011

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - The finish schedule shows 4 inch base in the restrooms. Make needed corrections.
Accessibility - Lavatories and sinks - Clear floor space
Resolved
08/03/2011

ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.) Action required - Detail on Sheet L12 does not meet this requirement. Make needed corrections.
Accessibility - Maneuvering Clearance at Doors.
Resolved
08/03/2011

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear space is not provided on the pull side of the exam room doors.
Bldg - Accessibility - Means of egress - Continuity and components 1007.2
Resolved
08/03/2011

2006 IBC 1007.2 - Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components: 1. Accessible routes complying with Section 1104. 2. Stairways within vertical exit enclosures complying with Sections 1007.3 and 1020. 3. Exterior exit stairways complying with Sections 1007.3 and 1023. 4. Elevators complying with Section 1007.4. 5. Platform lifts complying with Section 1007.5. 6. Horizontal exits complying with Section 1021. 7. Ramps complying with Section 1010. 8. Areas of refuge complying with Section 1007.6. See actual code for possible exceptions. Action required - Provide details for the accessible means of egress from the second floor.
Bldg - Elevators - Emergency signs
Corrective Action Required
08/02/2011

2006 IBC 3002.3 - Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways, and not to use the elevator in case of fire. The sign shall read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRS. The emergency sign shall not be required for elevators that are part of an accessible means of egress complying with Section 1007.4. Action required - This will be verified on inspection.
Misc
Corrective Action Required
08/02/2011

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required - This comment is for information purposes.
Misc
Corrective Action Required
08/02/2011

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration Department prior to the state insection so that a member of the staff can witness the inspection. Action required - This comment is for information purposes.
Bldg - Accessibility - Drinking fountains minimum number
Resolved
08/03/2011

2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. Action required - Make needed corrections.
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
08/02/2011

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Misc
Resolved
08/03/2011

2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Action required - Provide additional information.
Final Development Plan Review Approved 08/05/2011 08/03/2011
Mike Weisenborn
Fire Plan Review Approved 08/04/2011 08/02/2011
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
08/02/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for alarm system modification.
Installation acceptance testing
Corrective Action Required
08/02/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule alarm test. Testing shall be completed before or after regular business hours.
Portable fire extinguishers - general
Resolved
08/02/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide two minimum 2A:10B:C fire extinguishers on each floor. The second floor extinguishers shall be located near the doors to the stairs. Locate the first floor extinguishers near the exits.
Misc
Resolved
08/02/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required: Provide exterior emergency lighting over the front door.
Misc
Resolved
08/02/2011

The elevator shall be the requirements of the Missouri Safety Rules and Regulations.
Internal Plan Review (Res) Rejected 07/25/2011 07/25/2011
Mike Weisenborn
Building Plan Review Rejected 07/25/2011 07/25/2011
Mike Weisenborn
Misc
Corrective Action Required
07/25/2011

Detailed plans for the retaining wall have not been provided. Action required - Provide two (2) copies of the construction plans for the retaining wall which have been signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit issuance but shall be provided prior to construction of the wall.
Bldg - Toilet rooms - Floor surface and walls
Corrective Action Required
07/25/2011

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - The finish schedule shows 4 inch base in the restrooms. Make needed corrections.
Accessibility - Lavatories and sinks - Clear floor space
Corrective Action Required
07/25/2011

ICC/ANSI A117.1 2003 606.2 - Clear floor space. A clear floor space complying with Section 305.3, positioned for forward approach, shall be provided. Knee and toe clearance complying with Section 306 shall be provided. The dip of the overflow shall not be considered in determining knee and toe clearance. (See code for possible exceptions.) Action required - Detail on Sheet L12 does not meet this requirement. Make needed corrections.
Accessibility - Maneuvering Clearance at Doors.
Corrective Action Required
07/25/2011

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear space is not provided on the pull side of the exam room doors.
Bldg - Accessibility - Means of egress - Continuity and components 1007.2
Corrective Action Required
07/25/2011

2006 IBC 1007.2 - Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components: 1. Accessible routes complying with Section 1104. 2. Stairways within vertical exit enclosures complying with Sections 1007.3 and 1020. 3. Exterior exit stairways complying with Sections 1007.3 and 1023. 4. Elevators complying with Section 1007.4. 5. Platform lifts complying with Section 1007.5. 6. Horizontal exits complying with Section 1021. 7. Ramps complying with Section 1010. 8. Areas of refuge complying with Section 1007.6. See actual code for possible exceptions. Action required - Provide details for the accessible means of egress from the second floor.
Bldg - Elevators - Emergency signs
Corrective Action Required
07/25/2011

2006 IBC 3002.3 - Emergency signs. An approved pictorial sign of a standardized design shall be posted adjacent to each elevator call station on all floors instructing occupants to use the exit stairways, and not to use the elevator in case of fire. The sign shall read: IN FIRE EMERGENCY, DO NOT USE ELEVATOR. USE EXIT STAIRS. The emergency sign shall not be required for elevators that are part of an accessible means of egress complying with Section 1007.4. Action required - This will be verified on inspection.
Misc
Corrective Action Required
07/25/2011

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required - This comment is for information purposes.
Misc
Corrective Action Required
07/25/2011

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Contact the Lee's Summit Codes Administration Department prior to the state insection so that a member of the staff can witness the inspection. Action required - This comment is for information purposes.
Bldg - Accessibility - Drinking fountains minimum number
Corrective Action Required
07/25/2011

2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. Action required - Make needed corrections.
Accessibility - Refrigerator/Freezer - General requirements
Corrective Action Required
07/25/2011

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Misc
Corrective Action Required
07/25/2011

2005 NEC 517.13 - Grounding of receptacles and fixed electric equipment in patient care areas. Wiring in patient care areas shall comply with 517.13(A) and 517.13(B). Action required - Provide additional information.
License Tax Codes Approved 07/25/2011 07/25/2011
Mike Weisenborn
Fire Plan Review Rejected 07/25/2011 07/22/2011
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
07/22/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for alarm system modification.
Installation acceptance testing
Corrective Action Required
07/22/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule alarm test. Testing shall be completed before or after regular business hours.
Portable fire extinguishers - general
Corrective Action Required
07/22/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide two minimum 2A:10B:C fire extinguishers on each floor. The second floor extinguishers shall be located near the doors to the stairs. Locate the first floor extinguishers near the exits.
Misc
Corrective Action Required
07/22/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required: Provide exterior emergency lighting over the front door.
Misc
Corrective Action Required
07/22/2011

The elevator shall be the requirements of the Missouri Safety Rules and Regulations.
Historical Preservation Review Approved 07/25/2011 07/12/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Addition to Commercial $6,048.04 $6,048.04 Paid 08/04/2011
8331507-Sewer Connection Fee $720.00 $720.00 Paid 08/04/2011
8331506-EFHB Maybrook, Full $1,022.64 $1,022.64 Paid 08/04/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Electrical Inspection - Commercial Partial 10/12/2011 at 12:00 AM 10/12/2011
Footing Inspection - Commercial Partial 11/4/2011 (1:30) 1/24/2012 at 12:00 AM 11/04/2011
Misc
Corrective Action Required
11/04/2011
GADE BEAM & COLUMN PADS APPROVED BELOW: -LINE K/7 TO K/12 & APPROX. 5 FT FROM CORNER
Footing Inspection - Commercial Partial 11/7/2011 (11:30) 11/7/2011 at 12:00 AM 11/07/2011
Misc
Corrective Action Required
11/04/2011
GRADE BEAM & COLUMN PADS APPROVED BELOW: -LINE M/1 TO M/6 & APPROX. 5 FT FROM CORNER -COLUMN PADS: D/3,G/3,K/3,H/1,E/1,C/2
Footing Inspection - Commercial Partial 11/9/2011 11/9/2011 at 12:00 AM 11/09/2011
Misc
Corrective Action Required
11/07/2011
GRADE BEAM & COLUMN PADS APPROVED BELOW: -LINE M/1 TO M/6 & APPROX. 5 FT FROM CORNER -COLUMN PADS: C/2/4,D/3,E/1,F/3,G/3,H/1,K/3
Footing Inspection - Commercial Partial 11/10/2011 (1:00) 11/10/2011 at 12:00 AM 11/10/2011
Misc
Corrective Action Required
11/09/2011
-EXTERIOR GRADE BEAM & COLUMN PADS APPROVED FROM NE CORNER TO A/4 PAD -INTERIOR COLUMN PADS: C/2/4,D/3,E/1,F/3,G/3,H/1,K/3
Footing Inspection - Commercial Partial 11/15/2011 (2:30) 11/15/2011 at 12:00 AM 11/15/2011
Misc
Corrective Action Required
11/10/2011
-EXTERIOR GRADE BEAM & COLUMN PADS APPROVED FROM NE CORNER TO A/4 PAD -INTERIOR COLUMN PADS: C/2/4,D/3,E/1,F/3,G/3,H/1,K/3 -ELEVATOR PIT BASE
Footing Inspection - Commercial Partial 11/16/2011 (1:00) 11/16/2011 at 12:00 AM 11/16/2011
Misc
Corrective Action Required
11/15/2011
-EXTERIOR GRADE BEAM & COLUMN PADS APPROVED FROM NE CORNER TO A/4 PAD -INTERIOR COLUMN PADS: C/2/4,D/3,E/1,F/3,G/3,H/1,K/3 -ELEVATOR PIT BASE& WALL
Underslab Plumbing Inspection - Commercial Partial 11/16/2011 at 12:00 AM 11/16/2011
Misc
Corrective Action Required
11/16/2011
UNDERSLAB PLUMBING OK BELOW: -ALL UNDERSLAB PLUMBING FROM LINE F TO M
Foundation Inspection - Commercial Partial 11/17/2011 at 12:00 AM 11/17/2011
Misc
Corrective Action Required
11/17/2011
-BOTTOM GEOGRID INSTALLED
Underslab Plumbing Inspection - Commercial Passed 11/17/2011 at 12:00 AM 11/17/2011
Misc
Resolved
11/17/2011
UNDERSLAB PLUMBING OK BELOW: -ALL UNDERSLAB PLUMBING FROM LINE F TO M
Foundation Inspection - Commercial Partial 11/17/2011 (1:30) 11/17/2011 at 12:00 AM 11/17/2011
Misc
Corrective Action Required
11/17/2011
RETAINING WALL-CONSTRUCTION IN PROGRESS-OK
Footing Inspection - Commercial Passed 11/18/2011 at 12:00 AM 11/18/2011
Misc
Resolved
11/18/2011
-EXTERIOR GRADE BEAM & COLUMN PADS APPROVED FROM NE CORNER TO A/4 PAD -INTERIOR COLUMN PADS: C/2/4,D/3,E/1,F/3,G/3,H/1,K/3 -ELEVATOR PIT BASE& WALL
Foundation Inspection - Commercial Passed 11/18/2011 at 12:00 AM 11/18/2011
Misc
Resolved
11/18/2011
RETAINING WALL-CONSTRUCTION IN PROGRESS-OK
In-wall Inspection Partial 1/9/2012 at 12:00 AM 01/09/2012
Misc
Corrective Action Required
01/09/2012
OK TO COVER BELOW: -MECHANICAL UNITS SCREEN WALLS
In-wall Inspection Partial 1/17/2012 at 12:00 AM 01/17/2012
Misc
Corrective Action Required
01/09/2012
OK TO COVER BELOW: -MECHANICAL UNITS SCREEN WALLS CORECTIONS REQUIRED: -PROTECT PLUMBING WITHIN 1.5" OF BOTTOM TRACK -RM 100/103/104/135 NOT READY
In-wall Inspection Partial 1/18/2012 at 12:00 AM 01/18/2012
Misc
Corrective Action Required
01/17/2012
OK TO COVER BELOW: -MECHANICAL UNITS SCREEN WALLS -1ST FLOOR IN-WALL OK, EXCEPT RM 100/103/104/135 NOT READY
In-wall Inspection Partial 1/23/2012 at 12:00 AM 01/23/2012
Misc
Corrective Action Required
01/18/2012
OK TO COVER BELOW: -MECHANICAL UNITS SCREEN WALLS -1ST FLOOR IN-WALL -1 HR WALL IN ELEVATOR EQUIPMENT RM- OK TO ROCK
Gas Piping Inspection - Commercial Passed 1/24/2012 at 12:00 AM 01/24/2012
In-wall Inspection Partial 1/24/2012 at 12:00 AM 01/24/2012
Misc
Corrective Action Required
01/23/2012
OK TO COVER BELOW: -MECHANICAL UNITS SCREEN WALLS -1ST FLOOR IN-WALL -1 HR WALL IN ELEVATOR EQUIPMENT RM- OK TO ROCK -2ND FL-COMPLETE PLUMBING AT RESTROOM AND JANITOR SINK; INSTALL BLOCKINGS FOR VERTICAL GRAB BARS IN RESTROOMS; FILL IN GAP WITH FIREBLOCKING MATERIAL AT ALL FLOOR PENETRATIONS; DUCTS PENETRATION OF FLOOR SHALL BE DRAFTSTOPPED
In-wall Inspection Partial 1/26/2012 at 12:00 AM 01/26/2012
Misc
Corrective Action Required
01/24/2012
OK TO COVER BELOW: -MECHANICAL UNITS SCREEN WALLS -1ST & 2ND FLOOR IN-WALL -1 HR WALL IN ELEVATOR EQUIPMENT RM- OK TO ROCK
Sewer Service Inspection Passed 1/31/2012 1/31/2012 at 12:00 AM 01/31/2012
Above Ceiling Inspection Partial 2/10/2012 at 12:00 AM 02/10/2012
Misc
Corrective Action Required
02/10/2012
-OK TO DROP BORDER TILES ABOVE RESTROOMS AND EXAM ROOMS, 1ST FLOOR
Above Ceiling Inspection Partial 2/14/2012 at 12:00 AM 02/14/2012
Misc
Corrective Action Required
02/10/2012
OK TO DROP TILES AT FOLLOWING SPACES EXCEPT LEAVE OUT TILE TO PROVIDE VIEW FROM FLOOR OF HVAC FLEX CONNECTORS TO DIFFUSERS WHICH MUST BE SECURED AT INNER LAYER AND AT OUTER LAYER PER AIR DIFFUSION COUNCIL/SMACNA: 107-111; 113; 116; 118-124; 127; 130;
Above Ceiling Inspection Partial 2/24/2012 at 12:00 AM 02/24/2012
Misc
Corrective Action Required
02/14/2012
OK TO DROP TILES AT FOLLOWING SPACES: -1ST FLOOR EXCEPT AT CORRIDOR AND NURSING STATION -2ND FL OK EXCEPT AT LOCATION OF RETURN AIR NOT INSTALLED
Underground Electrical Inspection - Commercial Partial 2/28/2012 2/28/2012 at 12:00 AM 02/28/2012
Misc
Corrective Action Required
02/28/2012
UNDERGROUND ELECTRICAL TO LIGHT POLES-PARTIAL
Above Ceiling Inspection Partial 2/29/2012 at 12:00 AM 02/29/2012
Misc
Corrective Action Required
02/24/2012
OK TO DROP TILES AT FOLLOWING SPACES: -1ST FLOOR EXCEPT AT CORRIDOR AND NURSING STATION
Above Ceiling Inspection Partial 3/1/2012 at 12:00 AM 03/01/2012
Misc
Corrective Action Required
02/29/2012
ABOVE CEILING APPROVED EXCEPT AT ENCLOSED STAIRWAY.
In-wall Inspection Passed 03/01/2012
Misc
Resolved
03/01/2012
OK TO COVER BELOW: -MECHANICAL UNITS SCREEN WALLS -1ST & 2ND FLOOR IN-WALL -1 HR WALL IN ELEVATOR EQUIPMENT RM- OK TO ROCK
Gas Piping Inspection - Commercial Passed 03/01/2012
Rated Assembly Inspection Passed 3/9/2012 at 12:00 AM 03/09/2012
Above Ceiling Inspection Passed 3/9/2012 at 12:00 AM 03/09/2012
Misc
Resolved
03/09/2012
ABOVE CEILING APPROVED EXCEPT AT ENCLOSED STAIRWAY.
Underground Electrical Inspection - Commercial Passed 03/09/2012
Misc
Resolved
03/09/2012
UNDERGROUND ELECTRICAL TO LIGHT POLES-PARTIAL
Underground Electrical Inspection - Commercial Passed 3/12/2012 3/12/2012 at 12:00 AM 03/12/2012
Rated Assembly Inspection Passed 3/22/2012 at 12:00 AM 03/22/2012
Rated Assembly Inspection Passed 3/23/2012 at 12:00 AM 03/23/2012
Alarm Test Passed 3/27/2012 at 10:00 AM 03/27/2012
Occupancy Inspection - Fire Passed 3/27/2012 at 12:00 AM 03/27/2012
Misc
Corrective Action Required
03/27/2012
Occupancy inspection, PRCOM20113727 A copy of the elevator certification test to be obtained after completion by state inspectors. OK to occupy once cleared through codes administration
Occupancy Inspection - Codes Commercial Temporary C of O 3/27/2012 at 12:00 AM 03/27/2012
Misc
Corrective Action Required
03/27/2012
OBTAIN APPROVAL FROM THE FOLLOWING: -PLANNING AND DEVELOPMENT DEPARTMENT -PUBLIC WORKS
Misc
Corrective Action Required
03/27/2012
-COMPLETE EXTERIOR: FLASHING, SEAL EXTERIOR WALL PENETRATIONS -INSTALL TEMPERED GLASS ADJACENT BY STAIR WITHIN 5 FT OF FLOOR (WEST STAIR) -INSTALL 2ND FLOOR RESTROOM SIGNAGE -PAINT GAS PIPING EXPOSED TO WEATHER FOR PROTECTION
Occupancy Inspection - Planning Temporary C of O 3/27/2012 at 12:00 AM 03/27/2012
Carried Forward
03/29/2012
Required for Final Certificate of Occupancy: The 5ft concrete sidewalk along McBaine Drive shall be extended to the south property line as shown on the approved Final Development Plan.
Partial Correction
03/29/2012
Required for Final Certificate of Occupancy: All landscaping material and sod shall be installed.
Resolved
03/29/2012
Required for Final Certificate of Occupancy: Add a temporary asphalt curb along the edge of the parking lot drive that ends at the south property line.
Carried Forward
03/29/2012
Required for Final Certificate of Occupancy: All exterior facade materials/finishes shall be installed.
Resolved
03/29/2012
Required for Final Certificate of Occupancy: The exterior service door form the stone cladded stairwell on the south side of the building shall be painted to match the exterior stone work on the surrounding facade.
Occupancy Inspection - Planning Temporary C of O 3/29/2012 at 12:00 AM 03/29/2012
Corrective Action Required
03/29/2012
Required for Final Certificate of Occupancy: The 5ft concrete sidewalk along McBaine Drive shall be extended to the south property line as shown on the approved Final Development Plan.
Corrective Action Required
03/29/2012
Required for Final Certificate of Occupancy: All sod shall be installed.
Corrective Action Required
03/29/2012
Required for Final Certificate of Occupancy: All exterior facade materials/finishes shall be installed.
Occupancy Inspection - Planning Passed 04/13/2012
Occupancy Inspection - Codes Commercial Full C of O 4/18/2012 at 12:00 AM 04/18/2012
Misc
Resolved
04/18/2012
OBTAIN APPROVAL FROM THE FOLLOWING: -PLANNING AND DEVELOPMENT DEPARTMENT -PUBLIC WORKS
Misc
Resolved
04/18/2012
-COMPLETE EXTERIOR: FLASHING, SEAL EXTERIOR WALL PENETRATIONS -INSTALL TEMPERED GLASS ADJACENT BY STAIR WITHIN 5 FT OF FLOOR (WEST STAIR) -INSTALL 2ND FLOOR RESTROOM SIGNAGE -PAINT GAS PIPING EXPOSED TO WEATHER FOR PROTECTION
Water Service Inspection Passed 10/21/2011 (1:45) 10/21/2011 at 12:00 AM 04/23/2012
Documents & Images
Date Uploaded File Type Document Name
07/25/2011 Letter Plan Review Conditions
08/04/2011 Letter Building Permit
08/04/2011 Letter Plan Review Conditions
10/12/2011 Letter Inspection Summary
10/21/2011 Letter Inspection Summary
11/04/2011 Letter Inspection Summary
11/07/2011 Letter Inspection Summary
11/09/2011 Letter Inspection Summary
11/10/2011 Letter Inspection Summary
11/15/2011 Letter Inspection Summary
11/16/2011 Letter Inspection Summary
11/17/2011 Letter Inspection Summary
11/17/2011 Letter Inspection Summary
11/17/2011 Letter Inspection Summary
11/18/2011 Letter Inspection Summary
01/09/2012 Letter Inspection Summary
01/17/2012 Letter Inspection Summary
01/18/2012 Letter Inspection Summary
01/23/2012 Letter Inspection Summary
01/24/2012 Letter Inspection Summary
01/26/2012 Letter Inspection Summary
01/31/2012 Letter Inspection Summary
02/10/2012 Letter Inspection Summary
02/14/2012 Letter Inspection Summary
02/24/2012 Letter Inspection Summary
02/28/2012 Letter Inspection Summary
02/29/2012 Letter Inspection Summary
03/01/2012 Letter Inspection Summary
03/09/2012 Letter Inspection Summary
03/12/2012 Letter Inspection Summary
03/22/2012 Letter Inspection Summary
03/22/2012 Letter Inspection Summary
03/23/2012 Letter Inspection Summary
03/26/2012 Letter Fire (Alarm) Plan Review Notice
03/27/2012 Letter Fire Loss Reduction Form
03/27/2012 Letter Temporary Certificate of Occupancy
03/29/2012 Letter Planning Inspection Summary
03/29/2012 Letter Planning Inspection Summary
04/02/2012 Activity Document 20120402113226606.pdf
04/02/2012 Activity Document 20120402113126280.pdf
04/02/2012 Activity Document 20120402113149188.pdf
04/02/2012 Activity Document 20120402113158815.pdf
04/13/2012 Letter Planning Inspection Summary
04/18/2012 Letter Field Certificate of Occupancy
04/23/2012 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
06/26/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents