Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved
|
05/31/2011
|
02/13/2012
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
Plans received on Feb 9, 2012. Approved as per prior comments
|
|
|
Internal Plan Review (Res)
|
Approved
|
|
05/31/2011
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Approved
|
06/01/2011
|
05/31/2011
|
|
Mike Weisenborn
|
|
Accessibility - Water closet - Grab bars
Corrective Action Required
ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Action required - The required side wall vertical grab bar is not shown. Make needed corrections.
Mike Weisenborn May 31, 2011 - To be verified on inspection.
|
|
Accessibility - Water closet - Clearance around
ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided.
Action required - The sink is located within the required clearspace of the water closet. Make needed corrections.
Mike Weisenborn May 31, 2011 - Corrections have been made.
|
|
Plumb - Required public toilet facilities
Corrective Action Required
2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.
Action required - As separate men's and women's restrooms are required. Both restrooms shall be available to the public. This comment is for information purposes.
|
|
Plumb - Separate facilities
2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.)
Action required - Label the restrooms on the plans as men's and women's.
Mike Weisenborn May 31, 2011 - Restrooms have been labeled on the plans.
|
|
|
Fire Plan Review
|
Approved
|
06/01/2011
|
05/26/2011
|
|
Jim Eden
|
|
Address numbers required
2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
How is the new unit going to be addressed?Adjust the addressing on the existing doors as needed.
|
|
Misc
1006.3 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas:
1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress.
2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits.
3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits.
5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits.
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Provide exterior emergency lighting over the new doors.
|
|
Misc
Provide remote LED/Audible/reset panels for the duct detectors.
|
|
Misc
Corrective Action Required
Provide specifications for the Trident Locking System.
|
|
|
Zoning Review
|
Approved
|
05/13/2011
|
05/16/2011
|
|
Chris Hughey
|
|
|
Internal Plan Review (Res)
|
Rejected
|
05/13/2011
|
05/13/2011
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Rejected
|
05/13/2011
|
05/13/2011
|
|
Mike Weisenborn
|
|
Accessibility - Water closet - Grab bars
Corrective Action Required
ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.
Action required - The required side wall vertical grab bar is not shown. Make needed corrections.
|
|
Accessibility - Water closet - Clearance around
Corrective Action Required
ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided.
Action required - The sink is located within the required clearspace of the water closet. Make needed corrections.
|
|
Plumb - Required public toilet facilities
Corrective Action Required
2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.
Action required - As separate men's and women's restrooms are required both restrooms shall be available to the public. This comment is for information purposes.
|
|
Plumb - Separate facilities
Corrective Action Required
2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.)
Action required - Label the restrooms on the plans as men's and women's.
|
|
|
License Tax Codes
|
Approved
|
05/13/2011
|
05/13/2011
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Rejected
|
05/13/2011
|
05/12/2011
|
|
Jim Eden
|
|
Address numbers required
Corrective Action Required
2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
How is the new unit going to be addressed?Adjust the addressing on the existing doors as needed.
|
|
Misc
Corrective Action Required
1006.3 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas:
1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress.
2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits.
3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits.
5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits.
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.
Provide exterior emergency lighting over the new doors.
|
|
Misc
Corrective Action Required
Provide remote LED/Audible/reset panels for the duct detectors.
|
|
|
Historical Preservation Review
|
Approved
|
05/13/2011
|
05/11/2011
|
|
Mike Weisenborn
|
|
|