Permit Application Status

PRCOM20111185


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20111185
Building Permit - Commercial
Certificate of Occupancy
JAMS LEES BUSTER LLC
CHANGE OF TENANT
CHANGE OF TENANT FROM BLOCKBUSTER TO GAME SALES
05/03/2011
02/06/2012
11/09/2011
02/29/2012
Locations
Contacts
JAMS LEES BUSTER LLC, Address:605 W 47TH ST STE 200  
ARCVISION, Address:1950 CRAIG RD SUITE 300  
TITAN CONSTRUCTION INC, Address:7460 LANCASTER PIKE, Phone:(302) 234-6500  
CENTRAL SYSTEMS HEATING & A/C INC, Address:2857 WESTBOUND US HWY 40, Phone:(816) 228-2022  
REINHOLD ELECTRIC INC, Address:2511 LEMAY FERRY RD, Phone:(314) 631-1158  
HAMPTON PLUMBING INC, Address:P O BOX 552, Phone:(816) 628-5069  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 05/31/2011 02/13/2012
Brian Austerman
Misc
Corrective Action Required
02/13/2012

Plans received on Feb 9, 2012. Approved as per prior comments
Internal Plan Review (Res) Approved 05/31/2011
Mike Weisenborn
Building Plan Review Approved 06/01/2011 05/31/2011
Mike Weisenborn
Accessibility - Water closet - Grab bars
Corrective Action Required
05/24/2011

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - The required side wall vertical grab bar is not shown. Make needed corrections. Mike Weisenborn May 31, 2011 - To be verified on inspection.
Accessibility - Water closet - Clearance around
Resolved
05/31/2011

ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided. Action required - The sink is located within the required clearspace of the water closet. Make needed corrections. Mike Weisenborn May 31, 2011 - Corrections have been made.
Plumb - Required public toilet facilities
Corrective Action Required
05/24/2011

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - As separate men's and women's restrooms are required. Both restrooms shall be available to the public. This comment is for information purposes.
Plumb - Separate facilities
Resolved
05/31/2011

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Label the restrooms on the plans as men's and women's. Mike Weisenborn May 31, 2011 - Restrooms have been labeled on the plans.
Fire Plan Review Approved 06/01/2011 05/26/2011
Jim Eden
Address numbers required
Resolved
05/26/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). How is the new unit going to be addressed?Adjust the addressing on the existing doors as needed.
Misc
Resolved
05/26/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Provide exterior emergency lighting over the new doors.
Misc
Resolved
05/26/2011

Provide remote LED/Audible/reset panels for the duct detectors.
Misc
Corrective Action Required
05/26/2011

Provide specifications for the Trident Locking System.
Zoning Review Approved 05/13/2011 05/16/2011
Chris Hughey
Internal Plan Review (Res) Rejected 05/13/2011 05/13/2011
Mike Weisenborn
Building Plan Review Rejected 05/13/2011 05/13/2011
Mike Weisenborn
Accessibility - Water closet - Grab bars
Corrective Action Required
05/13/2011

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - The required side wall vertical grab bar is not shown. Make needed corrections.
Accessibility - Water closet - Clearance around
Corrective Action Required
05/13/2011

ICC/ANSI A117.1 2003 604.3.1 - Size. A clearance around a water closet 60 inches minimum, measured perpendicular from the sidewall, and 56 inches minimum, measured perpendicular from the rear wall, shall be provided. Action required - The sink is located within the required clearspace of the water closet. Make needed corrections.
Plumb - Required public toilet facilities
Corrective Action Required
05/13/2011

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - As separate men's and women's restrooms are required both restrooms shall be available to the public. This comment is for information purposes.
Plumb - Separate facilities
Corrective Action Required
05/13/2011

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Label the restrooms on the plans as men's and women's.
License Tax Codes Approved 05/13/2011 05/13/2011
Mike Weisenborn
Fire Plan Review Rejected 05/13/2011 05/12/2011
Jim Eden
Address numbers required
Corrective Action Required
05/12/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). How is the new unit going to be addressed?Adjust the addressing on the existing doors as needed.
Misc
Corrective Action Required
05/12/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Provide exterior emergency lighting over the new doors.
Misc
Corrective Action Required
05/12/2011

Provide remote LED/Audible/reset panels for the duct detectors.
Historical Preservation Review Approved 05/13/2011 05/11/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $326.80 $326.80 Paid 02/06/2012
8331507-Sewer Connection Fee $210.00 $210.00 Paid 02/06/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 2/9/2012 at 12:00 AM 02/09/2012
In-wall Inspection Partial 2/9/2012 at 12:00 AM 02/09/2012
Misc
Partial Correction
02/09/2012
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: N DEMMISING WALL; 101 SE CORNER + WEST WALL; 103; 104;
Rated Assembly Inspection Failed 2/9/2012 2/10/2012 at 12:00 AM 02/10/2012
Misc
Corrective Action Required
02/10/2012
DEMISING WALL SOUTH FACE SCREWS NOT AT 8" AT PERMETER & 12" IN THE FIELD AT ALL LOCATIONS
Rated Assembly Inspection Passed 2/13/2012 at 12:00 AM 02/13/2012
Misc
Resolved
02/13/2012
DEMISING WALL SOUTH FACE SCREWS NOT AT 8" AT PERMETER & 12" IN THE FIELD AT ALL LOCATIONS
Underslab Plumbing Inspection - Commercial Partial 2/15/2012 2/14/2012 at 12:00 AM 02/14/2012
Misc
Partial Correction
02/14/2012
OK TO COVER WHEN READY UNDER-SLAB WASTE PIPING AND FIXTURE STUB-UPS AT SUITE "A"; ALSO, 4" BUILDING DRAIN NORTH TO CONNECTION TO EXISTING IN SUITE "B". FIXTURE STUB-UPS AT SUITE "B" SOUTHWEST @ NEW WALL NOT SHOWN ON APPROVED DRAWINGS -- NOT APPROVED.
Above Ceiling Inspection Partial 2/15/2012 2/15/2012 at 12:00 AM 02/15/2012
Misc
Partial Correction
02/15/2012
OK TO COVER WHEN READY CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 101 EXCEPT LEAVE OUT TILE FOR COMPLETE VISIBILITY OF RTU INSTALLATION AREAS
In-wall Inspection Passed 2/17/2012 2/17/2012 at 12:00 AM 02/17/2012
Misc
Resolved
02/17/2012
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: N DEMMISING WALL; 101 SE CORNER + WEST WALL; 103; 104;
Above Ceiling Inspection Passed 2/22/2012 2/22/2012 at 12:00 AM 02/22/2012
Misc
Resolved
02/22/2012
OK TO COVER WHEN READY CEILING FRAMING AND ABOVE-CEILING SYSTEMS AT: 101 EXCEPT LEAVE OUT TILE FOR COMPLETE VISIBILITY OF RTU INSTALLATION AREAS
Electrical Service Inspection Passed 2/28/2012 at 12:00 AM 02/28/2012
Gas Piping Inspection - Commercial Passed 2/29/2012 at 12:00 AM 02/28/2012
Gas Service Inspection - Commercial Passed 2/28/2012 at 12:00 AM 02/28/2012
Underslab Plumbing Inspection - Commercial Passed 2/29/2012 at 12:00 AM 02/29/2012
Misc
Resolved
02/29/2012
OK TO COVER WHEN READY UNDER-SLAB WASTE PIPING AND FIXTURE STUB-UPS AT SUITE "A"; ALSO, 4" BUILDING DRAIN NORTH TO CONNECTION TO EXISTING IN SUITE "B". FIXTURE STUB-UPS AT SUITE "B" SOUTHWEST @ NEW WALL NOT SHOWN ON APPROVED DRAWINGS -- NOT APPROVED.
Occupancy Inspection - Fire Passed 2/29/2012 at 12:00 AM 02/29/2012
Occupancy Inspection - Codes Commercial Full C of O 2/29/2012 2/29/2012 at 12:00 AM 02/29/2012
Documents & Images
Date Uploaded File Type Document Name
05/13/2011 Letter Plan Review Conditions
02/06/2012 Letter Plan Review Conditions
02/06/2012 Letter 20120206112915835.pdf
02/06/2012 Letter Building Permit
02/09/2012 Letter Inspection Summary
02/10/2012 Letter Inspection Summary
02/13/2012 Letter Inspection Summary
02/14/2012 Letter Inspection Summary
02/15/2012 Letter Inspection Summary
02/17/2012 Letter Inspection Summary
02/22/2012 Letter Inspection Summary
02/28/2012 Letter Inspection Summary
02/28/2012 Letter Inspection Summary
02/29/2012 Letter Fire Loss Reduction Form
02/29/2012 Letter Field Certificate of Occupancy
03/01/2012 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home