Permit Application Status

PRCOM20111096


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20111096
Building Permit - Commercial
Certificate of Occupancy
CATHOLIC DIOCESE OF KC-ST JOE
ADDITION COMMERCIAL
SCHOOL ADDITION
05/02/2011
08/05/2011
10/06/2014
07/17/2012
Locations
Contacts
THE HOLLIS & MILLER GROUP, Address:1828 WALNUT ST STE 922, Phone:(816) 525-5600  
A L HUBER INC, Address:10770 EL MONTE, Phone:(913) 341-4880  
CATHOLIC DIOCESE OF KC-ST JOE, Address:130 NE MURRAY RD  
CITY WIDE HEATING & COOLING INC, Address:2824 ROE LANE, Phone:(913) 384-6006  
R F FISHER ELECTRIC COMPANY LLC, Address:5299 DTC BLVD STE 600, Phone:(913) 384-1500  
CENTRAL PLUMBING HTG & A/C INC, Address:P O BOX 218, Phone:(816) 942-6355  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 03/02/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
03/02/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received February 27, 2012.
Misc
Corrective Action Required
03/02/2012

Systems shall be designed to the 2006 IFC and the 2002 Edition of NFPA 13. For information only.
Installation acceptance testing
Corrective Action Required
03/02/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hydrostatic and flow tests.
Misc
Corrective Action Required
03/02/2012

Switchover from the old to new main shall require a minimal of of time and system impairment. Switchover should take place on a school holiday, weekend, or after hours.
Misc
Corrective Action Required
03/02/2012

The FDC shall be marked to indicate the portion of the building served.
Misc
Corrective Action Required
03/02/2012

Coordinate with the alarm company on the location of the exterior horn/strobe.
Misc
Corrective Action Required
03/02/2012

The inspectors test is not indicated on the riser detail. Confirm that a test is located on the existing system. Verified at inspection.
Alarm Plan Review Rejected 05/30/2011 01/27/2012
Jim Eden
Corrective Action Required
01/27/2012

See the alarm plans for PRCOM20115556.
Internal Plan Review (Res) Approved 07/29/2011 07/28/2011
Mike Weisenborn
Final Development Plan Review Approved 06/24/2011 07/28/2011
Mike Weisenborn
Building Plan Review Approved 06/09/2011 06/08/2011
Mike Weisenborn
Mech - Outdoor air required
Resolved
06/08/2011

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - Provide outdoor air calculations. Mike Weisenborn June 08, 2011 - Per resubmittal.
Bldg - Exit signage - Where required
Resolved
06/08/2011

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - Add an exit sign in the eastern portion of Corridor A107 so that it is visable when exiting Classroom 3 and the Teacher Planning Rm. Mike Weisenborn June 08, 2011 - Per resubmittal.
Fire Plan Review Approved 06/09/2011 06/06/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
06/02/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for review and approval.
Construction documents for fire alarm systems
Corrective Action Required
06/06/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for review and approval. Provide smoke detection for each set of doors on mag. hold open devices and above the FAEP.
Fire access roads or water supply required
Corrective Action Required
06/06/2011

2006 IFC 501.4- Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles in accordance with Section 505.2. Action required: The new water main to the hydrant and existing sprinkler system shall be installed and made operable prior to construction.
Misc
Resolved
06/06/2011

907.2.3 Group E. A manual fire alarm system shall be installed in Group E occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. Exceptions: 3.Manual fire alarm boxes shall not be required in Group E occupancies where the building is equipped throughout with an approved automatic sprinkler system, the notification appliances will activate on sprinkler water flow and manual activation is provided from a normally occupied location. Action required: Confirm a pull station is located at a normally occupied location.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Resolved
06/06/2011

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action Required: The existing sprinkler system shall have documentation of a current annual inspection.
Installation acceptance testing
Resolved
06/06/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test of the fire protection system prior to scheduling an occupancy inspection.
Misc
Resolved
06/06/2011

2006 IFC 503.3 Marking. Where required by the fire code official, approved signs or other approved notices shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Signs or notices shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. Action required: The lane between the new addition and the existing building to the south shall be posted "No Parking Fire Lane" on both sides.
Misc
Corrective Action Required
06/06/2011

901.7.4 Preplanned impairment programs. Preplanned impairments shall be authorized by the impairment coordinator. Before authorization is given, a designated individual shall be responsible for verifying that all of the following procedures have been implemented: 1. The extent and expected duration of the impairment have been determined. 2. The areas or buildings involved have been inspected and the increased risks determined. 3. Recommendations have been submitted to management or building owner/manager. 4. The fire department has been notified. 5. The insurance carrier, the alarm company, building owner/manager, and other authorities having jurisdiction have been notified. 6. The supervisors in the areas to be affected have been notified. 7. A tag impairment system has been implemented. 8. Necessary tools and materials have been assembled on the impairment site. Action required: The GC shall designate an Impairment Coordinator (Sprinkler Co.) to provide an Impairment Plan for the sprinkler system. The system shall not be shut down without notification of the Fire Department. Impairment shall be kept to a minimum and shall not occur while the school portion of the building is occupied. Action required: Provide a plan.
Fire protection equipment identification
Resolved
06/06/2011

2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Action required: Rooms A101 and A102 shall be marked "Fire Sprinkler Room".
Misc
Resolved
06/06/2011

Provide an intermediate exit sign outside of the Teacher Planning Room.
Unlawful to occupancy
Corrective Action Required
06/02/2011

2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved. For information only.
Internal Plan Review (Res) Rejected 05/16/2011 05/16/2011
Mike Weisenborn
License Tax Codes Approved 05/16/2011 05/16/2011
Mike Weisenborn
Building Plan Review Rejected 05/16/2011 05/16/2011
Mike Weisenborn
Mech - Outdoor air required
Corrective Action Required
05/16/2011

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action required - Provide outdoor air calculations.
Bldg - Exit signage - Where required
Corrective Action Required
05/16/2011

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - Add an exit sign in the eastern portion of Corridor A107 so that it is visable when exiting Classroom 3 and the Teacher Planning Rm.
Fire Plan Review Rejected 05/16/2011 05/16/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
05/16/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for review and approval.
Construction documents for fire alarm systems
Corrective Action Required
05/16/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for review and approval. Provide smoke detection for each set of doors on mag. hold open devices and above the FAEP.
Fire access roads or water supply required
Corrective Action Required
05/16/2011

2006 IFC 501.4- Timing of installation. When fire apparatus access roads or a water supply for fire protection is required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except when approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles in accordance with Section 505.2. Action required: The new water main to the hydrant and existing sprinkler system shall be installed and made operable prior to construction.
Misc
Corrective Action Required
05/16/2011

907.2.3 Group E. A manual fire alarm system shall be installed in Group E occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. Exceptions: 3.Manual fire alarm boxes shall not be required in Group E occupancies where the building is equipped throughout with an approved automatic sprinkler system, the notification appliances will activate on sprinkler water flow and manual activation is provided from a normally occupied location. Action required: Confirm a pull station is located at a normally occupied location.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
05/16/2011

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action Required: The existing sprinkler system shall have documentation of a current annual inspection.
Installation acceptance testing
Corrective Action Required
05/16/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test of the fire protection system prior to scheduling an occupancy inspection.
Misc
Corrective Action Required
05/16/2011

2006 IFC 503.3 Marking. Where required by the fire code official, approved signs or other approved notices shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Signs or notices shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. Action required: The lane between the new addition and the existing building to the south shall be posted "No Parking Fire Lane" on both sides.
Misc
Corrective Action Required
05/16/2011

901.7.4 Preplanned impairment programs. Preplanned impairments shall be authorized by the impairment coordinator. Before authorization is given, a designated individual shall be responsible for verifying that all of the following procedures have been implemented: 1. The extent and expected duration of the impairment have been determined. 2. The areas or buildings involved have been inspected and the increased risks determined. 3. Recommendations have been submitted to management or building owner/manager. 4. The fire department has been notified. 5. The insurance carrier, the alarm company, building owner/manager, and other authorities having jurisdiction have been notified. 6. The supervisors in the areas to be affected have been notified. 7. A tag impairment system has been implemented. 8. Necessary tools and materials have been assembled on the impairment site. Action required: The GC shall designate an Impairment Coordinator (Sprinkler Co.) to provide an Impairment Plan for the sprinkler system. The system shall not be shut down without notification of the Fire Department. Impairment shall be kept to a minimum and shall not occur while the school portion of the building is occupied.
Fire protection equipment identification
Corrective Action Required
05/16/2011

2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Action required: Rooms A101 and A102 shall be marked "Fire Sprinkler Room".
Misc
Corrective Action Required
05/16/2011

Provide an intermediate exit sign outside of the Teacher Planning Room.
Unlawful to occupancy
Corrective Action Required
05/16/2011

2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved. For information only.
Historical Preservation Review Approved 05/16/2011 05/03/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Addition to Commercial $1,451.67 $1,451.67 Paid 08/05/2011
8350015-Water Meter Fee $1,482.00 $1,482.00 Paid 08/05/2011
8331507-Sewer Connection Fee $30.00 $30.00 Paid 08/05/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Water Service Inspection Not Ready 8/9/2011 at 12:00 AM 08/09/2011
Water Service Inspection Passed 8/11/2011 at 12:00 AM 08/11/2011
Underslab Plumbing Inspection - Commercial Passed 11/4/2011 (8:00 to 5:00) 11/4/2011 at 12:00 AM 11/04/2011
Underslab Plumbing Inspection - Commercial Passed 11/4/2011 at 12:00 AM 11/04/2011
Footing Inspection - Commercial Partial 11/10/2011 (2:00) 11/10/2011 at 12:00 AM 11/10/2011
Misc
Partial Correction
11/14/2011
OK TO POUR WHEN READY GRADE BEAM/FOOTING AT FOLLOWING LOCATIONS: A100 EAST WALL N 24; DETAIL SECTION A9 @ A100, A107 TO WITHIN 8' OF NW CORNER;
Footing Inspection - Commercial Partial 11/11/2011 (2:00) 11/14/2011 at 12:00 AM 11/14/2011
Misc
Partial Correction
11/14/2011
OK TO PLACE WHEN READY GRADE BEAM/FOOTING AT FOLLOWING LOCATIONS: A100 EAST WALL N 24'; SECTION A9 @ A100 & A107 TO WITHIN 8' OF NW CORNER;
Footing Inspection - Commercial Partial 11/15/2011 (1:15) 11/15/2011 at 12:00 AM 11/15/2011
Misc
Partial Correction
11/15/2011
OK TO PLACE WHEN READY GRADE BEAM/FOOTING AT FOLLOWING LOCATIONS: A100 EAST WALL N 24'; SECTION A9 @ A100 & A107 TO WITHIN 8' OF NW CORNER; REMAINDER OF EXTERIOR AND INTERIOR FOOTINGS
Underslab Electrical Inspection - Commercial Passed 11/16/2011 11/17/2011 at 12:00 AM 11/17/2011
Rough Framing Inspection - Commercial Partial 12/28/2011 at 12:00 AM 12/28/2011
Misc
Partial Correction
12/28/2011
LIGHT-GAUGE STEEL FRAMING AT EXTERIOR WALLS ONLY OK TO COVER WXTERIOR FACE WHEN READY.
Misc
Corrective Action Required
12/28/2011
STRUCTURAL HOLD-DOWN ANCHORS AT EXTERIOR WALLS SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Corrective Action Required
12/28/2011
ANCHORAGE OF BOTTOM TRACKS NOT 3/4" BOLTS @ 32" O.C. PER APPROVED DRAWINGS.
Misc
Corrective Action Required
12/28/2011
CITY INSPECTION OF ERECTION OF ROOF TRUSSES DEFERRED TO 3RD PARTY INSPECTION
In-wall Inspection Partial 1/12/2012 at 12:00 AM 01/12/2012
Misc
Partial Correction
01/12/2012
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT FOLLOWING SPACES: A100; A100a W,S,&E WALLS ONLY; A101; A102; CORR A107 N-S LEG;
In-wall Inspection Partial 2/6/2012 2/6/2012 at 12:00 AM 02/06/2012
Misc
Partial Correction
01/12/2012
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT FOLLOWING SPACES: A100; A100a W,S,&E WALLS ONLY; A101; A102; CORR A107 N-S LEG; A103; A104; A105 CORRIDOR A107 E-W/SE-NW LEGS COVERED WITHOUT INSPECTION
Above Ceiling Inspection Passed 3/20/2012 at 12:00 AM 03/20/2012
Footing Inspection - Commercial Passed 11/15/2011 at 12:00 AM 03/23/2012
In-wall Inspection Passed 2/6/2012 at 12:00 AM 03/23/2012
Misc
Resolved
03/23/2012
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT FOLLOWING SPACES: A100; A100a W,S,&E WALLS ONLY; A101; A102; CORR A107 N-S LEG; A103; A104; A105 CORRIDOR A107 E-W/SE-NW LEGS COVERED WITHOUT INSPECTION
Rough Framing Inspection - Commercial Passed 12/28/2011 at 12:00 AM 03/23/2012
Misc
Resolved
03/23/2012
LIGHT-GAUGE STEEL FRAMING AT EXTERIOR WALLS ONLY OK TO COVER WXTERIOR FACE WHEN READY.
Misc
Resolved
03/23/2012
STRUCTURAL HOLD-DOWN ANCHORS AT EXTERIOR WALLS SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Resolved
03/23/2012
ANCHORAGE OF BOTTOM TRACKS NOT 3/4" BOLTS @ 32" O.C. PER APPROVED DRAWINGS.
Erosion Control Inspection Residential Passed 03/23/2012
In-wall Inspection Passed 4/4/2012 at 12:00 AM 04/04/2012
Occupancy Inspection - Codes Commercial Temporary C of O 4/19/2012 4/19/2012 at 12:00 AM 04/20/2012
Misc
Corrective Action Required
04/20/2012
PROVIDE SAFE PEDESTRIAN ACCESS AT ENTRANCE (NORMAL AND HANDICAPPED)
Misc
Corrective Action Required
04/20/2012
CHECK ALL INTERIOR ELECTRICAL RECEPTACLES; MAKE ALL SOLID TO BOX
Misc
Corrective Action Required
04/20/2012
RE-CHECK ALL ELECTRICAL CIRCUIT DESIGNATIONS AT PANEL SCHEDULES. CORRECT / ADD AS NEEDED.
Misc
Corrective Action Required
04/20/2012
COMPLETE ROOFTOP GAS PIPING SUPPORTS (CLAMPS NOT IN PLACE)
Misc
Corrective Action Required
04/20/2012
RTU ELECTRICAL RECEPTACLES NOT HOT FOR TEST
Misc
Corrective Action Required
04/20/2012
ENSURE RTU'S ARE LABELED BY NUMBER OR LETTER; REFLECT AT PANEL SCHEDULES
Misc
Corrective Action Required
04/20/2012
CLEAN ALL DEBRIS AND UNUSED MATERIAL FROM ROOF
Occupancy Inspection - Planning Temporary C of O 4/19/2012 at 12:00 AM 04/20/2012
Corrective Action Required
04/19/2012
Required for Final Certificate of Occupancy. All parking lot asphalt, curbing, sidewalks shall be installed.
Corrective Action Required
04/19/2012
Required for Final Certificate of Occupancy. All parking space striping, pedestrian crossings, and ADA parking space signs shall be installed.
Corrective Action Required
04/19/2012
Required for Final Certificate of Occupancy. All landscaping material shall be installed.
Corrective Action Required
04/19/2012
Required for Final Certificate of Occupancy. All construction debris and materials shall be removed.
Corrective Action Required
04/19/2012
Required for Final Certificate of Occupancy. The approved Final Development Plans show the west elevation wall as having a brick facade. However, a primarily stucco facade with brick trim was constructed. This change of material is acceptable since it is in keeping with the design of the addition. However, please submit revised elevation plans (Sheet A200) to show the constructed facade.
Occupancy Inspection - Codes Commercial Partial 4/25/2012 at 12:00 AM 04/25/2012
Misc
Corrective Action Required
04/20/2012
MAINTAIN SAFE PEDESTRIAN ACCESS AT ENTRANCE (NORMAL AND HANDICAPPED)
Misc
Resolved
04/25/2012
CHECK ALL INTERIOR ELECTRICAL RECEPTACLES; MAKE ALL SOLID TO BOX
Misc
Corrective Action Required
04/20/2012
COMPLETE PERMANENT PANEL SCHEDULES
Misc
Resolved
04/25/2012
COMPLETE ROOFTOP GAS PIPING SUPPORTS (CLAMPS NOT IN PLACE)
Misc
Resolved
04/25/2012
RTU ELECTRICAL RECEPTACLES NOT HOT FOR TEST
Misc
Corrective Action Required
04/20/2012
AFFIX PERMANENT NUMERICAL DESIGNATION LABELS ON RTU'S
Misc
Resolved
04/25/2012
CLEAN ALL DEBRIS AND UNUSED MATERIAL FROM ROOF
Occupancy Inspection - Codes Commercial Temporary C of O 6/27/2012 at 12:00 AM 06/27/2012
Misc
Resolved
06/27/2012
MAINTAIN SAFE PEDESTRIAN ACCESS AT ENTRANCE (NORMAL AND HANDICAPPED)
Misc
Resolved
06/27/2012
COMPLETE PERMANENT PANEL SCHEDULES
Misc
Resolved
06/27/2012
AFFIX PERMANENT NUMERICAL DESIGNATION LABELS ON RTU'S
Misc
Corrective Action Required
06/27/2012
OBTAIN APPROVAL BY PLANNING & DEVELOPMENT DEPARTMENT
Occupancy Inspection - Codes Commercial Partial 7/2/2012 at 12:00 AM 07/02/2012
Misc
Corrective Action Required
06/27/2012
OBTAIN APPROVAL BY PLANNING & DEVELOPMENT DEPARTMENT
Occupancy Inspection - Planning Temporary C of O 07/10/2012
Corrective Action Required
07/10/2012
Required for Final Certificate of Occupancy. One ADA parking sign shall be placed at the head of each ADA parking space. Staff recommends the signs be placed to the left and right of the 2 windows in front of the parking spaces.
Corrective Action Required
07/10/2012
Required for Final Certificate of Occupancy. Landscape plantings shall be added to the wood chipped areas of the site that run north and south along the east side of the addition and in the new parking lot island along the south property line. Staff recommends 4 ground cover plants or shrubs in each area. In addition, staff recommends evergreen shrubs be used in the parking lot island for year round greenery and to aid in identifying the island during snow cover.
Sprinkler - Hydrostatic Test Passed 3/20/2012 at 12:00 AM 07/11/2012
Sprinkler - Flow Test Passed 4/19/2012 at 12:00 AM 07/11/2012
Alarm Test Passed 4/19/2012 at 12:00 AM 07/11/2012
Occupancy Inspection - Fire Temporary C of O 7/19/2012 at 12:00 AM 07/11/2012
Occupancy Inspection - Fire Passed 7/11/2012 at 12:00 AM 07/11/2012
Occupancy Inspection - Planning Passed 07/17/2012
Occupancy Inspection - Codes Commercial Full C of O 7/17/2012 at 12:00 AM 07/17/2012
Misc
Resolved
07/17/2012
OBTAIN APPROVAL BY PLANNING & DEVELOPMENT DEPARTMENT
Occupancy Inspection - Engineering Passed 11/13/2013
Documents & Images
Date Uploaded File Type Document Name
08/05/2011 Letter Plan Review Conditions
08/11/2011 Letter Inspection Summary
11/04/2011 Letter Inspection Summary
11/04/2011 Letter Inspection Summary
11/04/2011 Letter Inspection Summary
11/10/2011 Letter Inspection Summary
11/14/2011 Letter Inspection Summary
11/15/2011 Letter Inspection Summary
11/17/2011 Letter Inspection Summary
12/28/2011 Letter Inspection Summary
01/12/2012 Letter Inspection Summary
02/06/2012 Letter Inspection Summary
03/02/2012 Letter Fire (Sprinkler) Plan Review
03/20/2012 Letter Inspection Summary
03/20/2012 Letter Inspection Summary
04/02/2012 Activity Document 20120402113209101.pdf
04/04/2012 Letter Inspection Summary
04/20/2012 Letter Temporary Certificate of Occupancy
04/20/2012 Letter Planning Inspection Summary
04/20/2012 Letter Planning Inspection Summary
04/25/2012 Letter Inspection Summary
04/25/2012 Letter Inspection Summary
06/27/2012 Letter Temporary Certificate of Occupancy
07/10/2012 Letter Planning Inspection Summary
07/17/2012 Letter Field Certificate of Occupancy
07/18/2012 Letter Final Certificate of Occupancy
07/18/2012 Letter Planning Inspection Summary
06/26/2013 Letter Final Plan Review Conditions
06/27/2013 Letter Fire Building Plan Review
08/28/2013 Letter Temporary Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home