Summary
PRCOM20110993
Building Permit - Commercial
Certificate of Occupancy
GRANDLAND DEVELOPMENT LC
CHANGE OF TENANT
SHOWROOM AND STORAGE FOR FLOORING SALES
04/28/2011
06/06/2011
11/07/2011
07/12/2011
Locations
Contacts
ABELN & ASSOCIATES ARCHITECTS PC, Address:11827 W 112th St, Suite 220  
GRANDLAND DEVELOPMENT LC, Address:PO BOX 10076  
GENESIS CONSTRUCTION MANAGEMENT LLC, Address:6116 N MERSINGTON AVE, Phone:(816) 326-8157  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
ACCURATE MECHANICAL LLC, Address:205 E 13TH AVE, Phone:(816) 471-2272  
DALTON PLUMBING COMPANY INC, Address:207 NW REDWING DR, Phone:(816) 524-1210  
5 STAR HEATING & COOLING, Address:211 NW 12TH, Phone:(816) 517-3341  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/02/2011 05/31/2011
Mike Weisenborn
Building Plan Review Approved 06/02/2011 05/31/2011
Mike Weisenborn
Plumb - Required public toilet facilities
Resolved
05/31/2011

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - The public restrooms are not easily accessible. Make needed corrections. Mike Weisenborn May 31, 2011 - Per resubmittal.
Bldg - Exit access - Common path of egress travel
Resolved
05/31/2011

2006 IBC 1014.3 - Common path of egress travel. In occupancies other than Groups H-1, H-2 and H-3, the common path of egress travel shall not exceed 75 feet. In Group H-1, H-2 and H-3 occupancies, the common path of egress travel shall not exceed 25 feet. For common path of egress travel in Group A occupancies having fixed seating, see Section 1025.8. (See code for possible exceptions.) The allowable common path of travel is exceeded in the storage area. Make needed corrections. Mike Weisenborn May 31, 2011 - Per resubmittal.
Bldg - Exit signage - Where required
Resolved
05/31/2011

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - Provide exit signage in the storage area.
Misc
Resolved
05/31/2011

Details and specifications for the plumbing, electrical and mechanical work have not been provided. Action required - Provide details and specifications for the plumbing, electrical and mechanical work.
Fire Plan Review Approved 06/02/2011 05/27/2011
Brian Austerman
Misc
Corrective Action Required
05/25/2011

2006 IFC 1903.7 Access plan. Where storage pile configurations could change because of changes in product operations and processing, the access plan shall be submitted for approval when required by the fire code official. Action required: Provide a storage plan for warehouse area. Ie, racks, pallets, piles etc and aisle widths RECEIVED ON RESUB
Portable fire extinguishers - general
Corrective Action Required
05/25/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: provide extinguishers based on IFC 2006 table 906.3(1) 1 unit of A for every 1500 sq/ft. verified at inspection. RECEIVED ON RESUB
Address numbers required
Corrective Action Required
05/25/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: All doors leading into the space shall be properly addressed, verified at inspection RECEIVED ON RESUB
Misc
Corrective Action Required
05/25/2011

2006 IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action Required: 2 exits are required based on occupant load, only 1 is shown on plans. Provide a second emergency exit in accordance with IFC table 1016.1 RECEIVED ON RESUB
Misc
Corrective Action Required
05/27/2011

2006 IFC 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. Required fire department access doors shall not be obstructed or eliminated. Exit and exit access doors shall comply with Chapter 10. Access doors for high-piled combustible storage shall comply with Section 2306.6.1. Action Required: The exterior of door 106b need to be marked as blocked. Verified at inspection
Zoning Review Approved 05/10/2011 05/16/2011
Chris Hughey
Internal Plan Review (Res) Rejected 05/10/2011 05/11/2011
Mike Weisenborn
Fire Plan Review Rejected 05/10/2011 05/11/2011
Mike Weisenborn
Misc
Corrective Action Required
05/09/2011

2006 IFC 1903.7 Access plan. Where storage pile configurations could change because of changes in product operations and processing, the access plan shall be submitted for approval when required by the fire code official. Action required: Provide a storage plan for warehouse area. Ie, racks, pallets, piles etc and aisle widths
Portable fire extinguishers - general
Corrective Action Required
05/09/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: provide extinguishers based on IFC 2006 table 906.3(1) ! unit of A for every 1500 sq/ft. verified at inspection.
Address numbers required
Corrective Action Required
05/09/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: All doors leading into the space shall be properly addressed, verified at inspection
Misc
Corrective Action Required
05/09/2011

2006 IFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action Required: 2 exits are required based on occupant load, only 1 is shown on plans. Provide a second emergency exit in accordance with IFC table 1016.1
License Tax Codes Approved 05/10/2011 05/10/2011
Mike Weisenborn
Building Plan Review Rejected 05/10/2011 05/10/2011
Mike Weisenborn
Plumb - Required public toilet facilities
Corrective Action Required
05/10/2011

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - The public restrooms are not easily accessible. Make needed corrections.
Bldg - Exit access - Common path of egress travel
Corrective Action Required
05/10/2011

2006 IBC 1014.3 - Common path of egress travel. In occupancies other than Groups H-1, H-2 and H-3, the common path of egress travel shall not exceed 75 feet. In Group H-1, H-2 and H-3 occupancies, the common path of egress travel shall not exceed 25 feet. For common path of egress travel in Group A occupancies having fixed seating, see Section 1025.8. (See code for possible exceptions.) The allowable common path of travel is exceeded in the storage area. Make needed corrections.
Bldg - Exit signage - Where required
Corrective Action Required
05/10/2011

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - Provide exit signage in the storage area.
Misc
Corrective Action Required
05/10/2011

Details and specifications for the plumbing, electrical and mechanical work have not been provided. Action required - Provide details and specifications for the plumbing, electrical and mechanical work.
Historical Preservation Review Approved 05/10/2011 04/28/2011
Codes Admin
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $306.38 $306.38 Paid 06/06/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 6/9/2011 6/9/2011 at 12:00 AM 06/09/2011
In-wall Inspection Passed 6/10/2011 at 12:00 AM 06/10/2011
Above Ceiling Inspection Partial 6/15/2011 6/15/2011 at 12:00 AM 06/15/2011
Misc
Corrective Action Required
06/15/2011
INSTALLATION OF HVAC FLEXIBLE DUCT CONNECTORS NOT SEALED AT FITTINGS PER SMACNA, ADC, NOR MANUFACTURER'S INSTRUCTIONS. CLAMPS & TAPING MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS. SEE INSTRUCTION SHEET IN EACH BOX OF MATERIAL.
Above Ceiling Inspection Partial 6/17/2011 at 12:00 AM 06/17/2011
Misc
Corrective Action Required
06/15/2011
INSTALLATION OF HVAC FLEXIBLE DUCT CONNECTORS NOT SEALED AT FITTINGS PER SMACNA, ADC, NOR MANUFACTURER'S INSTRUCTIONS. CLAMPS & TAPING MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS. SEE INSTRUCTION SHEET IN EACH BOX OF MATERIAL.
Above Ceiling Inspection Passed 6/20/2011 at 12:00 AM 06/20/2011
Misc
Resolved
06/20/2011
INSTALLATION OF HVAC FLEXIBLE DUCT CONNECTORS NOT SEALED AT FITTINGS PER SMACNA, ADC, NOR MANUFACTURER'S INSTRUCTIONS. CLAMPS & TAPING MUST BE PER INSTRUCTIONS. NON-METALLIC CLAMPS OK ONLY WITH BEADED FITTINGS. SEE INSTRUCTION SHEET IN EACH BOX OF MATERIAL.
Occupancy Inspection - Fire Temporary C of O 06/20/2011
Misc
Corrective Action Required
06/20/2011
(1)numerically address all front doors going into the business "300" 4" minimum numbers contrasting color (2) numerically address roll-up door with suite address "300" 4" minimum contrasting color (3) label the rear double doors that are not useable "THIS DOOR BLOCKED"
Occupancy Inspection - Codes Commercial Failed 6/20/2011 at 12:00 AM 06/20/2011
Misc
Corrective Action Required
06/20/2011
FLOOR FINISH AT SHOWROOM & RESTROOM 107 SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Corrective Action Required
06/20/2011
RESTROOM 107 SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Corrective Action Required
06/20/2011
ADA DRINKING FOUNTAINS SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Corrective Action Required
06/20/2011
PANEL SCHEDULES REQUIRED AT ALL ELECTRICAL SERVICE PANELS: NEC 408.4 EACH BREAKER MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
06/20/2011
EXPANSION TANK NOT INSTALLED AT WATER HEATER.
Misc
Corrective Action Required
06/20/2011
PLUMBING VENT THROUGH ROOF APPARENTLY NOT COMPLETED FROM RR 107
Misc
Corrective Action Required
06/20/2011
IPC 420.3 WATER CLOSET SEAT AT UNISEX RR NOT OPEN FRONT
Misc
Corrective Action Required
06/20/2011
4-PLEX ELECTRICAL RECEPTACLE NEAR SOUTH ELECT PANEL NOT SECURED SOLID IN BOX
Misc
Corrective Action Required
06/20/2011
SURFACE-MOUNTED ELECTRICAL RECEPTACLES EAST OF ELECT PANELS AT NE REQUIRE REPAIR -- LOOSE IN BOXES
Misc
Corrective Action Required
06/20/2011
ELECTRICAL RECEPTACLES NOT HOT FOR TEST AT: 105, 104, 103 NE
Underslab Plumbing Inspection - Commercial Passed 6/29/2011 6/29/2011 at 12:00 AM 06/29/2011
In-wall Inspection Passed 6/30/2011 at 12:00 AM 06/30/2011
Occupancy Inspection - Codes Commercial Temporary C of O 7/1/2011 at 12:00 AM 07/01/2011
Misc
Resolved
07/01/2011
FLOOR FINISH AT SHOWROOM & RESTROOM 107 SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Resolved
07/01/2011
RESTROOM 107 SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Corrective Action Required
06/20/2011
ADA DRINKING FOUNTAINS SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Resolved
07/01/2011
PANEL SCHEDULES REQUIRED AT ALL ELECTRICAL SERVICE PANELS: NEC 408.4 EACH BREAKER MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Resolved
07/01/2011
EXPANSION TANK NOT INSTALLED AT WATER HEATER.
Misc
Resolved
07/01/2011
PLUMBING VENT THROUGH ROOF APPARENTLY NOT COMPLETED FROM RR 107
Misc
Resolved
07/01/2011
IPC 420.3 WATER CLOSET SEAT AT UNISEX RR NOT OPEN FRONT
Misc
Resolved
07/01/2011
4-PLEX ELECTRICAL RECEPTACLE NEAR SOUTH ELECT PANEL NO FACEPLATE INSTALL
Misc
Resolved
07/01/2011
SURFACE-MOUNTED ELECTRICAL RECEPTACLES EAST OF ELECT PANELS AT NE REQUIRE REPAIR -- LOOSE IN BOXES
Misc
Resolved
07/01/2011
ELECTRICAL RECEPTACLES NOT HOT FOR TEST AT: 105, 104, 103 NE
Misc
Corrective Action Required
07/01/2011
COUNTER NOT INSTALLED. SUBJECT TO ACCESSIBLE REQUIREMENTS WHEN INSTALLED.
Occupancy Inspection - Fire Passed 07/01/2011
Occupancy Inspection - Codes Commercial Full C of O 7/12/2011 at 12:00 AM 07/12/2011
Misc
Resolved
07/12/2011
ADA DRINKING FOUNTAINS SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Resolved
07/12/2011
COUNTER NOT INSTALLED. SUBJECT TO ACCESSIBLE REQUIREMENTS WHEN INSTALLED.
Documents & Images
Date Uploaded File Type Document Name
05/11/2011 Letter Plan Review Conditions
06/06/2011 Letter Building Permit
06/06/2011 Letter Plan Review Conditions
06/09/2011 Letter Inspection Summary
06/10/2011 Letter Inspection Summary
06/15/2011 Letter Inspection Summary
06/20/2011 Letter Fire Loss Reduction Form
06/20/2011 Letter Inspection Summary
06/20/2011 Letter Inspection Summary
06/29/2011 Letter Inspection Summary
06/30/2011 Letter Inspection Summary
07/01/2011 Letter Temporary Certificate of Occupancy
07/01/2011 Letter Fire Loss Reduction Form
07/12/2011 Letter Field Certificate of Occupancy
07/13/2011 Letter Final Certificate of Occupancy
07/13/2011 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home