Permit Application Status

PRCOM20110514


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20110514
Building Permit - Commercial
Certificate of Occupancy
SUMMIT NORTHRIDGE LLC
NEW TENANT FINISH
JIMMY JOHN'S - TENANT FINISH FOR SANDWICH SHOP. SPACE WAS PREVIOUSLY UNOCCUPIED. RESTROOMS INCLUDED ON THE SHELL BUILDING
04/07/2011
05/03/2011
10/12/2011
07/06/2011
Locations
Contacts
SUMMIT NORTHRIDGE LLC, Address:605 W 47TH ST STE 200  
MADISON HOMES LLC, Address:15720 ANDRIE ST  
Arzido Design, Address:6910 Chauncey Ln, Suite 105  
RELIABLE MECHANICAL SERVICES, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
LUCAS ELECTRIC , Address:517 MARGARET LN, Phone:(816) 807-4432  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 06/09/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
06/09/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans recieved May 27, 2011.
Installation acceptance testing
Corrective Action Required
06/09/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule testing.
Internal Plan Review (Res) Approved 04/27/2011
Mike Weisenborn
Building Plan Review Approved 05/02/2011 04/27/2011
Mike Weisenborn
Health Dept Review
Resolved
04/27/2011

For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required - Provide documentation of the Health Departments plan review approval.
Health Dept Inspection
Corrective Action Required
04/26/2011

For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required - This comment is for information purposes. A responce is not necessary.
Planning - Signs
Corrective Action Required
04/26/2011

Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirments. Action required - This comment is for information purposes.
Misc
Corrective Action Required
04/26/2011

The license tax shall be paid on the shell building prior to receiving any type of occupancy on this tenant space. This comment is for information purposes.
Misc
Corrective Action Required
04/26/2011

This tenant finish can not be issued any type of occupancy, either temporary of full, until the shell building which it is located in is sufficiently completed. Action required - This comment is for information purposes.
Internal Plan Review (Res) Rejected 04/15/2011
Mike Weisenborn
Building Plan Review Rejected 04/15/2011 04/15/2011
Mike Weisenborn
Health Dept Review
Corrective Action Required
04/15/2011

For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required - Provide documentation of the Health Departments plan review approval.
Health Dept Inspection
Corrective Action Required
04/15/2011

For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required - This comment is for information purposes. A responce is not necessary.
Planning - Signs
Corrective Action Required
04/15/2011

Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirments. Action required - This comment is for information purposes.
Misc
Corrective Action Required
04/15/2011

The license tax shall be paid on the shell building prior to receiving any type of occupancy on this tenant space. This comment is for information purposes.
Misc
Corrective Action Required
04/15/2011

This tenant finish can not be issued any type of occupancy, either temporary of full, until the shell building which it is located in is sufficiently completed. Action required - This comment is for information purposes.
License Tax Codes Approved 04/15/2011 04/13/2011
Mike Weisenborn
Fire Plan Review Approved 04/15/2011 04/12/2011
Jim Eden
Address numbers required
Corrective Action Required
04/12/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: Post the address on the front and rear doors. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
04/12/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for sprinkler alteration..
Construction documents for fire alarm systems
Corrective Action Required
04/12/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for alarm notification appliances.
Posting of occupant load
Corrective Action Required
04/12/2011

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inspection.
Misc
Corrective Action Required
04/12/2011

1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. Action required: A deadbolt lock shall not be used on the front door with panic hardware. Verified at inspection.
Zoning Review Approved 04/15/2011 04/08/2011
Chris Hughey
Historical Preservation Review Approved 04/15/2011 04/08/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Tenent Finish $351.68 $351.68 Paid 05/03/2011
8331507-Sewer Connection Fee $210.00 $210.00 Paid 05/03/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Not Ready 5/12/2011 at 12:00 AM 05/12/2011
Misc
Corrective Action Required
05/12/2011
DESIGNATION OF PLUMBING CONTRACTOR NOT IN PLACE ON PERMIT
Underslab Plumbing Inspection - Commercial Partial 5/13/2011 at 12:00 AM 05/13/2011
Misc
Resolved
05/13/2011
DESIGNATION OF PLUMBING CONTRACTOR NOT IN PLACE ON PERMIT
Misc
Resolved
05/13/2011
DOORS LOCKED; NO ACCESS TO INTERIOR
Misc
Corrective Action Required
05/13/2011
PLUMBING SCHEDULE ON DRAWING SHOWS TRAP PRIMER ON FD-2, WHICH IS NOT IN PLACE; OK TO COVER WITH THIS EXCEPTION
Above Ceiling Inspection Partial 05/20/2011
Misc
Partial Correction
05/20/2011
FRAMING OF SOFFIT @ PREP 101 AND SYSTEMS ABOVE IT OK TO COVER WHEN READY
Gas Piping Inspection - Commercial Passed 5/20/2011 at 12:00 AM 05/20/2011
In-wall Inspection Partial 5/20/2011 at 12:00 AM 05/20/2011
Misc
Partial Correction
05/20/2011
WALL FRAMING AND IN-WALL SYSTEMS OK TO COVER WHEN READY EXCEPT AT TWO SEVERED STUDS TO BE HEADERED-OFF FOR HVAC DUCT PENETRATION
Above Ceiling Inspection Partial 6/17/2011 (8:00 to 5:00) 6/17/2011 at 12:00 AM 06/17/2011
Misc
Resolved
06/17/2011
FRAMING OF SOFFIT @ PREP 101 AND SYSTEMS ABOVE IT OK TO COVER WHEN READY
Misc
Partial Correction
06/17/2011
OK TO COVER WHEN READY ACT CEILING AT 101; 103 & 104 AFTER RR VENT FANS ARE WIRED;
Misc
Corrective Action Required
06/17/2011
ABOVE-CEILING AT 102 NOT COMPLETED & READY FOR INSPECTION. CEILING SUPPORT WIRES MUST HANG STRAIGHT (NOT BENT AROUND DUCT,ETC) FROM STRUCTURE ABOVE TO CEILING GRID BELOW.
Alarm Test Passed 6/20/2011 at 12:00 AM 06/20/2011
Sprinkler - Hydrostatic Test Passed 4/7/2011 at 12:00 AM 06/20/2011
Sprinkler - Flow Test Passed 5/5/2011 at 12:00 AM 06/20/2011
Above Ceiling Inspection Passed 6/20/2011 at 12:00 AM 06/20/2011
Misc
Resolved
06/20/2011
OK TO COVER WHEN READY ACT CEILING AT 101; 103 & 104 AFTER RR VENT FANS ARE WIRED;
Misc
Resolved
06/20/2011
ABOVE-CEILING AT 102 NOT COMPLETED & READY FOR INSPECTION. CEILING SUPPORT WIRES MUST HANG STRAIGHT (NOT BENT AROUND DUCT,ETC) FROM STRUCTURE ABOVE TO CEILING GRID BELOW.
In-wall Inspection Passed 6/20/2011 6/20/2011 at 12:00 AM 06/20/2011
Misc
Resolved
06/20/2011
WALL FRAMING AND IN-WALL SYSTEMS OK TO COVER WHEN READY EXCEPT AT TWO SEVERED STUDS TO BE HEADERED-OFF FOR HVAC DUCT PENETRATION
Occupancy Inspection - Fire Passed 06/21/2011
Misc
Corrective Action Required
06/21/2011
OK to occupy once cleared through codes administration
Occupancy Inspection - Codes Commercial Temporary C of O 6/21/2011 6/21/2011 at 12:00 AM 06/21/2011
Misc
Corrective Action Required
06/21/2011
BACKFLOW PREVENTION AT CARBONATED BEVERAGE DISPENSING EQUIPMENT NOT ASSE 1022 LISTED AS REQUIRED BY IPC 608
Occupancy Inspection - Codes Commercial Full C of O 7/6/2011 at 12:00 AM 07/06/2011
Misc
Resolved
07/06/2011
BACKFLOW PREVENTION AT CARBONATED BEVERAGE DISPENSING EQUIPMENT NOT ASSE 1022 LISTED AS REQUIRED BY IPC 608
Documents & Images
Date Uploaded File Type Document Name
04/15/2011 Letter Plan Review Conditions
05/03/2011 Letter Building Permit
05/03/2011 Letter Plan Review Conditions
05/13/2011 Letter Inspection Summary
05/13/2011 Letter Inspection Summary
05/20/2011 Letter Inspection Summary
06/17/2011 Letter Inspection Summary
06/17/2011 Letter Inspection Summary
06/20/2011 Letter Inspection Summary
06/21/2011 Letter Fire Loss Reduction Form
06/21/2011 Letter Temporary Certificate of Occupancy
07/06/2011 Letter Field Certificate of Occupancy
07/07/2011 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire (Sprinkler) Plan Review
06/25/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home