Permit Application Status

PRCOM20110360


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20110360
Building Permit - Commercial
Final Completion
CBL LEES SUMMIT EAST LLC
ALTERATION COMMERCIAL
CORRIDOR AND DEMISING WALLS AS PART OF THE SHELL BUILDING
03/17/2011
04/08/2011
06/20/2011
Locations
Contacts
CAMM CONSTRUCTION INC, Address:PO BOX 1417, Phone:(816) 607-3602  
CATES ELECTRIC LLC, Address:4568 MEADOW LANE, Phone:(913) 915-2953  
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 04/12/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
04/12/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Alarm alteration plans received April 11, 2011.
Installation acceptance testing
Corrective Action Required
04/12/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test.
Internal Plan Review (Res) Approved 03/25/2011 03/25/2011
Mike Weisenborn
Building Plan Review Approved 03/25/2011 03/25/2011
Mike Weisenborn
Project cost
Resolved
03/25/2011

The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the project cost. Called and got the project cost from the general.
Tenant Finish Plans Required
Corrective Action Required
03/25/2011

Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Separate permits shall be obtained prior to performing any work which requires permits. Action required - This comment is for information purposes.
Misc
Corrective Action Required
03/25/2011

Fire Plan Review Approved 03/25/2011 03/24/2011
Jim Eden
Misc
Corrective Action Required
03/24/2011

The standpipe (hose valve connection shall be maintained near the exterior door to the corridor.
Misc
Corrective Action Required
03/24/2011

The corridor shall have signs posted " No Storage in the Corridor".
Construction documents - Fire protection systems
Corrective Action Required
03/24/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for shell building sprinkle and alarm alterations.
Portable fire extinguishers - general
Corrective Action Required
03/24/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide one, minimum 2A:10B:C fire extinguisher in the corridor. Verified at inspection.
License Tax Codes Approved 03/25/2011 03/21/2011
Mike Weisenborn
Historical Preservation Review Approved 03/25/2011 03/21/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $59.38 $59.38 Paid 04/08/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Electrical Inspection - Commercial Partial 4/13/2011 4/13/2011 at 12:00 AM 04/13/2011
Misc
Corrective Action Required
04/13/2011
PENDING - CHANGE PLANS TO SHOW 3 5/8" STUDS INSTALLED PLANS SHOW 6". OK TO COVER PENDING CHANGE
Rated Assembly Inspection Failed 4/18/2011 5/2/2011 at 12:00 AM 04/18/2011
Misc
Corrective Action Required
04/18/2011
TOP OF TYPE [1] WALL NOT CONSTRUCTED PER DETAIL 6/A101.
Misc
Corrective Action Required
04/18/2011
PVC ROOF DRAIN PIPING PENETRATES TYPE [1] WALL AT EAST END OF CORRIDOR. CONSULT A/E FOR DIRECTION COMPLIANT WITH UL-LISTED PENETRATION DESIGN. A/E MUST ISSUE WRITTEN DIRECTION.
Miscellaneous Inspection Partial 4/19/2011 at 12:00 AM 04/19/2011
Misc
Partial Correction
04/19/2011
LIGHTED SIGN ELEMENTS FOUND TO HAVE UL LABELS AFFIXED.
Rated Assembly Inspection Partial 4/25/2011 at 12:00 AM 04/25/2011
Misc
Corrective Action Required
04/18/2011
TOP OF TYPE [1] WALL NOT CONSTRUCTED PER DETAIL 6/A101.
Misc
Corrective Action Required
04/18/2011
PVC ROOF DRAIN PIPING PENETRATES TYPE [1] WALL AT EAST END OF CORRIDOR. CONSULT A/E FOR DIRECTION COMPLIANT WITH UL-LISTED PENETRATION DESIGN. A/E MUST ISSUE WRITTEN DIRECTION.
Rated Assembly Inspection Partial 5/2/2011 4/29/2011 at 12:00 AM 04/29/2011
Misc
Partial Correction
04/29/2011
TOP OF TYPE [1] WALL NOT CONSTRUCTED PER DETAIL 6/A101.
Misc
Partial Correction
04/29/2011
PVC ROOF DRAIN PIPING PENETRATES TYPE [1] WALL AT EAST END OF CORRIDOR. CONSULT A/E FOR DIRECTION COMPLIANT WITH UL-LISTED PENETRATION DESIGN. A/E MUST ISSUE WRITTEN DIRECTION.
Alarm Test Passed 4/19/2011 05/03/2011
Sprinkler - Flow Test Passed 05/03/2011
Rough Electrical Inspection - Commercial Passed 05/17/2011
Misc
Resolved
05/17/2011
PENDING - CHANGE PLANS TO SHOW 3 5/8" STUDS INSTALLED PLANS SHOW 6". OK TO COVER PENDING CHANGE
Miscellaneous Inspection Passed 05/17/2011
Final Inspection - Commercial Partial 5/17/2011 at 12:00 AM 05/17/2011
Misc
Corrective Action Required
05/17/2011
A/E LETTER REQUIRED REGARDING CLOSURE OF TOP CORNER OF EAST RATED WALL
Occupancy Inspection - Fire Temporary C of O 05/17/2011
Occupancy Inspection - Fire Passed 6/6/2011 at 12:00 AM 06/06/2011
Rated Assembly Inspection Passed 6/17/2011 at 12:00 AM 06/17/2011
Misc
Resolved
05/17/2011
TOP OF TYPE [1] WALL NOT CONSTRUCTED PER DETAIL 6/A101.
Misc
Resolved
05/17/2011
PVC ROOF DRAIN PIPING PENETRATES TYPE [1] WALL AT EAST END OF CORRIDOR. CONSULT A/E FOR DIRECTION COMPLIANT WITH UL-LISTED PENETRATION DESIGN. A/E MUST ISSUE WRITTEN DIRECTION.
Misc
Resolved
06/17/2011
SEE FINAL BUILDING INSPECTION REGARDING FIRE BARRIER
Final Inspection - Commercial Passed 6/17/2011 at 12:00 AM 06/17/2011
Misc
Resolved
06/17/2011
A/E LETTER REQUIRED REGARDING CLOSURE OF TOP CORNER OF EAST RATED WALL
Occupancy Inspection - Fire Passed 5/26/2011 at 12:00 AM 06/21/2011
Documents & Images
Date Uploaded File Type Document Name
04/08/2011 Letter Fire Building Plan Review
04/08/2011 Letter Building Permit
04/08/2011 Letter Plan Review Conditions
04/12/2011 Letter Fire (Alarm) Plan Review Notice
04/13/2011 Letter Inspection Summary
04/18/2011 Letter Inspection Summary
04/29/2011 Letter Inspection Summary
05/17/2011 Letter Inspection Summary
05/17/2011 Letter Fire Loss Reduction Form
05/27/2011 Letter 20110527090523774.pdf
06/06/2011 Letter Fire Loss Reduction Form
06/17/2011 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home