Permit Application Status

PRCOM20110203


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20110203
Building Permit - Commercial
Certificate of Occupancy
LE GRAND APARTMENTS LLC
CHANGE OF TENANT
Tenant finish for drinking and dining establishment. Previous tenant was the same use.
02/24/2011
03/17/2011
09/04/2011
05/18/2011
Locations
Contacts
TERRY CHAPMAN, Address:2412 W 71ST ST  
MAR ENTERPRISES INC, Address:24408 E US 50 HWY, Phone:(816) 524-2398  
LE GRAND APARTMENTS LLC, Address:25706 E SHADYBROOK LN  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
PHILLIPS ELECTRIC LLC, Address:1913 SW ENSLEY LN, Phone:(816) 447-4945  
CL HOWERTON ENTERPRISES LLC, Address:224 NW AA HWY, Phone:(816) 237-6338  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/16/2011 03/17/2011
Joe Frogge
Fire Plan Review Approved 03/16/2011 03/15/2011
Jim Eden
Building Plan Review Approved 03/16/2011 03/14/2011
Mike Weisenborn
Health Dept Inspection
Corrective Action Required
03/11/2011

For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy. Action required - This comment is for information purposes.
Misc
Resolved
03/14/2011

For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit. Action required - Provide documentation of approval from the Health Department. Action taken - Received approval from the Health Department.
Plumb - Backflow general 608.3
Corrective Action Required
03/11/2011

2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination. Action required - Indicate the location and type of backflows to be installed. Action taken - Additional information has been shown on the plans. This will be verified on inspection.
Plumb - Backflow on beverage dispensers
Corrective Action Required
03/11/2011

2006 IPC 608.16.1 - Beverage dispensers. The water supply connection to beverage dispensers shall be protected against backflow by a backflow preventer conforming to ASSE 1022, CSA B64.3.1 or by an airgap. The backflow preventer device and the piping downstream therefrom shall not be affected by carbon dioxide gas. Action required - Indicate the location and type of backflows to be installed. Action taken - Additional information has been shown on the plans. This will be verified on inspection.
Plumb - Indirect waste for food handling fixtures
Corrective Action Required
03/11/2011

2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap. Action required - Indicate locations of indirect waste connections. Action taken - Additional information has been shown on the plans. This will be verified on inspection.
Misc
Corrective Action Required
03/11/2011

Type II Hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing machines. Action required - Provide a Type II hood over the dishwasher or provide documentation showing that one is not required. Action taken - The dishwasher is to be equiped with a factory provided heat and vapor exhaust. This will be verified on inspection.
Misc
Resolved
03/14/2011

The plans indicate that plywood is to be used in the new ceiling are. Plywood is not an allowable material in this application per Section 603.1 of the 2006 IBC. Action required - Make needed corrections. Action taken - The plywood deck has been changed to 5/8" Type X gypsum.
Internal Plan Review (Res) Rejected 03/08/2011 03/08/2011
Mike Weisenborn
Building Plan Review Rejected 03/08/2011 03/08/2011
Mike Weisenborn
Health Dept Inspection
Corrective Action Required
03/08/2011

For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy. Action required - This comment is for information purposes.
Misc
Corrective Action Required
03/08/2011

For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit. Action required - Provide documentation of approval from the Health Department.
Plumb - Backflow general 608.3
Corrective Action Required
03/08/2011

2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination. Action required - Indicate the location and type of backflows to be installed.
Plumb - Backflow on beverage dispensers
Corrective Action Required
03/08/2011

2006 IPC 608.16.1 - Beverage dispensers. The water supply connection to beverage dispensers shall be protected against backflow by a backflow preventer conforming to ASSE 1022, CSA B64.3.1 or by an airgap. The backflow preventer device and the piping downstream therefrom shall not be affected by carbon dioxide gas. Action required - Indicate the location and type of backflows to be installed.
Plumb - Indirect waste for food handling fixtures
Corrective Action Required
03/08/2011

2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap. Action required - Indicate locations of indirect waste connections.
Misc
Corrective Action Required
03/08/2011

Type II Hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing machines. Action required - Provide a Type II hood over the dishwasher or provide documentation showing that one is not required.
Misc
Corrective Action Required
03/08/2011

The plans indicate that plywood is to be used in the new ceiling are. Plywood is not an allowable material in this application per Section 603.1 of the 2006 IBC. Action required - Make needed corrections.
License Tax Codes Approved 03/08/2011 03/08/2011
Mike Weisenborn
Fire Plan Review Approved 03/08/2011 03/07/2011
Jim Eden
Address numbers required
Resolved
03/15/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: The address shall be posted on all exterior doors.
Type I hood - Where required
Corrective Action Required
03/07/2011

2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Action required: The existing hood and suppression system shall meet current NFPA 17A standards. The system shall have documentation of a current annual inspection.
Portable fire extinguishers for commercial cooking equipment.
Resolved
03/15/2011

2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action required: Provide a K class extinguisher under the manual pull sation for the hood system. Verified at inspection.
Installation acceptance testing
Resolved
03/15/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test of the hood system.
Posting of occupant load
Resolved
03/15/2011

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inspection.
Misc
Corrective Action Required
03/07/2011

All existing emergency and exit lighting shall be operable at inspection.
Historical Preservation Review Approved 03/08/2011 02/25/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $163.40 $163.40 Paid 03/17/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Rough Electrical Inspection - Commercial Passed 3/21/2011 3/21/2011 at 12:00 AM 03/21/2011
Above Ceiling Inspection Partial 03/21/2011
Misc
Corrective Action Required
03/21/2011
PARTIAL - HARD CEILING OVER COOLER APPROVED ABOVE CEILING INSPECTION REQUIRED IN KITCHEN BEFORE NEW SECTION OF TILE IS INSTALLED. (EXISTING CEILING IN PLACE THROUGHOUT)
All Rough Inspection - Commercial Passed 05/17/2011
Misc
Corrective Action Required
03/21/2011
WALLS APROVED TO COVER-HARD CEILING APPROVED TO COVER. GAS TEST MAYBE REQUIRED IF GAS PIPING IS EXTENDED IN KITCHEN.
Above Ceiling Inspection Passed 5/17/2011 at 12:00 AM 05/17/2011
Misc
Resolved
05/17/2011
PARTIAL - HARD CEILING OVER COOLER APPROVED ABOVE CEILING INSPECTION REQUIRED IN KITCHEN BEFORE NEW SECTION OF TILE IS INSTALLED. (EXISTING CEILING IN PLACE THROUGHOUT)
Occupancy Inspection - Codes Commercial Full C of O 5/18/2011 at 12:00 AM 05/18/2011
Occupancy Inspection - Fire Passed 05/19/2011
Documents & Images
Date Uploaded File Type Document Name
03/08/2011 Letter Plan Review Conditions
03/17/2011 Letter Plan Review Conditions
03/17/2011 Letter Plan Review Conditions
03/17/2011 Letter Building Permit
03/21/2011 Letter Inspection Summary
05/17/2011 Letter Inspection Summary
05/18/2011 Letter Field Certificate of Occupancy
05/19/2011 Letter Fire Loss Reduction Form
05/19/2011 Letter Final Certificate of Occupancy
07/19/2011 Letter 20110719133527578.pdf
06/25/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home