Permit Application Status

PRCOM20100308


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20100308
Building Permit - Commercial
Certificate of Occupancy
CBL LEES SUMMIT EAST LLC
NEW TENANT FINISH
COMPLETE TENANT FINISH
12/17/2010
01/13/2011
06/28/2011
02/09/2011
Locations
Contacts
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
LYTLE CONSTRUCTION INC, Address:18505 E 163RD ST, Phone:(816) 524-7275  
WESTHUES ELECTRIC INC, Address:PO BOX 18220, Phone:(816) 356-5223  
LEXINGTON PLUMBING & HEATING, Address:1620 TROOST AVE, Phone:(816) 231-2254  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 01/13/2011
Mike Weisenborn
Building Plan Review Approved 01/13/2011 01/13/2011
Mike Weisenborn
Plumb - Required public toilet facilities
Resolved
01/13/2011

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - Provide documentation from the tenant that the restroom will be available to the customers.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Resolved
01/13/2011

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - Show how this requirement will be met for the breakroom sink.
Bldg - Toilet rooms - Floor surface and walls
Corrective Action Required
01/06/2011

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - To be verified on inspection.
Bldg - Toilet rooms - Walls
Corrective Action Required
01/06/2011

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - To be verified on inspection.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Resolved
01/13/2011

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Show how this requirement will be met.
Bldg - Doors - Door hardware
Resolved
01/13/2011

2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate. Action required - Provide information on the door hardware to be used.
Misc
Resolved
01/13/2011

The rear wall of this space is the only rated assembly. The demising walls are not. Action required - Make needed corrections to the plans.
Misc
Resolved
01/13/2011

Details and pecifications for the alteration to the plumbing system have not been provided. Action required - Provide additional information.
Fire Plan Review Approved 01/13/2011 01/11/2011
Jim Eden
Address numbers required
Carried Forward
01/11/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED- PROVIDE ADRESS ON ALL EXTERIOR DOORS, VERIFIED AT INSPECTION
Construction documents - Fire protection systems
Carried Forward
01/11/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED- PROVIDE DRAWINGS FOR SPRINKLER MODIFICATIONS
Installation acceptance testing
Corrective Action Required
01/07/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED- CALL 969-1316 TO SCHEDULE ALARM TESTING PRIOR TO THE FINAL
Misc
Corrective Action Required
01/07/2011

Fire Department 2006 IFC- 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ACTION REQUIRED- VERIFIED AT INSPECTION
Approved by Fire. Changed to rejected for re-submittal purposes.
Internal Plan Review (Res) Rejected 01/03/2011 12/30/2010
Mike Weisenborn
Building Plan Review Rejected 01/03/2011 12/30/2010
Mike Weisenborn
Plumb - Required public toilet facilities
Corrective Action Required
12/30/2010

2006 IPC 403.4 - Required public toilet facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The accessible route to public facilities shall not pass through kitchens, storage rooms, closets or similar spaces. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities. Action required - Provide documentation from the tenant that the restroom will be available to the customers.
Bldg - Accessibility - Kitchens and kitchenettes - 1109.4
Corrective Action Required
12/30/2010

2006 IBC 1109.4 - Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible in accordance with ICC A117.1. Action required - Show how this requirement will be met for the breakroom sink.
Bldg - Toilet rooms - Floor surface and walls
Corrective Action Required
12/30/2010

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - Show how this requirement will be met.
Bldg - Toilet rooms - Walls
Corrective Action Required
12/30/2010

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - Show how this requirement will be met.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
12/30/2010

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Show how this requirement will be met.
Bldg - Doors - Door hardware
Corrective Action Required
12/30/2010

2006 IBC 1008.1.8.1 - Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate. Action required - Provide information on the door hardware to be used.
Misc
Corrective Action Required
12/30/2010

The rear wall of this space is the only rated assembly. The demising walls are not. Action required - Make needed corrections to the plans.
Misc
Corrective Action Required
12/30/2010

Details and pecifications for the alteration to the plumbing system have not been provided. Action required - Provide additional information.
Fire Plan Review Rejected 01/03/2011 12/30/2010
Mike Weisenborn
Address numbers required
Corrective Action Required
12/27/2010

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED- PROVIDE ADRESS ON ALL EXTERIOR DOORS, VERIFIED AT INSPECTION
Construction documents - Fire protection systems
Corrective Action Required
12/27/2010

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. ACTION REQUIRED- PROVIDE DRAWINGS FOR SPRINKLER MODIFICATIONS
Installation acceptance testing
Corrective Action Required
12/27/2010

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED- CALL 969-1316 TO SCHEDULE ALARM TESTING PRIOR TO THE FINAL
Misc
Corrective Action Required
12/27/2010

Fire Department 2006 IFC- 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. ACTION REQUIRED- VERIFIED AT INSPECTION
Approved by Fire. Changed to rejected for re-submittal purposes.
Sprinkler Plan Review Released for Construction 12/28/2010
Jim Eden
Misc
Corrective Action Required
12/28/2010

Fire Department- IFC Section 901.5 Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service main and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the code official. Call 816-969-1300 to schedule flow test.
Misc
Corrective Action Required
12/28/2010

Fire Department-IFC Section 901.2 The code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Stamped plans for the sprinkler system received on December 22, 2010.
Misc
Corrective Action Required
12/28/2010

Fire Department- Flow control valves shall be marked with the address served and their locations identified (above ceiling). Verified at inspection.
Alarm Plan Review Released for Construction 12/28/2010
Jim Eden
License Tax Codes Approved 01/03/2011 12/21/2010
Mike Weisenborn
Zoning Review Approved 01/03/2011 12/21/2010
Mike Weisenborn
Historical Preservation Review Approved 01/03/2011 12/21/2010
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $81.41 $81.41 Paid 01/13/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Passed 1/19/2011 at 12:00 AM 01/19/2011
In-wall Inspection Passed 1/21/2011 at 12:00 AM 01/21/2011
Misc
Resolved
01/21/2011
ELECTRICAL RUN INSIDE FURRED WALL AROUND STEEL COLUMN-OK
Above Ceiling Inspection Passed 1/25/2011 at 12:00 AM 01/25/2011
Sprinkler - Flow Test Passed 1/7/2011 at 12:00 AM 02/03/2011
Alarm Test Passed 2/4/2011 at 12:00 AM 02/04/2011
Occupancy Inspection - Fire Passed 02/04/2011
Corrective Action Required
02/04/2011
Occupancy Inspection - Codes Commercial Failed 2/4/2011 at 12:00 AM 02/04/2011
Misc
Corrective Action Required
02/04/2011
PADDING AT PIPING UNDER SINK PER ADA
Misc
Corrective Action Required
02/04/2011
LABEL GAS SERVICE ENTRY PER DISCUSSION
Misc
Corrective Action Required
02/04/2011
PERMANENT LABEL AT ELECTRICAL SERVICE METER
Misc
Corrective Action Required
02/04/2011
ANSI/ADA SIGN AT RESTROOM
Misc
Corrective Action Required
02/04/2011
EMERGENCY EGRESS LIGHT REQUIRED OUTSIDE FRONT ENTRANCE.
Occupancy Inspection - Codes Commercial Full C of O 2/9/2011 at 12:00 AM 02/09/2011
Misc
Resolved
02/09/2011
PADDING AT PIPING UNDER SINK PER ADA
Misc
Resolved
02/09/2011
LABEL GAS SERVICE ENTRY PER DISCUSSION
Misc
Resolved
02/09/2011
PERMANENT LABEL AT ELECTRICAL SERVICE METER
Misc
Resolved
02/09/2011
ANSI/ADA SIGN AT RESTROOM
Misc
Resolved
02/09/2011
EMERGENCY EGRESS LIGHT REQUIRED OUTSIDE FRONT ENTRANCE.
Documents & Images
Date Uploaded File Type Document Name
12/28/2010 Letter Fire (Sprinkler) Plan Review
12/28/2010 Letter Fire (Sprinkler) Plan Review
12/30/2010 Letter Plan Review Conditions
01/13/2011 Letter Plan Review Conditions
01/13/2011 Letter Building Permit
01/19/2011 Letter Inspection Summary
01/19/2011 Letter Inspection Summary
01/21/2011 Letter Inspection Summary
01/25/2011 Letter Inspection Summary
02/04/2011 Letter Fire Loss Reduction Form
02/04/2011 Letter Inspection Summary
02/09/2011 Letter Final Certificate of Occupancy
02/10/2011 Letter Final Certificate of Occupancy
06/27/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home