Permit Application Status

PRCOM20100205


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20100205
Building Permit - Commercial
Certificate of Occupancy
CHANGE OF TENANT
Tenant finish with canopy addition
11/30/2010
12/20/2010
06/08/2011
03/03/2011
Locations
Contacts
LYTLE CONSTRUCTION INC, Address:18505 E 163RD ST, Phone:(816) 524-7275  
TEMP-CON LLC, Address:15670 S KEELER ST, Phone:(913) 768-4888  
FOUR STAR ELECTRIC INC, Address:6220 NW KELLY DR, Phone:(816) 587-8157  
BOSS MECHANICAL, Address:P O BOX 998, Phone:(816) 413-0099  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 02/22/2011 02/17/2011
Mike Weisenborn
Internal Plan Review (Res) Approved 12/20/2010 12/20/2010
Codes Admin
Fire Plan Review Approved 12/28/2010 12/20/2010
Mike Weisenborn
Address numbers required
Corrective Action Required
12/22/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required. Provide on the fron t and rear doors. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
12/22/2010

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one 2A:10B:C fire extinguisher at a conspicuous and accessible location. Verified at inspection.
Misc
Corrective Action Required
12/22/2010

Fire Department- Exit doors and doors going to exits shall be openable without a key, tool, or special knowledge. For information only. Verified at inspection.
Building Plan Review Approved 12/20/2010 12/20/2010
Mike Weisenborn
Project cost
Corrective Action Required
12/17/2010

The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the project cost.
Security Code
Corrective Action Required
12/17/2010

The work authorized by this permit shall be constructed to comply with the Security Code provisions. (Chapter 7, Article 14 of the Lees Summit Code of Ordinances) Action required - Contact the Planning and Development Department at 816-969-1600 regarding the Security Code provisions and review. Per Bob McKay, the full building permit may be issued prior to approval of the security review. Alterations to the approved building permit plans may be required do to the the security review.
Misc
Corrective Action Required
12/20/2010

The Final Development Plan must be approved prior to issuing full building permits. Action required - This comment is for information purposes. Per Bob McKay, the full building permit may be issued prior to fdp approval. Alterations to the approved building permit plans may be required do to the fdp review.
Misc
Resolved
12/20/2010

2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. Action required - Make needed corrections. The drinking fountain has been removed.
Bldg - Horizontal projections - General
Resolved
12/20/2010

2006 IBC 1003.3.3 - Horizontal projections. Structural elements, fixtures or furnishings shall not project horizontally from either side more than 4 inches over any walking surface between the heights of 27 inches and 80 inches above the walking surface. Action required - A side view of the drinking fountain is not provided so I can not determine if it meets this requirement or not. Provide additional information. The drinking fountain has been removed.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
12/17/2010

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - An accessible teller window is not shown. Make needed corrections.
Misc
Resolved
12/20/2010

2006 IPC 409.2 - Water Connection. The water supply to a dishwashing machine shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608. Action required - The architectural plans indicate a dishwasher is to be installed in the breakroom but it is not referenced on the plumbing plans. Make needed corrections. Information has been added.
Misc
Corrective Action Required
12/17/2010

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Misc
Resolved
12/20/2010

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The door from the break room to the hall and the door from the teller area to the work area do not meet this requirement. Per resumittal.
Misc
Resolved
12/20/2010

Per the code, only one means of egress is required from the space at this time. The plans provide two means of egress, one of which is through the future expansion area which is unfinished at this time. The Codes Administration Department is not comfortable with using the rear door as a means of egress as this is an uncontrolled space. Action required - Remove the exit signage indicating the rear door as a means of egress or provide a defined path to the exterior door. The exit signs have been removed.
Internal Plan Review (Res) Rejected 12/10/2010 12/10/2010
Mike Weisenborn
Fire Plan Review Rejected 12/10/2010 12/10/2010
Mike Weisenborn
Address numbers required
Corrective Action Required
12/06/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required. Provide on the fron t and rear doors. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
12/06/2010

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one 2A:10B:C fire extinguisher at a conspicuous and accessible location. Verified at inspection.
Misc
Corrective Action Required
12/06/2010

Fire Department- Exit doors and doors going to exits shall be openable without a key, tool, or special knowledge. For information only. Verified at inspection.
Building Plan Review Rejected 12/10/2010 12/10/2010
Mike Weisenborn
Project cost
Corrective Action Required
12/01/2010

The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the project cost.
Security Code
Corrective Action Required
12/01/2010

The work authorized by this permit shall be constructed to comply with the Security Code provisions. (Chapter 7, Article 14 of the Lees Summit Code of Ordinances) Action required - Contact the Planning and Development Department at 816-969-1600 regarding the Security Code provisions and review.
Misc
Corrective Action Required
12/10/2010

The Final Development Plan must be approved prior to issuing full building permits. Action required - This comment is for information purposes.
Misc
Corrective Action Required
12/10/2010

2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. Action required - Make needed corrections.
Bldg - Horizontal projections - General
Corrective Action Required
12/10/2010

2006 IBC 1003.3.3 - Horizontal projections. Structural elements, fixtures or furnishings shall not project horizontally from either side more than 4 inches over any walking surface between the heights of 27 inches and 80 inches above the walking surface. Action required - A side view of the drinking fountain is not provided so I can not determine if it meets this requirement or not. Provide additional information.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
12/10/2010

Codes Administration - 2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - An accessible teller window is not shown. Make needed corrections.
Misc
Corrective Action Required
12/10/2010

2006 IPC 409.2 - Water Connection. The water supply to a dishwashing machine shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608. Action required - The architectural plans indicate a dishwasher is to be installed in the breakroom but it is not referenced on the plumbing plans. Make needed corrections.
Misc
Corrective Action Required
12/10/2010

ICC/ANSI A117.1 2003 804.6.6 - Refrigerator/Freezer. Combination refrigerators and freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches maximum above the floor when the shelves are installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach to the space dedicated to a refrigerator/freezer, shall be provided. The centerline of the clear floor space shall be offset 24 inches maximum from the centerline of the dedicated space. Action required - This comment is for information purposes.
Misc
Corrective Action Required
12/10/2010

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The door from the break room to the hall and the door from the teller area to the work area do not meet this requirement.
Misc
Corrective Action Required
12/10/2010

Per the code, only one means of egress is required from the space at this time. The plans provide two means of egress, one of which is through the future expansion area which is unfinished at this time. The Codes Administration Department is not comfortable with using the rear door as a means of egress as this is an uncontrolled space. Action required - Remove the exit signage indicating the rear door as a means of egress or provide a defined path to the exterior door.
Historical Preservation Review Approved 12/10/2010 12/10/2010
Mike Weisenborn
License Tax Codes Approved 12/10/2010 12/10/2010
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,143.80 $1,143.80 Paid 12/20/2010
8331507-Sewer Connection Fee $90.00 $90.00 Paid 12/20/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 12/27/2010 at 12:00 AM 12/27/2010
Underslab Plumbing Inspection - Commercial Passed 12/27/2010 at 12:00 AM 12/27/2010
In-wall Inspection Partial 1/4/2011 at 12:00 AM 01/04/2011
Misc
Partial Correction
01/04/2011
OK TO COVER WHEN READY: SOFFITS; WALL FRAMING AND IN-WALL SYSTEMS EXCEPT PLUMBING WALLS
Misc
Corrective Action Required
01/04/2011
IN-WALL PLUMBING: INSTALL CODE-CONFORMING SHIELD PLATES TO PROTECT PVC AND COPPER PIPING WHERE LESS THAN 1-1/2" FROM FACE OF FRAMING; INSTALL GROMMETS TO PROTECT COPPER PIPING WHERE PASSING THROUGH STEEL STUDS
Footing Inspection - Commercial Partial 1/6/2011 at 12:00 AM 01/06/2011
Misc
Partial Correction
01/06/2011
OK TO POUR WHEN READY: TWO CANOPY FOOTINGS
In-wall Inspection Passed 1/6/2011 at 12:00 AM 01/06/2011
Misc
Resolved
01/06/2011
OK TO COVER WHEN READY: SOFFITS; WALL FRAMING AND IN-WALL SYSTEMS EXCEPT PLUMBING WALLS
Misc
Resolved
01/06/2011
IN-WALL PLUMBING: INSTALL CODE-CONFORMING SHIELD PLATES TO PROTECT PVC AND COPPER PIPING WHERE LESS THAN 1-1/2" FROM FACE OF FRAMING; INSTALL GROMMETS TO PROTECT COPPER PIPING WHERE PASSING THROUGH STEEL STUDS
Above Ceiling Inspection Partial 1/6/2011 at 12:00 AM 01/06/2011
Misc
Partial Correction
01/06/2011
OK TO COVER WHEN READY GWB SOFFITS AND SUPPORTS THEREOF
Footing Inspection - Commercial Passed 1/7/2011 at 12:00 AM 01/07/2011
Misc
Resolved
01/07/2011
OK TO POUR WHEN READY: TWO CANOPY FOOTINGS
Rough Framing Inspection - Commercial Passed 1/18/2011 at 12:00 AM 01/18/2011
All Rough Inspection - Commercial Passed 1/21/2011 at 12:00 AM 01/21/2011
Rough Framing Inspection - Commercial Passed 1/26/2011 at 12:00 AM 01/26/2011
Above Ceiling Inspection Partial 2/1/2011 at 12:00 AM 02/01/2011
Misc
Resolved
02/01/2011
OK TO COVER WHEN READY GWB SOFFITS AND SUPPORTS THEREOF
Misc
Partial Correction
02/01/2011
ACT CEILING GRID AND ABOVE-CEILING SYSTEMS OK FOR PLACEMENT OF CUT BORDER TILES ONLY; SUBJECT TO FULL INSPECTION AFTER HVAC WORK IS COMPLETED. ENSURE MC CABLES ARE SECURED TO STRUCTURE OR CONDUIT WITHIN 12" OF ENTRY TO BOXES WHEREVER POSSIBLE.
Occupancy Inspection - Codes Commercial Not Ready 2/1/2011 at 12:00 AM 02/01/2011
Misc
Corrective Action Required
02/01/2011
SLOPE OF RAMPS MAY NOT EXCEED 1:12 FOR ADA/ANSI COMPLIANCE. SEE SOUTH ENTRANCE.
Misc
Corrective Action Required
02/01/2011
STEPS/STAIRS AT COMMERCIAL BUILDINGS MUST HAVE COMPLIANT HANDRAILS -- ONE EACH SIDE OF STAIR. SEE NORTH ENTRANCE.
Above Ceiling Inspection Failed 2/3/2011 02/03/2011
Misc
Partial Correction
02/01/2011
ACT CEILING GRID AND ABOVE-CEILING SYSTEMS OK FOR PLACEMENT OF CUT BORDER TILES ONLY; SUBJECT TO FULL INSPECTION AFTER HVAC WORK IS COMPLETED. ENSURE MC CABLES ARE SECURED TO STRUCTURE OR CONDUIT WITHIN 12" OF ENTRY TO BOXES WHEREVER POSSIBLE.
Above Ceiling Inspection Passed 2/7/2011 at 12:00 AM 02/07/2011
Misc
Resolved
02/07/2011
ACT CEILING GRID AND ABOVE-CEILING SYSTEMS OK FOR PLACEMENT OF CUT BORDER TILES ONLY; SUBJECT TO FULL INSPECTION AFTER HVAC WORK IS COMPLETED. ENSURE MC CABLES ARE SECURED TO STRUCTURE OR CONDUIT WITHIN 12" OF ENTRY TO BOXES WHEREVER POSSIBLE.
Miscellaneous Inspection Partial 2/9/2011 at 12:00 AM 02/09/2011
Misc
Corrective Action Required
02/09/2011
COMPLIANCE OF ACCESSIBILITY RAMP AT SOUTH ENTRANCE IN QUESTION -- INVESTIGATION IN PROGRESS.
Occupancy Inspection - Codes Commercial Failed 2/17/2011 at 12:00 AM 02/17/2011
Misc
Corrective Action Required
02/01/2011
SLOPE OF RAMPS MAY NOT EXCEED 1:12 FOR ADA/ANSI COMPLIANCE. SEE SOUTH ENTRANCE.
Misc
Corrective Action Required
02/01/2011
STEPS/STAIRS AT COMMERCIAL BUILDINGS MUST HAVE COMPLIANT HANDRAILS -- ONE EACH SIDE OF STAIR. SEE NORTH ENTRANCE.
Misc
Corrective Action Required
02/17/2011
PER NEC 600.3 EACH ELEMENT OF LIGHTED SIGNS MOUNTED DIRECTLY ON BUILDING SURFACE MUST BEAR LISTING LABEL VISIBLE FOR INSPECTION.
Misc
Corrective Action Required
02/17/2011
EXTERIOR BUILDING FINISH MUST BE COMPLETED. SEE DRIVE-THROUGH AND ROOFTOP TOWER AT SOUTH ENTRANCE.
Misc
Corrective Action Required
02/17/2011
ROOFTOP INSPECTION: ALL WORK AT ROOFTOP SUBJECT TO INSPECTION WHEN COMPLED (CLEAR/CLEAN OF DEBRIS AND UNUSED MATERIAL)
Occupancy Inspection - Fire Temporary C of O 2/17/2011 at 12:00 AM 02/17/2011
Corrective Action Required
02/17/2011
PRCOM20100205 (1) Post the suites address on the rear door (2) NW glass man door - remove the address and label the door with the wording " THIS DOOR BLOCKED"
Corrective Action Required
02/17/2011
Occupancy Inspection - Codes Commercial Failed 2/17/2011 at 12:00 AM 02/17/2011
Misc
Corrective Action Required
02/17/2011
SLOPE OF RAMPS MAY NOT EXCEED 1:12 FOR ADA/ANSI COMPLIANCE. SEE SOUTH ENTRANCE.
Misc
Corrective Action Required
02/17/2011
STEPS/STAIRS AT COMMERCIAL BUILDINGS MUST HAVE COMPLIANT HANDRAILS -- ONE EACH SIDE OF STAIR. SEE NORTH ENTRANCE.
Misc
Corrective Action Required
02/17/2011
PER NEC 600.3 EACH ELEMENT OF LIGHTED SIGNS MOUNTED DIRECTLY ON BUILDING SURFACE MUST BEAR LISTING LABEL VISIBLE FOR INSPECTION.
Misc
Corrective Action Required
02/17/2011
EXTERIOR BUILDING FINISH MUST BE COMPLETED. SEE DRIVE-THROUGH AND ROOFTOP TOWER AT SOUTH ENTRANCE.
Misc
Corrective Action Required
02/17/2011
ROOFTOP INSPECTION: ALL WORK AT ROOFTOP SUBJECT TO INSPECTION WHEN COMPLED (CLEAR/CLEAN OF DEBRIS AND UNUSED MATERIAL)
A604.5.1 Fixed Side Wall Grab Bars
Corrective Action Required
02/17/2011
WATER CLOSETS AND TOILET COMPARTMENTS. Fixed sidewall grab bars shall be 42 inches (1065 mm) minimum in length, located 12 inches (305 mm) maximum from the rear wall and extending 54 inches (1370 mm) minimum from the rear wall. In addition, a vertical grab bar 18 inches (455 mm) minimum in length shall be mounted with the bottom of the bar located between 39 inches (990 mm) and 41 inches (1040 mm) above the floor, and with the center line of the bar located between 39 inches (990 mm) and 41 inches (1040 mm) from the rear wall. EXCEPTIONS: 1. In Type A and Type B units, the vertical grab bar component is not required. 2. In a Type B unit, when a side wall is not available for a 42-inch (1065 mm) grab bar, the sidewall grab bar shall be permitted to be 18 inches (455 mm) minimum in length, located 12 inches (305 mm) maximum from the rear wall and extending 30 inches (760 mm) minimum from the rear wall.
E110.22 Identification of disconnection means
Corrective Action Required
02/17/2011
ELECTRICAL LABELING- LABEL PANELS IN SORAGE ROOM, IDENTIFY PANELS BEHIND DBL DOORS IN BREAK ROOM. LABEL METER WITH CORRECT ADDRESS
Misc
Corrective Action Required
02/17/2011
APPROVED TO STOCK AND TRAINNING ONLY SEE FIRE DEPART. FOR APPROVAL (FIRE DEPART- OK FOR TCO)
Occupancy Inspection - Codes Commercial Temporary C of O 2/18/2011 at 12:00 AM 02/18/2011
Misc
Corrective Action Required
02/17/2011
SLOPE OF RAMPS MAY NOT EXCEED 1:12 FOR ADA/ANSI COMPLIANCE. SEE SOUTH ENTRANCE.
Misc
Corrective Action Required
02/17/2011
STEPS/STAIRS AT COMMERCIAL BUILDINGS MUST HAVE COMPLIANT HANDRAILS -- ONE EACH SIDE OF STAIR. SEE NORTH ENTRANCE. TEMP HANDRAILS IN PLACE
Misc
Corrective Action Required
02/17/2011
PER NEC 600.3 EACH ELEMENT OF LIGHTED SIGNS MOUNTED DIRECTLY ON BUILDING SURFACE MUST BEAR LISTING LABEL VISIBLE FOR INSPECTION. REAR SIGN OK
Misc
Corrective Action Required
02/17/2011
EXTERIOR BUILDING FINISH MUST BE COMPLETED. SEE DRIVE-THROUGH AND ROOFTOP TOWER AT SOUTH ENTRANCE.
Misc
Resolved
02/18/2011
ROOFTOP INSPECTION: ALL WORK AT ROOFTOP SUBJECT TO INSPECTION WHEN COMPLED (CLEAR/CLEAN OF DEBRIS AND UNUSED MATERIAL)
A604.5.1 Fixed Side Wall Grab Bars
Resolved
02/18/2011
WATER CLOSETS AND TOILET COMPARTMENTS. Fixed sidewall grab bars shall be 42 inches (1065 mm) minimum in length, located 12 inches (305 mm) maximum from the rear wall and extending 54 inches (1370 mm) minimum from the rear wall. In addition, a vertical grab bar 18 inches (455 mm) minimum in length shall be mounted with the bottom of the bar located between 39 inches (990 mm) and 41 inches (1040 mm) above the floor, and with the center line of the bar located between 39 inches (990 mm) and 41 inches (1040 mm) from the rear wall. EXCEPTIONS: 1. In Type A and Type B units, the vertical grab bar component is not required. 2. In a Type B unit, when a side wall is not available for a 42-inch (1065 mm) grab bar, the sidewall grab bar shall be permitted to be 18 inches (455 mm) minimum in length, located 12 inches (305 mm) maximum from the rear wall and extending 30 inches (760 mm) minimum from the rear wall.
E110.22 Identification of disconnection means
Resolved
02/18/2011
ELECTRICAL LABELING- LABEL PANELS IN SORAGE ROOM, IDENTIFY PANELS BEHIND DBL DOORS IN BREAK ROOM. LABEL METER WITH CORRECT ADDRESS
Misc
Corrective Action Required
02/17/2011
APPROVED FOR 14DAY TCO SEE FIRE DEPART. FOR APPROVAL (FIRE DEPART- OK FOR TCO)
Occupancy Inspection - Fire Passed 2/22/2011 at 12:00 AM 02/23/2011
Corrective Action Required
02/23/2011
Occupancy Inspection - Codes Commercial Full C of O 3/3/2011 3/3/2011 at 12:00 AM 03/03/2011
Misc
Resolved
03/03/2011
SLOPE OF RAMPS MAY NOT EXCEED 1:12 FOR ADA/ANSI COMPLIANCE. SEE SOUTH ENTRANCE.
Misc
Resolved
03/03/2011
STEPS/STAIRS AT COMMERCIAL BUILDINGS MUST HAVE COMPLIANT HANDRAILS -- ONE EACH SIDE OF STAIR. SEE NORTH ENTRANCE. TEMP HANDRAILS IN PLACE
Misc
Resolved
03/03/2011
PER NEC 600.3 EACH ELEMENT OF LIGHTED SIGNS MOUNTED DIRECTLY ON BUILDING SURFACE MUST BEAR LISTING LABEL VISIBLE FOR INSPECTION. REAR SIGN OK
Misc
Resolved
03/03/2011
EXTERIOR BUILDING FINISH MUST BE COMPLETED. SEE DRIVE-THROUGH AND ROOFTOP TOWER AT SOUTH ENTRANCE.
Misc
Resolved
03/03/2011
APPROVED FOR 14DAY TCO SEE FIRE DEPART. FOR APPROVAL (FIRE DEPART- OK FOR TCO)
Documents & Images
Date Uploaded File Type Document Name
12/06/2010 Letter Plan Review Conditions
12/10/2010 Letter Plan Review Conditions
12/20/2010 Letter Plan Review Conditions
12/20/2010 Letter Building Permit
12/27/2010 Letter Inspection Summary
01/04/2011 Letter Inspection Summary
01/06/2011 Letter Inspection Summary
01/07/2011 Letter Inspection Summary
01/18/2011 Letter Inspection Summary
01/21/2011 Letter Inspection Summary
01/26/2011 Letter Inspection Summary
02/01/2011 Letter Inspection Summary
02/03/2011 Letter Inspection Summary
02/03/2011 Letter Inspection Summary
02/07/2011 Letter Inspection Summary
02/17/2011 Letter Fire Loss Reduction Form
02/17/2011 Letter Inspection Summary
02/18/2011 Letter Temporary Certificate of Occupancy
02/23/2011 Letter Fire Loss Reduction Form
02/23/2011 Letter Fire Loss Reduction Form
03/03/2011 Letter Field Certificate of Occupancy
03/04/2011 Letter Final Certificate of Occupancy
06/27/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home