PL2017191
Hawthorn Ridge 1st Plat - Hook Rd. Improvements
Engineering Plan Review
Engineering Plan Review
Approved
09/14/2017
CMH PARKS INC
traffic improvements to Hook Rd.
Locations
Contacts
Not shown for privacy reasons.
Not shown for privacy reasons.
CMH PARKS INC, Address:5000 CLAYTON RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Traffic Review Approved with Conditions 12/21/2018 01/19/2018
Gene Williams, P.E.
Engineering Review Approved with Conditions 12/21/2018 01/19/2018
Gene Williams, P.E.
Engineering Review Corrections 10/03/2017 10/02/2017
Gene Williams, P.E.
Corrective Action Required
10/02/2017

An erosion and sediment control plan appeared to be missing.
Corrective Action Required
10/02/2017

Driveways impacted by this project should be replaced with KCMMB concrete from the roadway, to the right of way line.
Corrective Action Required
10/02/2017

The minimum size driveway culvert is 15". If using CMP, it should be aluminized.
Corrective Action Required
10/02/2017

Sheet C317: KCMMB concrete mix should be specified for the driveway typical section.
Traffic Review Corrections 10/03/2017 10/02/2017
Michael Park
Corrective Action Required
10/02/2017

Sheet C303. Typical Road Sections are inconsisent with the Saw Cut/Mill & Overlay detail.
Corrective Action Required
10/02/2017

Is the existing manhole structure and lid near Station 29+40 (Note for Contractor to Raise Lid 0.56') traffic rated?
Corrective Action Required
10/02/2017

Sheet C305. Detour Plan is incomplete and not efficient (consideration of northbound traffic is lacking north of M-150, use of Scherer Road should be signed, the signing for traffic south of M-150 can be minimized/relocated, etc.). Use of M-150 as detour route requires MoDOT permitting and review. Hook Road west of Pryor Road should not be part of the detour route.
Corrective Action Required
10/02/2017

Sheet C306. Use consistent scale on a roadway plan across match lines.
Corrective Action Required
10/02/2017

Plan sheets generally lack complete details, dimensions, stations/offsets for construction, inspection and record drawings.
Corrective Action Required
10/02/2017

Driveway culverts do not align with ditch sections.
Corrective Action Required
10/02/2017

Driveways require at least 50' depth of hard surface from edge of pavement per ordinances. Where this condition exceeds right-of-way or ability to acquire temporary construction easement, a waiver may be considered.
Corrective Action Required
10/02/2017

Are the locations of mail boxes (relocated) adjacent to the properties addressed? Has this issue been coordinated with the postal service and their (as well as property owner) preference been accommodated? It's possible some of these mail boxes may be relocated across the street if better/safer access can be provided.
Corrective Action Required
10/02/2017

Pavement Marking Sheets. The diagonal lines between Arbor Valley Dr and Arborridge Drive are in the wrong direction.
Corrective Action Required
10/02/2017

Pavement Marking Sheets. Pavement markings for the right-turn lanes and left-turn lanes are missing.
Corrective Action Required
10/02/2017

Signing Sheets. The R3-8 lane use signs should be removed.
Hearings

There are no hearings for this planning application.

Documents & Images
Date Uploaded File Type Document Name
01/15/2020 check to city for shoulder improvements
12/14/2017 Plans 17-12-13_Williams_Response Letter
12/14/2017 Plans 2017.12.13 Hook Road Improvement Plans
12/14/2017 Plans 2017.12.13. Trans.Resubmittal.Public Plans
10/17/2017 Plans C317 DETAILS
10/17/2017 Plans C316 CROSS SECTION PROFILE (3-2)
10/17/2017 Plans C315 CROSS SECTION PROFILE (3)
10/17/2017 Plans C314 CROSS SECTION PROFILE (2-2)
10/17/2017 Plans C313 CROSS SECTION PROFILE (2)
10/17/2017 Plans C312 CROSS SECTION PROFILE (1-2)
10/17/2017 Plans C311 CROSS SECTION PROFILE 1
10/17/2017 Plans C310 STORM SEWER PLAN & PROFILE
10/17/2017 Plans C309 ROADWAY SPOT ELEVATIONS
10/17/2017 Plans C308 PAVEMENT MARKING PLAN
10/17/2017 Plans C307 DIMENSION PLAN
10/17/2017 Plans C306 ROADWAY PAVEMENT PLAN
10/17/2017 Plans C305 DETOUR PLAN
10/17/2017 Plans C304 EXISTING & DEMOLITION PLAN
10/17/2017 Plans C303 GRADING PLAN
10/17/2017 Plans C302 GENERAL NOTES
10/17/2017 Plans C301 TITLE SHEET
10/03/2017 Letter DE-Comment Letter (Engineering Plans)
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home