Planning Application Status

PL2023170




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2023170
Wilshire Hills 4th Plat - Public Sanitary
Engineering Plan Review
Engineering Plan Review
Approved
06/27/2023
JEFFREY E SMITH INV CO LC
CREATE A LOT, TRACT AND ASSOCIATED ROW ASSOCIATED WITH DEVELOPMENT OF A 52 UNIT APARTMENT BUILDING
Locations
Contacts
JEFFREY E SMITH INV CO LC, Address:PO BOX 7688  
ENGINEERING SURVEYS & SERVICES, Address:1113 FAY ST, Phone:(573) 449-2646  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review No Comments 03/05/2024 03/05/2024
Gene Williams, P.E.
Engineering Review Approved with Conditions 12/12/2023 12/12/2023
Gene Williams, P.E.
Waiting for receipt of an Engineer’s Estimate of Probable Construction Costs and Payment of the Engineering Plan Review and Inspection Fee based on an accepted estimate above per Gene approval on 12/12/23.
Engineering Review Approved with Conditions 11/01/2023 11/02/2023
Gene Williams, P.E.
Engineering Review Corrections 07/14/2023 07/17/2023
Gene Williams, P.E.
Corrective Action Required
07/17/2023

Why are there two (2) cover sheets for this project?
Corrective Action Required
07/17/2023

Please rename the plans to "Wilshire Hills 4th Plat - Sanitary Sewer" or equivalent.
Corrective Action Required
07/17/2023

Normal procedure is to show a general overview of the entire sanitary sewer line in plan view format on one (1) sheet if possible. It appears this is possible. Please provide a general overview sheet of the entire line shown on one (1) sheet.
Corrective Action Required
07/17/2023

The general overview sheet discussed above should provide proposed lot lines that correspond with the plat. No such lot lines appear to exist. Please provide the lot lines to determine whether the length of the sanitary line extension is sufficient to serve all lots within Wilshire Hills 4th Plat.
Corrective Action Required
07/17/2023

Provide a callout of all existing city manhole numbers on all plan sheets. In this instance, the existing manhole that is being connected is #11-277. Please update as appropriate.
Corrective Action Required
07/17/2023

Sheet C4.02: It appears there is a missing storm crossing in the profile at around 7+65.
Corrective Action Required
07/17/2023

Sanitary lines shall be SDR 26 rather than SDR 35. Please revise.
Corrective Action Required
07/17/2023

Sanitary sewer stubs shall be SDR 26 rather than SDR 35. Please revise.
Corrective Action Required
07/17/2023

The service connection called “standard” at 7+78.96 is approx. 7’ deep at the cleanout and 11.5’ where it connects to the sewer main. The service connection at 3+82.71, labeled a deep service connection, is approx. 7’ deep at cleanout and 13’ where it connects to the sewer main. One doesn’t seem to be deeper than the other. Is there a difference in these connections?
Corrective Action Required
07/17/2023

Tracer wire called out for service at 2+24.74 but none of the others. Tracer wire required for all service connections/stubs
Corrective Action Required
07/17/2023

We noticed an existing flow line "in" elevation listed on manhole 11-277. We checked an old manhole inspection photo and identified a pipe in, and a pipe out on what is indicated to be a dead end manhole so I suspect that there is an existing stub with a cap on it. The stub should be removed and a new pipe shall be installed into the manhole in lieu of using a coupling to connect to the end of the stub.
Hearings

There are no hearings for this planning application.

Documents & Images
Date Uploaded File Type Document Name
06/27/2023 Plans Sanitary Sewer Extension Plans_Rev0_PL2023170
07/17/2023 Letter Comment Letter (Engineering Plans)_PL2023170
10/17/2023 Letter Response Letter_Rev0_2023172
10/18/2023 Engineer Report/Study Hydraulic Report (Public Improvments)_PL2023170
10/18/2023 Plans Sewer Plans_Rev0_PL2023170
11/02/2023 Letter Approval Email_Rev0_PL2023170
12/01/2023 Plans Sewer Plans_Rev1_PL2023170
12/12/2023 Email Approval E-mail_Rev1_PL2023170
02/19/2024 Plans Sanitary Sewer Extension Plans_Rev1_PL2023170
04/01/2024 Plans Sewer Plans_Rev1_PL2023170
04/17/2024 Plans Sewer Plans_Rev2_PL2023170
05/14/2024 Engineers Estimate Probable Construction Costs Estimate_PL2023170
05/22/2024 Engineers Estimate Fee Worksheet_PL2023170
05/22/2024 Plans Stamped Approved Plans_PL2023170
05/22/2024 Email Approval Email_PL2023170
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home