Summary
PL2021079
WOODLAND OAKS - OFFSITE SANITARY SEWER (located in Woodland Shores subdivision, to the south of Woodland Oaks)
Engineering Plan Review
Engineering Plan Review
Void
03/02/2021
WOODLAND OAKS LLC
voided - this was for a pipe bursting project that never came to fruition due to impracticality of the job.
Locations
Contacts
WOODLAND OAKS LLC, Address:656 BAYBERRY LN STE 101  
NOBLE FAMILY REVOCABLE TRUST, Address:2345 NE LAKEBREEZE LN  
DENNIS CALEB M & KATIE L, Address:2321 NE LAKE BREEZE LN  
HAUB WAYNE B & SHIRLEY A, Address:2333 LAKEBREEZE LANE  
WOODRUM DEBORAH & TAMARA, Address:2325 NE LAKE BREEZE LN  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review No Comments 05/25/2021 05/25/2021
Gene Williams, P.E.
Engineering Review Corrections 03/26/2021 03/26/2021
Gene Williams, P.E.
Corrective Action Required
03/26/2021

HDR’s review recommended the upsizing of segments 26-192 to 26-174 and 26-174 to 26-173. The plans from ES did not include the upsizing of segment 26-174 to 26-173.
Corrective Action Required
03/26/2021

Existing manhole numbers should be shown.
Corrective Action Required
03/26/2021

Sheet C.402: Sta. 2+14.60 should be 2+09.74?
Corrective Action Required
03/26/2021

Specifications don’t seem to be aligned with the intent. Sheet C.402 called out PVC replacement pipe. Specification seems geared towards HDPE with little to no mention of PVC. PVC has to be restrained to be used for pipe bursting. This needs to be clarified in the specifications. Also, PVC can’t be used with pneumatic bursting head.
Corrective Action Required
03/26/2021

References are made to VCP jacking pipe and fittings and FRP and Polymer concrete jacking pipe and fittings. These paragraphs don’t seem necessary unless there is something that I am missing
Corrective Action Required
03/26/2021

There are questions concerning the final flowline elevation of the pipe once pipe bursting is complete. It appears at least two of the manholes may have no drop across the inverts in the present condition. After pipe bursting, it is our understanding the pipe will match the existing flowline elevation, and the pipe bursting will cause the pipe to move in the upward direction rather than downward. Please confirm, because if this is not the case, there may be issues.
Corrective Action Required
03/26/2021

Please change the title of the plans to "Woodland Oaks Off-Site Sanitary Sewer Improvements". If desired, you may choose to note that the improvements are located within the Woodland Shores subdivision, but the title needs to reflect Woodland Oaks.
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home