PL2020227
Whispering Woods 2nd Plat - Public Sanitary
Engineering Plan Review
Engineering Plan Review
Complete
08/10/2020
ROBBINS KAREN
Locations
Contacts
Snyder & Associates, Address:802 Francis St, Phone:(816) 364-5222  
ROBBINS KAREN, Address:1509 SW 27TH ST  
RICKY & LINDA KING TRUST DATED 12/21/2021, Address:1601 SW 27TH ST  
KERBER LOURIE S & THOMAS J, Address:265 LEMONWOOD LN  
BURAU PAIGE & AUSTIN, Address:1609 SW 27TH ST  
BARG SAMUEL A & AMY L, Address:1613 SW 27TH ST  
SCHLOSSER JEREMY & KRISTIN, Address:1617 SW 27TH ST  
GUNTER GARTH & DAWNA, Address:1621 SW 27TH ST  
FOX MICHAEL & KIRSTIN, Address:1701 SW 27TH ST  
COLEMAN BRANDON & STEPHANIE, Address:1705 SW 27TH ST  
D AND D BUILDING INC, Address:1100 NE DELTA SCHOOL RD  
HOLLIS JACOB B, Address:1604 SW 27TH ST  
FISCHER ADAM B, Address:906 THOMPSON BLVD  
STRECK WILLIAM P & HALEY L, Address:1612 SW 27TH ST  
D&D BUILDING INC, Address:1100 NE DELTA SCHOOL RD  
DASILVA PEREZ ALBERTO R & KERKHOFF PEREZ JULIANE, Address:1620 SW 27TH ST  
UTZ HAYLEY R, Address:1624 SW 27TH ST  
JARNEVIC LIVING TRUST DATED 9-7-2011 AMEND 11-27-2018, Address:1700 SW 27TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Record Drawings Review No Comments 11/24/2021 11/23/2021
Gene Williams, P.E.
Engineering Review No Comments 10/12/2021 10/12/2021
Gene Williams, P.E.
Engineering Review No Comments 10/22/2020 10/08/2020
Gene Williams, P.E.
Engineering Review Corrections 10/08/2020 10/08/2020
Gene Williams, P.E.
Corrective Action Required
10/08/2020

Notes are shown on the revised profile views which mention the use of unapproved private lateral materials. If using notes, please refer to the approved standard drawing provided in the standard details section. Tees are not allowed, only wye connections.
Engineering Review Corrections 08/21/2020 08/21/2020
Gene Williams, P.E.
Corrective Action Required
08/21/2020

The City now requires that all sanitary sewer manholes be centered within the pavement. Please revise. It will be acceptable to skew the angle of the line where the existing manhole B-4, provided that proper horizontal clearance can be maintained between water lines and storm lines and structures.
Corrective Action Required
08/21/2020

Sheet 5: The proposed line between existing manhole B-4 and proposed B-5 appeared to be missing from the profile view.
Corrective Action Required
08/21/2020

Sheet 6: Please edit the standard drawing for the manhole lid to read "SEWER", in addition to "City of Lee's Summit" along the outer ring. This can be in the form of a note next to the drawing, with the word "STORM" "x-ed" out, as long as it is clearly-visible to a contractor and/or inspector in the field.
Corrective Action Required
08/21/2020

Sheet 3: Please review each lateral location in relation to other wyes or manholes. The following requirements must be met: 1) the distance to the wye must be a minimum of 4.0 feet, as measured from the outside of the manhole, and the beginning of the wye (i.e., not the centerline of the wye), 2) the distance between subsequent wyes on a line must be a minimum of 4.0 feet as measured from the centerline of the wye, to the centerline of the wye. Ensure that both of these requirements are met. If discrepancies are found in the field, the contractor shall be required to adjust and/or replace to these standards.
Corrective Action Required
08/21/2020

It appears the sanitary sewer will be less than 1000 feet in length. As such, no MDNR construction permit shall be required.
Hearings
Title Location Date Time
Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home