Planning Application Status

PL2017104




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2017104
Summit Village 1st Plat Street & Storm, Water Line, Sanitary Plan
Engineering Plan Review
Engineering Plan Review
Approved
04/28/2017
UNITY REALTY LLC
Locations
Contacts
PAUL OSBORNE (OLSSON ASSOCIATES), Address:1301 BURLINGTON ST, SUITE 100, Phone:(816) 587-4320  
UNITY REALTY LLC, Address:1901 NW BLUE PKWY, Phone:(816) 251-3593  
Reviews
Review Type Outcome Est. Completion Date Completed
Traffic Review No Comments 07/19/2017 07/17/2017
Michael Park
Engineering Review No Comments 07/19/2017 07/17/2017
Sue Pyles, P.E.
Traffic Review Corrections 06/23/2017 06/27/2017
Michael Park
Corrective Action Required
06/27/2017

The proposed 4" white line along Blue Pkwy shall be high build paint according to City specifications, not thermoplastic.
Corrective Action Required
06/27/2017

The 4" white line along Blue Pkwy should be dimensioned on the plans.
Corrective Action Required
06/27/2017

Include a plan note for pavement marking removal that requires removal procedures that do not scar the pavement.
Engineering Review Corrections 06/23/2017 06/23/2017
Sue Pyles, P.E.
Corrective Action Required
06/23/2017

Sheet C409: Note 6 refers to the detail sheet for ADA ramp details. Please include the sheet number for the details in the note, as well.
Corrective Action Required
06/23/2017

Sheet C409:Revise the intersection details to provide all information required by the Design & Construction Manual Section 5304.8 and Table LS-5.
Corrective Action Required
06/23/2017

Sheet C410: Include the water and storm crossings near Sta. 15+00 in the Profile view to match the Plan view.
Corrective Action Required
06/23/2017

Sheets C418 & C419: Revise the standard details to be project specific.
Corrective Action Required
06/23/2017

Sheet C602: Include the sanitary crossing near 10+20 in the Profile view to match the Plan view.
Corrective Action Required
06/23/2017

Please review all standard details in the plan set. Many details have been recently updated and are available online.
Corrective Action Required
06/23/2017

Sheet C407: Include beginning and ending stations for the pavement marking on NW Blue Parkway.
Corrective Action Required
06/23/2017

The quantities for Subrade Stabilization items and the Fine Grading item should be greater than the Asphalt quantity. The asphalt does not extend as far left and right of centerline as those items. Check and revise quantities in the Estimate of Quantities table on sheet C402 and on the Engineer's Estimate of Probable Construction Costs as needed.
Engineering Review Corrections 06/06/2017 06/07/2017
Sue Pyles, P.E.
Corrective Action Required
06/06/2017

Revise all paving related details so the subgrade design meets the Design and Construction Manual Section 5200 requirements.
Corrective Action Required
06/06/2017

Sheet C409: Revise the intersection details showing the ADA-accessible sidewalk ramps to meet the requirements of the Design and construction Manual Section 5304.8 and Table LS-5. Include project specific standard details in the plans.
Corrective Action Required
06/06/2017

SheetC412: Revise structure labels and drainage area information for clarity. Much of the information is very hard to read.
Traffic Review Corrections 06/06/2017 06/05/2017
Michael Park
Corrective Action Required
06/05/2017

Provide pavement marking plans for the southbound left turn lane along Blue Pkwy.
Traffic Review Corrections 05/02/2017 05/02/2017
Michael Park
Corrective Action Required
05/02/2017

Refer to FDP comments pertaining to the roadway.
Engineering Review Corrections 05/02/2017 05/01/2017
Sue Pyles, P.E.
Corrective Action Required
04/28/2017

The water main and sanitary main extensions are short enough to be included in the street & storm plans. Please combine into one set of plans.
Corrective Action Required
04/28/2017

Submit an Engineer’s Estimate of Probable Construction Costs.
Corrective Action Required
04/28/2017

Sanitary Sheet C502: Include an item for Encasement in the “Estimate of Quantitiies” table.
Corrective Action Required
04/28/2017

Sanitary Sheet C504: Revise the Ex MH 1-1 station equation to reference the existing sanitary main in the Profile view.
Corrective Action Required
04/28/2017

Sanitary Sheet C504: Show cardinal directions for the inflow elevations at Ex MH 1-1 in the Profile view.
Corrective Action Required
04/28/2017

Sanitary Sheet C504: The area requiring compacted backfill is shown in with a “See Note” label in the Profile view. There is no note included.
Corrective Action Required
04/28/2017

Sanitary: Add the “Sanitary Pipe Encasement” detail to the plan set.
Corrective Action Required
04/28/2017

Water Sheet C602: Revise the “Summary of Quantities” table to match the information in the plan set.
Corrective Action Required
04/28/2017

Water Sheet C604: Coordinate water main stationing between Plan and Profile views.
Corrective Action Required
04/28/2017

Water Sheet C604: Include the sanitary crossing near Sta 11+10 in the Profile view.
Corrective Action Required
04/28/2017

Water: Include standard details in the plan set.
Hearings

There are no hearings for this planning application.

Documents & Images
Date Uploaded File Type Document Name
05/02/2017 Letter PW-Comment Letter (Engineering Plans)
06/07/2017 Letter PW-Comment Letter (Engineering Plans)
06/27/2017 Letter PW-Comment Letter (Engineering Plans)
07/17/2017 Letter PW-Engineering Approval Letter
10/24/2017 Plans C402 C_GEN01_63182 - GENERAL NOTES
10/24/2017 Plans C403 C_GEN02_63182 - GENERAL LAYOUT
10/24/2017 Plans C404 C_GEO01_63182 - GEOMETRIC PLAN
10/24/2017 Plans C405 C_TYP01_63182 - TYPICAL SECTIONS
10/24/2017 Plans C406 C_GRD01_63182 - GRADING PLAN
10/24/2017 Plans C407 C_RPP01_63182 - ROADWAY PLAN & PROFILE
10/24/2017 Plans C408 C_SPT01_63182 - INTERSECTION DETAILS
10/24/2017 Plans C409 C_SPT02_63182 - INTERSECTION DETAILS
10/24/2017 Plans C410 C_STM01_63182 - STORM SEWER PLAN & PROFILE
10/24/2017 Plans C411 C_STM02_63182 - STORM SEWER PLAN & PROFILE
10/24/2017 Plans C412 C_DRN01_63182 - DRAINAGE PLAN
10/24/2017 Plans C413 C_TAB01_63182 - DRAINAGE TABLES
10/24/2017 Plans C414 C_DTL01_63182 - STORM SEWER DETAILS
10/24/2017 Plans C415 C_DTL01_63182 - STORM SEWER DETAILS 2
10/24/2017 Plans C416 C_DTL01_63182 - SIGN DETAILS
10/24/2017 Plans C417 C_DTL01_63182 - SIGN AND TTC
10/24/2017 Plans C418 C_DTL01_63182 - PVMT MARKING
10/24/2017 Plans C419 C_DTL01_63182 - ADA DETAILS
10/24/2017 Plans C420 C_DTL01_63182 - ADA DETAILS 2
10/24/2017 Plans C501 C_GEN02_63182 - SANITARY SEWER GENERAL LAYOUT
10/24/2017 Plans C502 C_SAN01_63182 - SANITARY SEWER PLAN & PROFILE
10/24/2017 Plans C503 C_DTL01_63182 - SANITARY SEWER DETAIL SHEET
10/24/2017 Plans C504 C_DTL02_63182 - SANITARY SEWER DETAIL SHEET
10/24/2017 Plans C601 C_GEN02_63182 - WATER MAIN GENERAL LAYOUT
10/24/2017 Plans C602 C_WAT01_63182 - WATER MAIN PLAN & PROFILE
10/24/2017 Plans C603 C_DTL01_63182 - WATER MAIN DETAIL SHEET
10/24/2017 Plans C401 C_TTL01_63182 - COVER SHEET
01/19/2018 Activity Document Fees PL2017104 Summit Village 1st Plat Street & Storm, Water Line, Sanitary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents