PL2015038
VERIZON CO LOCATE
Commercial Final Development Plan
Commercial Final Development Plan
Approved
03/27/2015
TELECOM TOWERS LLC
TELECOM CO LOCATE ON EXISTING TOWER.
Locations
Contacts
SELECTIVE SITE CONSULTANTS, INC, Address:9900 WEST 109TH STREET SUITE 300, Phone:(913) 438-7700  
TELECOM TOWERS LLC, Address:PO BOX 723597  
Reviews
Review Type Outcome Est. Completion Date Completed
Planning Review No Comments 04/10/2015 06/10/2015
Hector Soto Jr.
Fire Review Approved with Conditions 05/26/2015 05/26/2015
Jim Eden
Code Statement
Corrective Action Required
05/18/2015

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2012 International Fire Code.
Knox Locks
Corrective Action Required
05/18/2015

IFC 506.1 -Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official.506.1.1 Locks.An approved lock shall be installed on gates or similar barriers when required by the fire code official. Gates shall be provided with Knox padlocks.
Hazmat
Corrective Action Required
05/18/2015

The structure shall have appropriate NFPA 704 placard and labeling for the diesel fuel stored in the generator.
Engineering Review No Comments 05/26/2015 05/26/2015
Gene Williams, P.E.
Planning Review Corrections 05/26/2015 05/19/2015
Hector Soto Jr.
Corrective Action Required
05/19/2015

INSPECTION REPORT. A copy of an inspection report current within the last 3 years is required to be provided. The inspection report provided with the resubmittal is 5 years old, and so does not satisfy the requirement for approval.
Traffic Review No Comments 05/26/2015 05/19/2015
Michael Park
Fire Review Approved with Conditions 04/13/2015 04/15/2015
Jim Eden
Code Statement
Corrective Action Required
04/13/2015

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2012 International Fire Code.
Knox Locks
Corrective Action Required
04/13/2015

IFC 506.1 -Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official.506.1.1 Locks.An approved lock shall be installed on gates or similar barriers when required by the fire code official. Gates shall be provided with Knox padlocks.
Hazmat
Corrective Action Required
04/15/2015

The structure shall have appropriate NFPA 704 placard and labeling for the diesel fuel stored in the generator.
Traffic Review No Comments 04/13/2015 04/14/2015
Michael Park
Engineering Review No Comments 04/13/2015 04/14/2015
Gene Williams, P.E.
Planning Review Corrections 04/13/2015 04/13/2015
Hector Soto Jr.
Corrective Action Required
04/13/2015

FCC REGISTRATION. Tower owners shall provide documentation (i.e., a copy of the FCC Antenna Structure Registration and any other relevant documents) indicating that each telecommunications tower is in compliance with all federal requirements. A statement declaring that the existing tower is still in compliance and will remain so after any proposed alterations or additions shall be submitted when the structure is altered or antenna(s) added.
Corrective Action Required
04/13/2015

INSPECTION REPORT. A copy of an inspection report current within the last 3 years.
Corrective Action Required
04/13/2015

INSURANCE. Proof of general liability insurance for claims from injury or death and property damage in an amount approved by the City, but not less than $2,000,000.00 per occurrence for personal injury and $2,000,000.00 per occurrence for property damage with the City listed as an additional insured.
Corrective Action Required
04/13/2015

LANDSCAPING. The new equipment shelter shall be screened from view along I-470 using evergreen trees at least 8' in height at the time of planting. Provide a landscape plan to illustrate how the screening requirement will be met. The plan shall identify the number, species and height of the proposed evergreen trees.
Fire Review Approved with Conditions 04/10/2015 03/31/2015
Jim Eden
Code Statement
Corrective Action Required
03/31/2015

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2012 International Fire Code. Provide detailed plans for Building Permit review for the enclosure, generator, fuel storage, and fire suppression system. Approval of the FDP is conditioned on approval of the enclosure and interior systems.
Knox Locks
Corrective Action Required
03/31/2015

IFC 506.1 -Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official.506.1.1 Locks.An approved lock shall be installed on gates or similar barriers when required by the fire code official. Gates shall be provided with Knox padlocks.
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $600.00 $600.00 Paid 03/27/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
03/27/2015 Receipt Receipt for transaction: 2015-000477
03/30/2015 Letter Routing Sheet - FDP
04/14/2015 Letter Applicant Letter - FDP (DFDP)
05/18/2015 Letter Resubmittal Routing Sheet - FDP
06/10/2015 Letter Applicant Letter - FDP (DFDP)
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home