Planning Application Status

PL2011160




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2011160
MAZUMA CREDIT UNION PARKING LOT IMPROVEMENTS
Commercial Final Development Plan
Commercial Final Development Plan
Approved
12/06/2011
DACUR INVESTMENT COMPANY INC
Locations
Contacts
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
Reviews
Review Type Outcome Est. Completion Date Completed
Planning Review No Comments 03/08/2012 03/09/2012
Hector Soto Jr.
Engineering Review No Comments 03/08/2012 03/08/2012
Gene Williams, P.E.
Fire Review Complete 03/08/2012 03/05/2012
Jim Eden
Code Statement
Corrective Action Required
03/05/2012

Fire Department-All building and life safety issues shall comply with the 2006 International Fire Code and local amendments as adopted by the City of Lee’s Summit.
Traffic Review No Comments 03/01/2012 03/02/2012
Michael Park
Planning Review No Comments 01/25/2012 02/01/2012
Hector Soto Jr.
Engineering Review Corrections 01/25/2012 01/26/2012
Gene Williams, P.E.
Corrective Action Required
01/25/2012

It is unclear why the plan shows the sidewalk to be placed directly on top of an existing water main. Is it possible to move the sidewalk closer to the property line in accordance with the City policy to located sidewalks within a foot of the property line? If this is done, the sidewalk will no longer be directly on top of a water main.
Corrective Action Required
01/25/2012

The plan shows a curb at the intersection of the sidewalk crossing. It is assumed this curb is 6 inches in height. How will the sidewalk be constructed to meet ADA requirements concerning maximum slope of 8.33%, a level (i.e., less than 2%) landing, etc.? These details need to be shown on the plan.
Corrective Action Required
01/26/2012

Floodplain note needs to be changed to read "...0.2% annual chance flood" rather than 0.02% annual chance flood.
Corrective Action Required
01/26/2012

The silt fence details do not meet current standards. The APWA changed the requirements, and the City adopted these new reqauirements 2 years ago which no longer allow for trenched-in silt fence. In other words, silt fence must be installed using a dedicated silt fence machine.
Traffic Review No Comments 01/18/2012 01/23/2012
Michael Park
Fire Review Complete 01/25/2012 01/20/2012
Jim Eden
Traffic Review No Comments 12/20/2011 12/22/2011
Michael Park
Engineering Review Corrections 12/20/2011 12/20/2011
Gene Williams, P.E.
Corrective Action Required
12/20/2011

All utilities must be shown on the plan, including sanitary sewer, water, and storm sewer.
Corrective Action Required
12/20/2011

The sidewalk must be 5 feet in width with appropriate transitions to match the existing 4 foot sidewalk sections.
Corrective Action Required
12/20/2011

It is unclear how the new sidewalk on the northeast portion of the project will be connected with the hatched area (presumably a pedestrian crossing area). Will there be an ADA-accessible ramp constructed at this location? If so, what are the key elevations (as shown on the APWA standard drawings)?
Corrective Action Required
12/20/2011

Since these are new improvements within the right of way, the existing sidewalk shown on the northeast portion of the project will be required to meet the new standards for ADA accessibility.
Corrective Action Required
12/20/2011

A copy of the MoDOT permit will be required prior to approval.
Corrective Action Required
12/20/2011

What is the drainage plan for the green space between the property line and the right of way? It appears there may be a problem with the new sidewalk creating an obstruction.
Corrective Action Required
12/20/2011

A note must be added to the plan stating that all construction shall follow the City of Lee's Summit Design and Construction Manual as adopted by Ordinance 5813.
Corrective Action Required
12/20/2011

A note must be added to the plan stating that a minimum of 48 hours notice be given to Public Works Inspections prior to commencement of work.
Corrective Action Required
12/20/2011

An erosion and sediment control plan must be submitted. It is acceptable to overlay this plan over the existing plan provided that all information is clearly presented.
Fire Review Complete 12/20/2011 12/20/2011
Hector Soto Jr.
Planning Review Corrections 12/20/2011 12/19/2011
Hector Soto Jr.
Planning Correction
Corrective Action Required
12/19/2011

MoDOT PERMIT. - Provide a copy of the MoDOT permit referenced in the plans. - Does the permit issued by MoDOT indicate or include approval for the permanent encroachment of the drive lane widening into the right-of-way? If not, provide some type of documentation indicating approval for this encroachment.
Planning Correction
Corrective Action Required
12/19/2011

SIDEWALK. The relocated sidewalk shall be a minimum 5' in width in order to comply with current UDO standards.
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $600.00 $600.00 Paid 12/06/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
12/06/2011 Letter Admin Route Sheet FDP
12/20/2011 Letter Applicant Letter (FDP)
01/18/2012 Letter Admin Re-Route FDP
02/01/2012 Letter Applicant Letter (FDP)
03/01/2012 Letter Admin Re-Route FDP
03/08/2012 Letter Approval Letter (Administrative)
03/08/2012 Engineers Estimate Mar 2012.pdf
03/09/2012 Letter Applicant Letter (FDP)
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.