Permit Application Status

PRRES20252473


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20252473
Building Permit - Residential
Final Completion
MEDLIN JOE & LAUREN
ALTERATION SINGLE FAMILY
ROOF MOUNTED SOLAR - 11.60 KW
06/13/2025
07/02/2025
12/21/2025
10/07/2025
Locations
Contacts
Natural Energy Solutions LLC, Address:PO Box 11124  
RHAYES@USNATURALENERGY.COM  
MEDLIN JOE & LAUREN, Address:634 NE ST ANDREWS CRT  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Department Solar Review Approved 08/14/2025 08/19/2025
Jim Eden
Residential Plan Review Approved 06/26/2025 06/24/2025
Andrea Sessler
Residential Plan Review Rejected 06/18/2025 06/18/2025
Andrea Sessler
Fire Department Solar Review Approved 06/18/2025 06/18/2025
Jim Eden
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Add/Alter Single Family $212.80 $212.80 Paid 07/02/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Failed 9/16/2025 9/16/2025 09/16/2025
Misc
Corrective Action Required
09/16/2025
See final inspection report
Final Inspection - Residential Failed 9/16/2025 9/16/2025 09/16/2025
Misc
Corrective Action Required
09/16/2025
-Provide #4 cu ungrounded conductors per plan -Bond metal raceway -Enclose PV #4 grounding electrode conductor inside raceway -Ground PV meter to rod -Provide permanent AC rating label that can withstand weather, no handwriting -Install plaque per 705
Electrical Service Inspection Passed 10/7/2025 10/7/2025 10/07/2025
Misc
Resolved
10/07/2025
See final inspection report
Final Inspection - Residential Passed 10/7/2025 10/7/2025 10/07/2025
Misc
Resolved
10/07/2025
-Provide #4 cu ungrounded conductors per plan -Bond metal raceway -Enclose PV #4 grounding electrode conductor inside raceway -Ground PV meter to rod -Provide permanent AC rating label that can withstand weather, no handwriting -Install plaque per 705
Documents & Images
Date Uploaded File Type Document Name
06/13/2025 Application Form APPLICATION
06/16/2025 Lauren Medlin-PLAN (3)
06/18/2025 Permit Codes Residential Plan Review
06/24/2025 Plans Lauren_Medlin-PLAN_Sealed
06/24/2025 Approved Plans APPROVED PLANS
07/02/2025 Permit DS Building Permit
07/02/2025 Receipt Receipt for transaction:2025-005203
08/11/2025 Lauren Medlin-PLAN_Rev01 (1)
08/11/2025 Response Letter_docx (5)
08/19/2025 Approved Plans 8-19-25 APPROVED PLANS
09/16/2025 Letter INSPECTION SUMMARY
09/16/2025 Letter INSPECTION SUMMARY
10/07/2025 Letter INSPECTION SUMMARY
10/07/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home