PRRES20251619
Building Permit - Residential
Final Completion
AVITAL HOMES LLC
ALTERATION SINGLE FAMILY
762 Square Feet basement finish
04/21/2025
04/29/2025
06/09/2025
Locations
Contacts
Avital Homes, LLC, Address:7500 W 151st Street, #23100, Phone:(816) 914-7128  
DOUG@APGKC.COM  
AVITAL HOMES LLC, Address:15729 BALLENTINE ST  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 04/28/2025 04/28/2025
Andrea Sessler
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Add/Alter Single Family $151.49 $151.49 Paid 04/29/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Residential Failed 5/2/2025 5/2/2025 05/02/2025
Misc
Corrective Action Required
05/02/2025
Ensure city stamped plans on site for reinspect -light switch at basement stairs to comply with R303.7 of the 2018 IRC -fire block in basement bedroom closet needed wall space to ceiling space -basement smoke CO cannot be with in 3’ of bathroom -add supports at fur down ceiling joist to floor joist above where heather than 4’ span
All Rough Inspection - Residential Passed 5/6/2025 5/6/2025 05/06/2025
Misc
Resolved
05/06/2025
Ensure city stamped plans on site for reinspect -light switch at basement stairs to comply with R303.7 of the 2018 IRC -fire block in basement bedroom closet needed wall space to ceiling space -basement smoke CO cannot be with in 3’ of bathroom -add supports at fur down ceiling joist to floor joist above where heather than 4’ span
Final Inspection - Residential Passed 6/9/2025 (7:00AM to 4:00PM) 6/9/2025 06/09/2025
Documents & Images
Date Uploaded File Type Document Name
04/21/2025 Scope of Work SCOPE OF WORK
04/28/2025 Approved Plans APPROVED BASEMENT DRAWING
04/29/2025 Permit DS Building Permit
04/29/2025 Receipt Receipt for transaction:2025-002657
05/02/2025 Letter INSPECTION SUMMARY
05/06/2025 Letter INSPECTION SUMMARY
06/09/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home