Permit Application Status

PRRES20242857


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20242857
Building Permit - Residential
Issued
NEW DUPLEX
NEW DUPLEX - FINISHED AND UNFINISHED BASEMENT - COVERED PORCH - SUSPENDED SLAB
06/04/2024
07/11/2024
12/03/2024
Locations
Contacts
ROCK CREEK HOMES, Address:6126 METCALF LANE, Phone:(913) 522-1945  
Kevin Guinan, Address:6126 Metcalf Lane  
KEVIN@ROCKCREEKHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
PRIDE SERVICES INC, Address:3842 GEORGIA TERR, Phone:(785) 242-9700  
BILL'S PLUMBING SERVICE LLC, Address:308 E PARK STREET, Phone:(913) 829-8213  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Duplex $2,603.66 $2,603.66 Paid 07/11/2024
8350015-Water Meter Fee $1,496.06 $1,496.06 Paid 07/11/2024
8331507-Sanitary Sewer Development Fee $4,570.00 $4,570.00 Paid 07/11/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 07/11/2024
7232302-Residential License Tax Fee $1,240.32 $1,240.32 Paid 07/11/2024
8331401-Water Tap Fee $7,946.00 $7,946.00 Paid 07/11/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Occupancy Inspection - Codes Residential Pending
Erosion Control Inspection Residential Pending
Misc
Corrective Action Required
11/07/2024
REMOVE GRAVEL FROM STREET AT MULTIPLE ADDRESSES
Driveway Inspection Pending
Misc
Informational
03/03/2025
3-3-25 BR Driveway is formed with aggregate is place and compacted ready for concrete.
Footing Inspection - Residential Passed 8/8/2024 08/08/2024
Underslab Electrical Inspection - Residential Passed 8/26/2024 08/26/2024
Misc
Informational
08/26/2024
Both 1418 & 1420 approved
Erosion Control Inspection Residential Partial 10/8/2024 10/8/2024 08/28/2024
Misc
Informational
08/28/2024
In compliance at time of inspection
Misc
Resolved
08/28/2024
Sewer Service Inspection - R Passed 8/28/2024 08/28/2024
Erosion Control Inspection Residential Failed 8/29/2024 08/29/2024
Misc
Resolved
08/29/2024
In compliance at time of inspection
Miscellaneous Correction
Corrective Action Required
08/29/2024
Silt fence at the front of the property is damaged and will no longer serve its intended purpose. Repair or replace silt fence Full erosion control measures must be maintained until CofO
Water Service Inspection - R Passed 8/29/2024 08/29/2024
Underslab Plumbing Inspection - Residential Passed 9/3/2024 9/3/2024 09/03/2024
Misc
Informational
09/03/2024
1418 and 1420
Suspended Slab Inspection Passed 9/26/2024 09/26/2024
Misc
Informational
09/26/2024
- INSPECTION PERFORED BY APEX ENGINEERS
Rated Assembly Inspection Failed 9/30/2024 9/30/2024 09/30/2024
Miscellaneous Correction
Corrective Action Required
09/30/2024
Both sides - Spots in the field are missing fasteners and fasteners are not installed on the edges along the rafters
Rated Assembly Inspection Failed 10/2/2024 10/2/2024 10/02/2024
Miscellaneous Correction
Corrective Action Required
09/30/2024
Both sides - Spots in the field are missing fasteners and fasteners are not installed on the edges along the rafters- -- Screws are not set against the sheetrock. Fully seat all screws to sheetrock to secure sheetrock against studs. Reschedule when complete. This can be inspected during the all-rough.
Erosion Control Inspection Residential Failed 10/2/2024 10/02/2024
Miscellaneous Correction
Corrective Action Required
08/29/2024
Silt fence at the front of the property is damaged and will no longer serve its intended purpose. Repair or replace silt fence
Misc
Corrective Action Required
10/02/2024
install erosion control- contain all trash and debris.
Rated Assembly Inspection Failed 10/4/2024 10/4/2024 10/04/2024
Miscellaneous Correction
Corrective Action Required
10/02/2024
Both sides -- Screws are not set against the sheetrock. Fully seat all screws to sheetrock to secure sheetrock against studs. Reschedule when complete. This can be inspected during the all-rough.
Erosion Control Inspection Residential Partial 10/8/2024 10/08/2024
Miscellaneous Correction
Resolved
10/08/2024
Silt fence at the front of the property is damaged and will no longer serve its intended purpose. Repair or replace silt fence
Misc
Resolved
10/08/2024
install erosion control- contain all trash and debris.
Miscellaneous Correction
Informational
10/08/2024
Full erosion control measures are in place and must be properly maintained until CofO
Rated Assembly Inspection Failed 10/10/2024 10/10/2024 10/10/2024
Miscellaneous Correction
Resolved
10/10/2024
Both sides -- Screws are not set against the sheetrock. Fully seat all screws to sheetrock to secure sheetrock against studs. Reschedule when complete. This can be inspected during the all-rough.
Miscellaneous Correction
Corrective Action Required
10/10/2024
Fully seat sheet rock screws up against the rafter at demising wall on both sides
Rated Assembly Inspection Partial 10/17/2024 10/17/2024 10/17/2024
Miscellaneous Correction
Resolved
10/17/2024
Fully seat sheet rock screws up against the rafter at demising wall on both sides
Misc
Corrective Action Required
10/17/2024
ATTIC SPACE AND RIM BOARD PARTIAL 1418 Fire caulk front corner mechanical room Fire caulk top of bedroom demise wall 1420 Seal gaps at roof deck
Gas Service Inspection - Residential Passed 11/7/2024 11/07/2024
Misc
Informational
11/07/2024
For both 1418 and 1420
Electrical Service Inspection Passed 11/7/2024 11/7/2024 11/07/2024
Misc
Informational
11/07/2024
both 1418 and 1420
Rated Assembly Inspection Partial 11/7/2024 11/7/2024 11/07/2024
Misc
Resolved
11/07/2024
Misc
Corrective Action Required
11/07/2024
ATTIC SPACE AND RIM BOARDSCREW PATTERN BOTH SIDES APPROVED ONLY ( ready for tape )
All Rough Inspection - Residential Failed 11/7/2024 11/7/2024 11/07/2024
Misc
Corrective Action Required
11/07/2024
1418 - Nail off studs at exterior corners of bedroom 2 - Strap top plate, top plate not tied together at entry to garage return wall - 1420 - anchor bolt at garage portal frame to be in middle third of sill plate - Strap top plate, top plate not tied together at entry to garage return wall - Nail triple studs pack together at refrigerator under double LVL
Erosion Control Inspection Residential Failed 11/7/2024 11/07/2024
Miscellaneous Correction
Resolved
11/07/2024
Full erosion control measures are in place and must be properly maintained until CofO
Misc
Corrective Action Required
11/07/2024
REMOVE GRAVEL FROM STREET AT MULTIPLE ADDRESSES
All Rough Inspection - Residential Passed 11/12/2024 11/12/2024 11/12/2024
Misc
Resolved
11/12/2024
1418 - Nail off studs at exterior corners of bedroom 2 - Strap top plate, top plate not tied together at entry to garage return wall - 1420 - anchor bolt at garage portal frame to be in middle third of sill plate - Strap top plate, top plate not tied together at entry to garage return wall - Nail triple studs pack together at refrigerator under double LVL
Rated Assembly Inspection Failed 12/3/2024 12/3/2024 12/03/2024
Misc
Corrective Action Required
11/07/2024
ATTIC SPACE AND RIM BOARDSCREW PATTERN BOTH SIDES APPROVED ONLY ( ready for tape )
Miscellaneous Correction
Corrective Action Required
12/03/2024
1420 - some areas in the shower appear to have fastners spaced more than 8 inches apart - both sides of the bathroom vanity sheet rock walls need to be fastened to backing at the outside edges - bedroom angle wall from the ceiling to the outside wall needs fastners along the edge 8 inches on center 1418 - both the bathroom vanity and shower areas need the outside Sheetrock edges secured to backing every 8 inches on center - bedroom angle wall from the ceiling to the outside wall needs fasteners along the edge 8 inches on center
Rated Assembly Inspection Failed 12/5/2024 12/5/2024 12/05/2024
Misc
Corrective Action Required
12/03/2024
ATTIC SPACE AND RIM BOARDSCREW PATTERN BOTH SIDES APPROVED ONLY ( ready for tape )
Miscellaneous Correction
Resolved
12/05/2024
1420 - some areas in the shower appear to have fastners spaced more than 8 inches apart - both sides of the bathroom vanity sheet rock walls need to be fastened to backing at the outside edges - bedroom angle wall from the ceiling to the outside wall needs fastners along the edge 8 inches on center 1418 - both the bathroom vanity and shower areas need the outside Sheetrock edges secured to backing every 8 inches on center - bedroom angle wall from the ceiling to the outside wall needs fasteners along the edge 8 inches on center
Miscellaneous Correction
Corrective Action Required
12/05/2024
1418 - The shower area needs the outside Sheetrock edges secured to backing every 8 inches on center 1420 passed rated assembly inspection
Rated Assembly Inspection Passed 12/6/2024 12/6/2024 12/06/2024
Misc
Resolved
12/06/2024
ATTIC SPACE AND RIM BOARDSCREW PATTERN BOTH SIDES APPROVED ONLY ( ready for tape )
Miscellaneous Correction
Informational
12/06/2024
1418, 1420 passed rated assembly inspection
Driveway Inspection Passed 3/11/2025 3/11/2025 03/11/2025
Misc
Informational
03/03/2025
3-3-25 BR Driveway is formed with aggregate is place and compacted ready for concrete. 3-11-25 BR Driveway is constructed to LS specifications.
Sidewalk Inspection Partial 4/29/2025 4/29/2025 04/29/2025
Misc
Informational
04/29/2025
4/29/25 RH. Sidewalk is formed up and approved to pour, contractor was told to replace straw waddles and clean up street.
Sidewalk Inspection Passed 5/6/2025 5/6/2025 05/06/2025
Misc
Informational
04/29/2025
4/29/25 RH. Sidewalk is formed up and approved to pour, contractor was told to replace straw waddles and clean up street. 5-6-25 RH. Sidewalk passed inspection.
Documents & Images
Date Uploaded File Type Document Name
06/04/2024 Application - Lot 49
06/04/2024 Tax Form - Lot 49
06/06/2024 Permit Codes Residential Plan Review
06/06/2024 Approved Plans APPROVED PLANS
06/24/2024 Plot Plan APPROVED PLOT PLAN
06/24/2024 Permit Codes Residential Plan Review
07/11/2024 Permit DS Building Permit
07/11/2024 Receipt Receipt for transaction: 2024-005739
08/08/2024 Letter INSPECTION SUMMARY
08/26/2024 Letter INSPECTION SUMMARY
08/28/2024 Letter INSPECTION SUMMARY
08/28/2024 Letter INSPECTION SUMMARY
08/29/2024 Letter INSPECTION SUMMARY
08/29/2024 Letter INSPECTION SUMMARY
09/03/2024 Letter INSPECTION SUMMARY
09/26/2024 2024_09_10_1418-20 SW Winthrop Terrace_Gslab_Report_Sealed
09/26/2024 Approved Plans APPROVED PLANS
09/26/2024 Letter INSPECTION SUMMARY
09/30/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/04/2024 Letter INSPECTION SUMMARY
10/08/2024 Letter INSPECTION SUMMARY
10/10/2024 Letter INSPECTION SUMMARY
10/17/2024 Letter INSPECTION SUMMARY
11/07/2024 Letter INSPECTION SUMMARY
11/07/2024 Letter INSPECTION SUMMARY
11/07/2024 Letter INSPECTION SUMMARY
11/07/2024 Letter INSPECTION SUMMARY
11/07/2024 Letter INSPECTION SUMMARY
11/07/2024 Letter INSPECTION SUMMARY
11/12/2024 Letter INSPECTION SUMMARY
12/03/2024 Letter INSPECTION SUMMARY
12/05/2024 Letter INSPECTION SUMMARY
12/06/2024 Letter INSPECTION SUMMARY
03/03/2025 Letter INSPECTION SUMMARY
03/11/2025 Letter INSPECTION SUMMARY
03/11/2025 Letter INSPECTION SUMMARY
04/29/2025 Letter INSPECTION SUMMARY
05/06/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home