Permit Application Status

PRRES20220708


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20220708
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE- UNFINSIHED BASEMENT - COVERED DECK
02/25/2022
04/18/2022
08/28/2022
03/09/2024
Locations
Contacts
IQ CONSTRUCTION, Address:P O BOX 6423, Phone:(816) 582-8100  
Jennifer Pestka, Address:p o box 6423  
JENNIFER@IQHOMEBUILDERS.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
SAFEHOUSE ELECTRIC COMPANY, Address:P O BOX 1833, Phone:(816) 935-8113  
GARRISON PLUMBING, Address:15430 S MAHAFFIE ST STE 102, Phone:(913) 768-1311  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $570.00 $570.00 Paid 04/18/2022
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 04/18/2022
7232302-Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 04/18/2022
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 04/18/2022
8350015-Water Meter Fee $479.24 $479.24 Paid 04/18/2022
9110078-Valuation Fee New Single Family $1,374.39 $1,374.39 Paid 04/18/2022
$0.00 $0.00 $0.00 N/A
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Failed 4/18/2022 04/18/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
04/18/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Footing Inspection - Residential Failed 4/18/2022 (11:00) 4/18/2022 04/18/2022
Misc
Corrective Action Required
04/18/2022
inspection denied erosion control not in compliance Mitchell Schwarz 04/18/2022 11:19 AM
Erosion Control Inspection Residential Passed 4/19/2022 04/19/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
04/19/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Footing Inspection - Residential Failed 4/19/2022 04/19/2022
Misc
Resolved
04/19/2022
inspection denied erosion control not in compliance Mitchell Schwarz 04/18/2022 11:19 AM
Misc
Corrective Action Required
04/19/2022
-Address Rear of home frost footing water in footing and clean out, all of frost footing must maintain 36” depth -address most south column pad not to plans
Footing Inspection - Residential Passed 4/19/2022 04/19/2022
Misc
Resolved
04/19/2022
-Address Rear of home frost footing water in footing and clean out, all of frost footing must maintain 36” depth -address most south column pad not to plans
Underslab Plumbing Inspection - Residential Passed 5/16/2022 5/16/2022 05/16/2022
Piers/Caissons Inspection - Residential Passed 7/14/2022 (10:15) 7/14/2022 07/14/2022
Sewer Service Inspection - R Passed 8/18/2022 08/18/2022
Water Service Inspection - R Passed 8/19/2022 8/19/2022 08/19/2022
Electrical Service Inspection Passed 12/1/2022 12/1/2022 12/01/2022
All Rough Inspection - Residential Failed 12/1/2022 12/1/2022 12/01/2022
Misc
Corrective Action Required
12/01/2022
-uncover covered pfg exter nailing at garage -fire block dwv N garage wall into furr down -nail all intersecting exterior wall corners to code -address holes drilled in joists closer than 2” at garage entry for pex -address over notched double floor joist above great room near windows -address double joists above great room near stairs hole drilled greater than 3” -address holes drilled closer than 2” in floor joist above great room near stairs -plans call for 3 king studs either side of front entry door -fire block W bed 3 wall to ceiling space -missing hangers on joists above 2nd story hallway -fire block SW master shower corner wall to ceiling space -minimum 3 studs at exterior wall corners see basement
Gas Service Inspection - Residential Passed 12/1/2022 12/1/2022 12/01/2022
All Rough Inspection - Residential Failed 12/15/2022 12/15/2022 12/15/2022
Misc
Corrective Action Required
12/01/2022
-address holes drilled in joists closer than 2” at garage entry for pex -address over notched double floor joist above great room near windows -address double joists above great room near stairs hole drilled greater than 3” -address holes drilled closer than 2” in floor joist above great room near stairs Okay to insulate DO NOT COVER ANY ITEMS STILL IN NEED OF INSPECTION
All Rough Inspection - Residential Passed 12/16/2022 12/16/2022 12/16/2022
Misc
Resolved
12/16/2022
-address holes drilled in joists closer than 2” at garage entry for pex -address over notched double floor joist above great room near windows -address double joists above great room near stairs hole drilled greater than 3” -address holes drilled closer than 2” in floor joist above great room near stairs Okay to insulate DO NOT COVER ANY ITEMS STILL IN NEED OF INSPECTION
Driveway Inspection Partial 2/21/2023 2/21/2023 02/21/2023
Misc
Informational
02/21/2023
2-21-23 RH. Forms are up and aggreate is placed and compacted. Approved to pour.
Sidewalk Inspection Failed 2/27/2023 02/27/2023
Misc
Informational
02/27/2023
2-27-23 RH. Subgrade was oversatured and not solid due to the rain overnight. There was visible mud that needed removed. Contractor will clean up and call in tomorrow.
Sidewalk Inspection Partial 3/1/2023 3/1/2023 03/01/2023
Misc
Informational
02/27/2023
2-27-23 RH. Subgrade was oversatured and not solid due to the rain overnight. There was visible mud that needed removed. Contractor will clean up and call in tomorrow. 3-1-23 RH. Sidewalk was formed up and aggreagte is placed and compacted. Cross slope currenly passes. Approved to pour.
Driveway Inspection Passed 3/7/2023 3/7/2023 03/07/2023
Misc
Informational
02/21/2023
2-21-23 RH. Forms are up and aggreate is placed and compacted. Approved to pour. 3-7-23 RH. Driveway meets LS and ADA specification.
Sidewalk Inspection Passed 3/7/2023 03/07/2023
Misc
Informational
03/01/2023
2-27-23 RH. Subgrade was oversatured and not solid due to the rain overnight. There was visible mud that needed removed. Contractor will clean up and call in tomorrow. 3-1-23 RH. Sidewalk was formed up and aggreagte is placed and compacted. Cross slope currenly passes. Approved to pour. 3-7-23 RH. Sidewalk meets LS and ADA specification.
Plot Plan Inspection Passed 3/13/2024 03/13/2024
Occupancy Inspection - Codes Residential Failed 3/13/2024 3/13/2024 03/13/2024
Misc
Corrective Action Required
03/13/2024
-address pending sidewalk inspection -obtain issued lawn irrigation permit -sump pump discharge to extend 36” from foundation -steps at front stoop greater than 3/8 difference in rise. Also top step greater that 7 3/4 rise -address gap in Sheetrock right of garage stairs -handrail required at garage stairs -address guard rail at rear deck on north and south side. Secure to rest lateral force -15 amp breaker labeled “range 110” needs afci protection -
Sidewalk Inspection Failed 3/20/2024 03/20/2024
Misc
Corrective Action Required
03/20/2024
3-20-24 Dustin A, Concrete debris needs to be removed from ADA ramp
Sidewalk Inspection Passed 03/28/2024
Misc
Corrective Action Required
03/20/2024
3-20-24 Dustin A, Concrete debris needs to be removed from ADA ramp 3-28-24 Dustin A, Issue has been resolved. Passed
Occupancy Inspection - Codes Residential Full C of O 3/29/2024 3/29/2024 03/29/2024
Misc
Resolved
03/29/2024
-address pending sidewalk inspection -obtain issued lawn irrigation permit -sump pump discharge to extend 36” from foundation -steps at front stoop greater than 3/8 difference in rise. Also top step greater that 7 3/4 rise -address gap in Sheetrock right of garage stairs -handrail required at garage stairs -address guard rail at rear deck on north and south side. Secure to rest lateral force -15 amp breaker labeled “range 110” needs afci protection -
Documents & Images
Date Uploaded File Type Document Name
02/25/2022 3204 SW Saddlebred Terrace - Permit and Tax Application
03/01/2022 Approved Plans APPROVED PLANS
03/01/2022 Permit Codes Residential Plan Review
03/02/2022 Plot Plan APPROVED PLOT PLAN
03/02/2022 Permit Codes Residential Plan Review
04/18/2022 Permit DS Building Permit
04/18/2022 Receipt Receipt for transaction:2022-002141
04/18/2022 Letter INSPECTION SUMMARY
04/19/2022 Letter INSPECTION SUMMARY
04/19/2022 Letter INSPECTION SUMMARY
04/19/2022 Letter INSPECTION SUMMARY
04/19/2022 Letter INSPECTION SUMMARY
05/16/2022 Letter INSPECTION SUMMARY
07/14/2022 Letter INSPECTION SUMMARY
08/18/2022 Letter INSPECTION SUMMARY
08/19/2022 Letter INSPECTION SUMMARY
12/01/2022 Letter INSPECTION SUMMARY
12/01/2022 Letter INSPECTION SUMMARY
12/01/2022 Letter INSPECTION SUMMARY
12/15/2022 Letter INSPECTION SUMMARY
12/15/2022 SVF120 Spec - Inspection Letter (12-9-22)
02/21/2023 Letter INSPECTION SUMMARY
02/27/2023 Letter INSPECTION SUMMARY
03/01/2023 Letter INSPECTION SUMMARY
03/07/2023 Letter INSPECTION SUMMARY
03/07/2023 Letter INSPECTION SUMMARY
07/25/2023 Letter INSPECTION SUMMARY
07/25/2023 Letter Codes 140 Day Letter
07/25/2023 Letter Codes 140 Day Letter
03/04/2024 Letter Codes 140 Day Letter
03/04/2024 Letter Codes 180 Day Letter
03/12/2024 Letter EXTENSION REQUEST FORM
03/13/2024 Letter INSPECTION SUMMARY
03/13/2024 Letter INSPECTION SUMMARY
03/20/2024 Letter INSPECTION SUMMARY
03/20/2024 Letter INSPECTION SUMMARY
03/28/2024 Letter INSPECTION SUMMARY
03/29/2024 Letter Field Certificate of Occupancy
03/29/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home