Permit Application Status

PRRES20214881


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20214881
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW HOUSE. COVERED DECK. ROOF TRUSSES.
09/20/2021
10/26/2021
03/20/2022
10/13/2022
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
CMH PARKS INC, Address:5000 CLAYTON RD  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
AJ@SUMMITHOMESKC.COM  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $360.00 $360.00 Paid 10/26/2021
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 10/26/2021
8350015-Water Meter Fee $479.24 $479.24 Paid 10/26/2021
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 10/26/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 10/26/2021
9110078-Valuation Fee New Single Family $1,031.38 $1,031.38 Paid 10/26/2021
8331504-EFHB Middle Big Creek, Full $401.76 $401.76 Paid 10/26/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 11/29/2021 11/29/2021 11/29/2021
Misc
Informational
11/29/2021
APPROVED PER BRADLEY HUXOL 11/17/21
Underslab Plumbing Inspection - Residential Passed 12/14/2021 12/14/2021 12/14/2021
Sewer Service Inspection - R Passed 1/7/2022 (11:15) 1/7/2022 01/07/2022
Water Service Inspection - R Passed 1/11/2022 (10:30) 1/11/2022 01/11/2022
Electrical Service Inspection Passed 5/25/2022 5/26/2022 05/26/2022
Gas Service Inspection - Residential Failed 5/25/2022 5/26/2022 05/26/2022
Misc
Corrective Action Required
05/26/2022
-gas pressure 0 psi, must maintain 10 psi for test -gas line bond required
All Rough Inspection - Residential Failed 5/26/2022 5/26/2022 05/26/2022
Misc
Corrective Action Required
05/26/2022
-maintain erosion control silt fence front of lot -nail stud shoes master bath vanity -ground metal light plates at master vanity, kitchen, front bath -provide bocca protection plate at top plate DWV master shower -fireblock HVAC plate penetration laundry -fireblock at fireplace lid -covered front porch, support ridge at both ends, rafters landing on blocks above top plate -provide (4) 2x4 stud packs at all girder truss bearing ends per plans -fireblock 1st floor tub trap, (foam too large for annular space and has fallen) -address floor joist bored for pex less than 2” from of joist, see SE basement left of service panel -address floor joist bored for gas line less than 2” from end of joist, see west corner basement above sump pump -toenail all floor joists per code -provide joist hanger at joist to dbl rim connection above left side window basement -provide dbl 2x10 joist at N side basement per plans -gas pressure 0 psi, must maintain 10 psi for test -gas line bond required
Erosion Control Inspection Residential Failed 5/26/2022 5/26/2022 05/26/2022
Misc
Corrective Action Required
05/26/2022
-maintain erosion control silt fence front of lot
All Rough Inspection - Residential Failed 6/13/2022 6/13/2022 06/13/2022
Misc
Corrective Action Required
05/26/2022
-nail stud shoes master bath vanity -covered front porch, rafters landing on blocks above top plate -provide (4) 2x4 stud packs at all girder truss bearing ends per plans -toenail all floor joists per code -provide joist hanger at joist to dbl rim connection above left side window basement -provide dbl 2x10 joist at N side basement per plans
Gas Service Inspection - Residential Passed 6/13/2022 6/13/2022 06/13/2022
Misc
Resolved
06/13/2022
All Rough Inspection - Residential Passed 6/23/2022 6/23/2022 06/23/2022
Misc
Resolved
06/23/2022
Erosion Control Inspection Residential Partial 06/23/2022
Misc
Resolved
06/23/2022
-maintain erosion control silt fence front of lot
Driveway Inspection Partial 8/2/2022 08/02/2022
Misc
Informational
08/02/2022
Rock has been installed and compacted. Appears to meet ADA standards.Steve Robbins 08/02/2022 2:11 PM
Sidewalk Inspection Partial 8/2/2022 08/02/2022
Misc
Informational
08/02/2022
Rock has been installed and compacted. Expansion joint material was on-site . The forms appear to be ADA compliant. Steve Robbins 08/02/2022 2:14 PM
Erosion Control Inspection Residential Passed 10/6/2022 10/6/2022 10/06/2022
Occupancy Inspection - Codes Residential Failed 10/6/2022 10/6/2022 10/06/2022
Misc
Corrective Action Required
10/06/2022
-final driveway and sidewalk inspections required, contact development services to schedule -dishwasher outlet requires GFCI protection -basement stairs, handrail height 34”-38” by code, top of handrail over 38” -water pressure regulator required at water line -set electrical ground rod below grade at exterior
Driveway Inspection Passed 10/12/2022 10/12/2022 10/12/2022
Misc
Informational
08/02/2022
Rock has been installed and compacted. Appears to meet ADA standards.Steve Robbins 08/02/2022 2:11 PM 10-12-22 RH. Driveway meets LS and ADA specification.
Sidewalk Inspection Passed 10/12/2022 10/12/2022 10/12/2022
Misc
Informational
08/02/2022
Rock has been installed and compacted. Expansion joint material was on-site . The forms appear to be ADA compliant. Steve Robbins 08/02/2022 2:14 PM 10-12-22 RH. Sidewalk meets LS and ADA specification.
Plot Plan Inspection Passed 10/13/2022 10/13/2022 10/13/2022
Occupancy Inspection - Codes Residential Full C of O 10/13/2022 10/13/2022 10/13/2022
Misc
Resolved
10/13/2022
Documents & Images
Date Uploaded File Type Document Name
09/20/2021 MN #109 - PERMIT APP
09/21/2021 Approved Plans APPROVED DRAWINGS
09/21/2021 Approved Plans APPROVED TRUSS LAYOUT
09/21/2021 Approved Plans APPROVED TRUSS PACKAGE
09/21/2021 Permit Codes Residential Plan Review
09/23/2021 Plot Plan APPROVED PLOT PLAN
09/23/2021 Permit Codes Residential Plan Review
10/26/2021 Permit DS Building Permit
10/26/2021 Receipt Receipt for transaction:2021-008245
11/19/2021 109 Manor at Stoney Creek FTNG
11/29/2021 Letter INSPECTION SUMMARY
12/14/2021 Letter INSPECTION SUMMARY
01/07/2022 Letter INSPECTION SUMMARY
01/11/2022 Letter INSPECTION SUMMARY
05/26/2022 Letter INSPECTION SUMMARY
05/26/2022 Letter INSPECTION SUMMARY
05/26/2022 Letter INSPECTION SUMMARY
05/26/2022 Letter INSPECTION SUMMARY
06/13/2022 Letter INSPECTION SUMMARY
06/13/2022 Letter INSPECTION SUMMARY
06/23/2022 Letter INSPECTION SUMMARY
06/23/2022 Letter INSPECTION SUMMARY
08/02/2022 Letter INSPECTION SUMMARY
08/02/2022 Letter INSPECTION SUMMARY
08/02/2022 Letter INSPECTION SUMMARY
10/06/2022 Letter INSPECTION SUMMARY
10/06/2022 Letter INSPECTION SUMMARY
10/12/2022 Letter INSPECTION SUMMARY
10/12/2022 Letter INSPECTION SUMMARY
10/13/2022 Letter INSPECTION SUMMARY
10/13/2022 Letter Field Certificate of Occupancy
10/13/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home