Permit Application Status

PRRES20213952


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20213952
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED DECK
07/30/2021
08/26/2021
01/26/2022
09/01/2022
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
LOREN@SUMMITHOMESKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $420.00 $420.00 Paid 08/26/2021
Water Tap Fee $3,655.00 $3,655.00 Paid 08/26/2021
Water Meter Fee $479.24 $479.24 Paid 08/26/2021
Right of Way Permit Fee $80.00 $80.00 Paid 08/26/2021
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 08/26/2021
Valuation Fee New Single Family $1,052.30 $1,052.30 Paid 08/26/2021
Not Ready Inspection Fee $50.00 $50.00 Paid 08/31/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 10/19/2021 10/19/2021 10/19/2021
Misc
Informational
10/19/2021
APPROVED PER BRADLEY HUXOL 9/17/21
Water Service Inspection - R Passed 10/21/2021 (11:30) 10/21/2021 10/21/2021
Erosion Control Inspection Residential Failed 10/21/2021 10/21/2021 10/21/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
10/21/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Underslab Plumbing Inspection - Residential Passed 10/22/2021 10/22/2021 10/22/2021
Gas Service Inspection - Residential Failed 4/18/2022 4/18/2022 04/18/2022
Misc
Corrective Action Required
04/18/2022
-complete gas line for inspection -provide gas gaugh with minimum 10 psi for inspection
Electrical Service Inspection Passed 4/18/2022 4/18/2022 04/18/2022
Erosion Control Inspection Residential Failed 4/18/2022 04/18/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
04/18/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
04/18/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. maintain gravel filter
All Rough Inspection - Residential Failed 4/18/2022 4/18/2022 04/18/2022
Misc
Corrective Action Required
04/18/2022
-no further inspections until erosion control in compliance -fire block furr out at rear garage wall -protect nm with in 6’ of attic access -midway strap all dwv 2” in diameter or less -seal bottom plate penetration in bath 2 -seal bottom plate penetration in laundry -fire block seal space at laundry/pantry (seal gaps) -strap top plate where lapped less than 24” in pantry -seal top plate penetration in kitchen exterior wall not being used -truss hold downs at front patio -seal gaps above fire place. (If using Unfaced insulation must be packed tight and secured) -address stud bored right of fire place less than 5/8” to edge -seal bottom and top plate penetration hall master entry -block/seal hole under master tub for dwv -complete bath vent in master bath -strap top plate where lapped less than 25” master toilet -seal bottom plate penetration in master shower -seal bottom and top plate penetrations in dining -fire block at furr down ends in basement -seal all penetrations in vertical to horizontal fire block in basement -anchor bolts in basement to be tight and with in 12” of plate breaks -5 2x6 under beam bed 4 per plans -sold block to plans under kitchen island area and near -4 2x6 under beam behind bath 3 -double ever other joist per plans at cantilever -solid block cantilever -block under foyer closet -provide truss plans for inspection -complete gas line for inspection
All Rough Inspection - Residential Not Ready 4/29/2022 4/29/2022 04/29/2022
Misc
Corrective Action Required
04/18/2022
Inspection denied erosion control not in compliance -no further inspections until erosion control in compliance -fire block furr out at rear garage wall -protect nm with in 6’ of attic access -midway strap all dwv 2” in diameter or less -seal bottom plate penetration in bath 2 -seal bottom plate penetration in laundry -fire block seal space at laundry/pantry (seal gaps) -strap top plate where lapped less than 24” in pantry -seal top plate penetration in kitchen exterior wall not being used -truss hold downs at front patio -seal gaps above fire place. (If using Unfaced insulation must be packed tight and secured) -address stud bored right of fire place less than 5/8” to edge -seal bottom and top plate penetration hall master entry -block/seal hole under master tub for dwv -complete bath vent in master bath -strap top plate where lapped less than 25” master toilet -seal bottom plate penetration in master shower -seal bottom and top plate penetrations in dining -fire block at furr down ends in basement -seal all penetrations in vertical to horizontal fire block in basement -anchor bolts in basement to be tight and with in 12” of plate breaks -5 2x6 under beam bed 4 per plans -sold block to plans under kitchen island area and near -4 2x6 under beam behind bath 3 -double ever other joist per plans at cantilever -solid block cantilever -block under foyer closet -provide truss plans for inspection -complete gas line for inspection
Gas Service Inspection - Residential Failed 4/29/2022 4/29/2022 04/29/2022
Misc
Corrective Action Required
04/18/2022
Inspection denied erosion control not in compliance -complete gas line for inspection -provide gas gaugh with minimum 10 psi for inspection
Gas Service Inspection - Residential Passed 5/6/2022 5/6/2022 05/06/2022
Misc
Resolved
05/06/2022
Inspection denied erosion control not in compliance -complete gas line for inspection -provide gas gaugh with minimum 10 psi for inspection
All Rough Inspection - Residential Failed 5/6/2022 5/6/2022 05/06/2022
Misc
Corrective Action Required
04/29/2022
-fire block furr out at rear garage wall -anchor bolts in basement to be tight and with in 12” of plate breaks 5/6/22 - Support gas line to deck fire place - Fire block south basement wall at top plate
All Rough Inspection - Residential Passed 5/13/2022 5/13/2022 05/13/2022
Misc
Resolved
05/13/2022
Plot Plan Inspection Passed 8/9/2022 08/09/2022
Occupancy Inspection - Codes Residential Failed 8/9/2022 8/9/2022 08/09/2022
Misc
Corrective Action Required
08/09/2022
-address pending driveway and sidewalk inspections -address piers for deck poured without inspection -address pending sewer inspection -through bolts at deck post to beam connections -lock out for water heater breaker -paint gas line -tamper caps at A/c unit -seal all exterior penetrations -sod -splash blocks and sump pump discharge to extend 36” from foundation
Sewer Service Inspection - R Passed 8/25/2022 08/25/2022
Occupancy Inspection - Codes Residential Failed 8/25/2022 8/25/2022 08/25/2022
Misc
Corrective Action Required
08/09/2022
-pay all fees -address piers for deck poured without inspection
Piers/Caissons Inspection - Residential Passed 9/1/2022 09/01/2022
Erosion Control Inspection Residential Passed 9/1/2022 09/01/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
09/01/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. maintain gravel filter
Occupancy Inspection - Codes Residential Full C of O 9/1/2022 9/1/2022 09/01/2022
Misc
Resolved
09/01/2022
-pay all fees -address piers for deck poured without inspection
Documents & Images
Date Uploaded File Type Document Name
07/30/2021 H4 #136 - PERMIT APPLICATION
07/30/2021 Approved Plans Approved Drawings
07/30/2021 Approved Plans Approved Truss Package
07/30/2021 Approved Plans Approved Truss Layout
07/30/2021 Permit Codes Residential Plan Review
08/03/2021 Plot Plan Approved Plot Plan
08/03/2021 Permit Codes Residential Plan Review
08/26/2021 Permit DS Building Permit
08/26/2021 Receipt Receipt for transaction:2021-006846
10/18/2021 136 Hawthorne Ridge Subgrade
10/18/2021 136 Hawthorne Ridge FTNG
10/19/2021 Letter INSPECTION SUMMARY
10/21/2021 Letter INSPECTION SUMMARY
10/21/2021 Letter INSPECTION SUMMARY
10/22/2021 Letter INSPECTION SUMMARY
03/11/2022 Letter Codes 140 Day Letter
04/18/2022 Letter INSPECTION SUMMARY
04/18/2022 Letter INSPECTION SUMMARY
04/18/2022 Letter INSPECTION SUMMARY
04/18/2022 Letter INSPECTION SUMMARY
04/25/2022 136 Hawthorne Ridge - Field Issue (003)
04/29/2022 Letter INSPECTION SUMMARY
04/29/2022 Letter INSPECTION SUMMARY
05/06/2022 Letter INSPECTION SUMMARY
05/06/2022 Letter INSPECTION SUMMARY
05/13/2022 Letter INSPECTION SUMMARY
08/09/2022 Letter INSPECTION SUMMARY
08/09/2022 Letter INSPECTION SUMMARY
08/23/2022 H4136_SewerInspectionLetter
08/25/2022 Letter INSPECTION SUMMARY
08/25/2022 Letter INSPECTION SUMMARY
08/31/2022 136 Hawthorne Ridge FTNG
08/31/2022 Receipt Receipt for transaction:2022-007170
09/01/2022 Letter Codes Final Certificate of Occupancy
09/01/2022 Letter Field Certificate of Occupancy
09/01/2022 Letter INSPECTION SUMMARY
09/01/2022 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home