Permit Application Status

PRRES20210948


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20210948
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED PATIO
03/04/2021
03/16/2021
08/31/2021
11/15/2021
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
JOSH@SUMMITHOMESKC.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 03/18/2021 03/16/2021
Kim Brennan
Property boundary
Corrective Action Required
03/16/2021

Property boundary distances and bearings, as shown on the recorded plat, must be provided on the plot plan. Not shown for the front of the lot
Basement opening elevations
Corrective Action Required
03/16/2021

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan. The MLO's were removed on this lot
Basement egress
Corrective Action Required
03/16/2021

Basement egress location(s) and elevation of the lowest adjacent grade must be provided on the plot plan.
Residential Plan Review Approved 03/18/2021 03/16/2021
Kim Brennan
Residential Plan Review Approved 03/08/2021 03/05/2021
Kim Brennan
09 Identify furnace and water heater locations
Corrective Action Required
03/04/2021

Identify furnace and water heater location(s). (IRC Section G2406) Note 6.11 References the furnace but the drawings do not show a 6.11
Planning Review (RES) Approved 03/08/2021 03/04/2021
Kim Brennan
Plot Plan Review Rejected 03/08/2021 03/04/2021
Kim Brennan
Property boundary
Corrective Action Required
03/04/2021

Property boundary distances and bearings, as shown on the recorded plat, must be provided on the plot plan. Not shown for the front of the lot
Basement opening elevations
Corrective Action Required
03/04/2021

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan. The MLO's were removed on this lot
Basement egress
Corrective Action Required
03/04/2021

Basement egress location(s) and elevation of the lowest adjacent grade must be provided on the plot plan.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,018.79 $1,018.79 Paid 03/16/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 03/16/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 03/16/2021
8331507-Sewer Connection Fee $390.00 $390.00 Paid 03/16/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 03/16/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 03/16/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/17/2021
9110080-3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 10/17/2021
Outstanding Fees Amount Paid Owing Date Paid
9110080-Not Ready Inspection Fee $50.00 $0.00 $50.00 Not Paid


$50.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Failed 4/13/2021 (11:30) 4/13/2021 at 11:55 AM 04/13/2021
Misc
Corrective Action Required
04/13/2021
- PROVIDE ADDRESS - - PROVIDE HELIX OPTION DETAIL SHEET ( PLANS SHOW TWO #4 BARS CONTINIOUS ) - - PROVIDE ENGINEER'S SUBGRADE INSPECTION REPORT -
Footing Inspection - Residential Failed 4/14/2021 (1:45) 4/14/2021 at 2:00 PM 04/14/2021
Misc
Corrective Action Required
04/13/2021
- PROVIDE ADDRESS - - PROVIDE HELIX OPTION DETAIL SHEET ( PLANS SHOW TWO #4 BARS CONTINIOUS ) - - PROVIDE ENGINEER'S SUBGRADE INSPECTION REPORT - - PROVIDE 3RD PARTY FOOTING WITHIN 48 HOURS OF POUR -
Footing Inspection - Residential Failed 4/19/2021 04/19/2021
Misc
Corrective Action Required
04/14/2021
- PROVIDE ADDRESS - - PROVIDE HELIX OPTION DETAIL SHEET ( PLANS SHOW TWO #4 BARS CONTINIOUS ) : 3RD PARTY: - : 3RD PARTY FOOTING BY COLBY SHAW @ RES SIGNED & SEALED BY BRADLEY HUXOL ( NO SUBGRADE REPORT, SOIL BEARING NOT ADDRESSED ON 3RD PARTY FOOTING ) - PROVIDE ENGINEER'S SUBGRADE INSPECTION REPORT -
Footing Inspection - Residential Passed 4/20/2021 04/20/2021
Misc
Resolved
04/20/2021
Erosion Control Inspection Residential Failed 5/13/2021 05/13/2021
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/13/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - PROVIDE GRAVEL FILTER AT LOT ACCESS -
Underslab Plumbing Inspection - Residential Passed 5/13/2021 5/13/2021 05/13/2021
All Rough Inspection - Residential Partial 7/8/2021 7/8/2021 07/08/2021
Misc
Informational
07/08/2021
GARAGE PFH PORTAL FRAME OK TO COVER FRONT PORCH OK TO COVER COVERED DECK OK TO COVER : ONLY ABOVE ITEMS INSPECTED :
Gas Service Inspection - Residential Failed 7/27/2021 7/27/2021 07/27/2021
Misc
Corrective Action Required
07/27/2021
PROVIDE MIN 10 PSI FOR 15 MIN
All Rough Inspection - Residential Failed 7/27/2021 7/27/2021 07/27/2021
Misc
Informational
07/08/2021
GARAGE PFH PORTAL FRAME OK TO COVER FRONT PORCH OK TO COVER COVERED DECK OK TO COVER : ONLY ABOVE ITEMS INSPECTED :
Miscellaneous Correction
Corrective Action Required
07/27/2021
Provide 1 roof vent covered patio per plan Provide 4 studs GT bearing point at refrigerator/ stairway per plan Provide LIB bed #2 closet per plan Provide mid point support vert Seal fire blocking kitchen / stairway Seal top plate penetration pantry Seal bottom plate penetration master bed near sec & tub Provide nail protection plate master near sec Solid block sheathing breaks garage at front stoop Tighten anchor bolts garage Seal top plate penetrations at south wall garage Seal fire blocking gas line entry point Fire block ( insulate ) beam pockets Seal vertical to horizontal fire blocking rec room / bed 3 closet Seal Upward penetrations above service panel Install tubs Boca plate DWV BED # 3 Nail exterior sheathing per code
Sewer Service Inspection - R Passed 7/30/2021 (10:45) 7/30/2021 07/30/2021
Erosion Control Inspection Residential Failed 8/2/2021 08/02/2021
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/13/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - PROVIDE GRAVEL FILTER AT LOT ACCESS -
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
08/02/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - MAINTAIN SILT FENCE - - MAINTAIN GUTTER BUDDY REMOVE SEDIMENT BUILD UP -
Water Service Inspection - R Passed 8/2/2021 (10:30) 8/2/2021 08/02/2021
Gas Service Inspection - Residential Failed 8/4/2021 8/4/2021 08/04/2021
Misc
Corrective Action Required
07/27/2021
PROVIDE MIN 10 PSI FOR 15 MIN 0 PSI Michael Harkins 08/04/2021 10:30 AM
Electrical Service Inspection Passed 8/4/2021 8/4/2021 08/04/2021
All Rough Inspection - Residential Not Ready 8/4/2021 8/4/2021 08/04/2021
Misc
Informational
07/27/2021
GARAGE PFH PORTAL FRAME OK TO COVER FRONT PORCH OK TO COVER COVERED DECK OK TO COVER : ONLY ABOVE ITEMS INSPECTED :
Miscellaneous Correction
Corrective Action Required
07/27/2021
Provide LIB bed #2 closet per plan ( provide 2 nails top & bottom plate ) Fire block ( insulate ) beam pockets Seal Upward penetrations above service panel Install tubs Nail exterior sheathing per code
All Rough Inspection - Residential Failed 8/6/2021 8/6/2021 08/06/2021
Misc
Informational
08/04/2021
GARAGE PFH PORTAL FRAME OK TO COVER FRONT PORCH OK TO COVER COVERED DECK OK TO COVER : ONLY ABOVE ITEMS INSPECTED :
Miscellaneous Correction
Corrective Action Required
08/04/2021
Fire block ( insulate ) beam pockets Seal Upward penetrations above service panel ( seal vertical to horizontal at top plate fire blocking at furr out leave exposed for inspection) Install tubs Nail exterior sheathing per code : OK TO INSULATE :
All Rough Inspection - Residential Failed 8/11/2021 8/11/2021 08/11/2021
Misc
Informational
08/06/2021
GARAGE PFH PORTAL FRAME OK TO COVER FRONT PORCH OK TO COVER COVERED DECK OK TO COVER : ONLY ABOVE ITEMS INSPECTED :
Miscellaneous Correction
Corrective Action Required
08/06/2021
INSULATE TUB TRAP MASTER : OK TO INSULATE :
Gas Service Inspection - Residential Passed 8/12/2021 08/12/2021
Misc
Resolved
08/12/2021
All Rough Inspection - Residential Passed 8/12/2021 8/12/2021 08/12/2021
Misc
Informational
08/11/2021
GARAGE PFH PORTAL FRAME OK TO COVER FRONT PORCH OK TO COVER COVERED DECK OK TO COVER : ONLY ABOVE ITEMS INSPECTED :
Miscellaneous Correction
Resolved
08/12/2021
: OK TO INSULATE :
Driveway Inspection Partial 8/23/2021 8/23/2021 08/23/2021
Misc
Corrective Action Required
08/23/2021
Forms were placed and aggregate was present and compacted. Curbing is busted up and needs 2 panels removed and replaced. RP 8-23-21
Driveway Inspection Partial 8/27/2021 8/27/2021 08/27/2021
Misc
Corrective Action Required
08/23/2021
Forms were placed and aggregate was present and compacted. Curbing is busted up and needs 2 panels removed and replaced. RP 8-23-21
Misc
Informational
08/27/2021
Busted curbing has been removed. New curbing has been formed and dowel bars have been inserted. RP 8-27-21
Driveway Inspection Passed 9/10/2021 9/10/2021 09/10/2021
Misc
Informational
09/10/2021
Finished driveway meets LS and ADA specs. RP 9-10-21
Sidewalk Inspection Partial 10/7/2021 10/7/2021 10/07/2021
Misc
Informational
10/07/2021
Forms are in place and aggregate is present and compacted.
Sidewalk Inspection Passed 10/15/2021 10/15/2021 10/12/2021
Misc
Informational
10/07/2021
Forms are in place and aggregate is present and compacted.
Misc
Informational
10/12/2021
10-12-21 AN sidewalk looks good and meets ADA specs
Erosion Control Inspection Residential Failed 10/20/2021 10/20/2021
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
08/02/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - PROVIDE GRAVEL FILTER AT LOT ACCESS -
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
08/02/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - MAINTAIN SILT FENCE - - MAINTAIN GUTTER BUDDY REMOVE SEDIMENT BUILD UP -
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
10/20/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - MAINTAIN ERIOSION CONTROL UNTIL SOD COMPLETE -
Piers/Caissons Inspection - Residential Passed 10/20/2021 10/20/2021
Misc
Informational
10/20/2021
ON 3RD PARTY FOOTING
Occupancy Inspection - Codes Residential Failed 10/20/2021 10/20/2021 10/20/2021
Miscellaneous Correction
Corrective Action Required
10/20/2021
submit back flow certification - provide sod & splash blocks -Moisture barrier on top of outside lighting fixtures and power meter. -label non-gfci outlets in garage. -install window above front door. - provide access panel for jet tub in master bedroom. - Self closing door to garage.
Occupancy Inspection - Codes Residential Not Ready 10/22/2021 10/22/2021 10/22/2021
Miscellaneous Correction
Corrective Action Required
10/20/2021
submit back flow certification - provide sod - -Moisture barrier on top of outside lighting fixtures and power meter. -label non-gfci outlets in garage. -install window above front door. - provide access panel for jet tub in master bedroom.
Occupancy Inspection - Codes Residential Temporary C of O 10/26/2021 10/26/2021 10/26/2021
Miscellaneous Correction
Corrective Action Required
10/22/2021
*TCO UNTIL 11/26/2021* -install window above front door.
Plot Plan Inspection Passed 10/26/2021 10/26/2021 10/26/2021
Occupancy Inspection - Codes Residential Full C of O 11/15/2021 11/15/2021 11/15/2021
Miscellaneous Correction
Resolved
11/15/2021
Documents & Images
Date Uploaded File Type Document Name
03/04/2021 Application Form Permit Application and License Tax Form
03/04/2021 Letter Codes Residential Plan Review
03/05/2021 Approved Plans Approved Plans
03/05/2021 Approved Plans Approved Truss Layout
03/05/2021 Approved Plans Approved Truss Package
03/16/2021 Plot Plan Approved Plot Plan
03/16/2021 Receipt Receipt for transaction:2021-001309
03/16/2021 Letter DS Building Permit
04/13/2021 Letter INSPECTION SUMMARY
04/14/2021 Lot 89 Woodside Ridge Footing Inspection
04/14/2021 Letter INSPECTION SUMMARY
04/14/2021 Letter INSPECTION SUMMARY
04/16/2021 W0 #89 - Newhaven - Mediterranean - A3, GN1_0, S3_1 REVISION- signed
04/19/2021 Letter INSPECTION SUMMARY
04/20/2021 Lot 89 Woodside Ridge Footing Inspection
04/20/2021 Letter INSPECTION SUMMARY
04/20/2021 Letter INSPECTION SUMMARY
05/13/2021 Letter INSPECTION SUMMARY
05/13/2021 Letter INSPECTION SUMMARY
07/08/2021 Letter INSPECTION SUMMARY
07/27/2021 Letter INSPECTION SUMMARY
07/27/2021 Letter INSPECTION SUMMARY
07/30/2021 Letter INSPECTION SUMMARY
08/02/2021 Letter INSPECTION SUMMARY
08/02/2021 Letter INSPECTION SUMMARY
08/04/2021 Letter INSPECTION SUMMARY
08/04/2021 Letter INSPECTION SUMMARY
08/04/2021 Letter INSPECTION SUMMARY
08/04/2021 Letter INSPECTION SUMMARY
08/11/2021 Letter INSPECTION SUMMARY
08/11/2021 Letter INSPECTION SUMMARY
08/12/2021 Letter INSPECTION SUMMARY
08/12/2021 Letter INSPECTION SUMMARY
08/23/2021 Letter INSPECTION SUMMARY
08/27/2021 Letter INSPECTION SUMMARY
09/10/2021 Letter INSPECTION SUMMARY
09/20/2021 Approved Plans Approved Revised Patio Drawings
10/07/2021 Letter INSPECTION SUMMARY
10/12/2021 Letter INSPECTION SUMMARY
10/17/2021 Receipt Receipt for transaction:2021-008038
10/20/2021 Letter INSPECTION SUMMARY
10/20/2021 Letter INSPECTION SUMMARY
10/20/2021 Letter INSPECTION SUMMARY
10/22/2021 Letter INSPECTION SUMMARY
10/25/2021 306 NW Ambersham Dr 2021-Back Flow
10/26/2021 Letter Codes Temporary Certificate of Occupancy
10/26/2021 Letter INSPECTION SUMMARY
11/12/2021 window install picture before trim
11/15/2021 Letter Field Certificate of Occupancy
11/15/2021 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home