Review Type |
Outcome |
Est. Completion Date |
Completed |
Plot Plan Review
|
Approved
|
03/26/2021
|
03/24/2021
|
|
Kim Brennan
|
|
Sidewalks
Corrective Action Required
Sidewalks with dimensions must be provided on the plot plan.
|
|
|
Residential Plan Review
|
Approved
|
03/26/2021
|
03/24/2021
|
|
Kim Brennan
|
|
07 Identify emergency escape openings from bedrooms
Corrective Action Required
Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance)
|
|
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315)
|
|
10 Combustion air
Corrective Action Required
Provide combustion air calculations and specify transfer air grilles for fuel burning appliances located in confined space(s). (IRC Chapter 17 and Section G2407)
|
|
Misc
Corrective Action Required
Drawings must be sealed and stamped by a licensed professional in the State of Missouri
|
|
12 Detail required separation between garage and living area including door
Corrective Action Required
Detail required separation between garage and living area including door, door closer and gypsum board. (IRC R302.5)
Does not specify 20 minute rated
|
|
15 Provide size, spacing, species, and grade of rafter, ceiling joist mater
Corrective Action Required
Provide size, spacing, species, and grade of rafter, ceiling joist materials and ridge and valley members. (IRC Section R802)
|
|
16 Identify location(s) of vertical supports and purlins.
Corrective Action Required
Identify location(s) of vertical supports and purlins. (IRC Section R802.5.1)
|
|
17 Specification of rafter ties or ridge beam design.
Corrective Action Required
Specification of rafter ties or ridge beam design. (IRC Section 802.3.1)
|
|
30 Identify type of protection used in unfinished areas under
Corrective Action Required
Identify type of protection used in unfinished areas under floor trusses. (IRC Section R501.3)
|
|
33 Identify braced wall locations and length of braced wall panel(s).
Corrective Action Required
Identify braced wall locations and length of braced wall panel(s). (IRC Section R602.10)
|
|
34 Specify type of wall bracing method(s) utilized.
Corrective Action Required
Specify type of wall bracing method(s) utilized. (IRC Section R602.10)
|
|
35 Specify acceptable material and size of exterior sheathing.
Corrective Action Required
Specify acceptable material and size of exterior sheathing. (IRC Section R703)
|
|
|
Plot Plan Review
|
Rejected
|
02/19/2021
|
02/17/2021
|
|
Kim Brennan
|
|
Sidewalks
Corrective Action Required
Sidewalks with dimensions must be provided on the plot plan.
|
|
|
Residential Plan Review
|
Rejected
|
02/19/2021
|
02/17/2021
|
|
Kim Brennan
|
|
07 Identify emergency escape openings from bedrooms
Corrective Action Required
Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance)
|
|
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315)
|
|
10 Combustion air
Corrective Action Required
Provide combustion air calculations and specify transfer air grilles for fuel burning appliances located in confined space(s). (IRC Chapter 17 and Section G2407)
|
|
Misc
Corrective Action Required
Drawings must be sealed and stamped by a licensed professional in the State of Missouri
|
|
12 Detail required separation between garage and living area including door
Corrective Action Required
Detail required separation between garage and living area including door, door closer and gypsum board. (IRC R302.5)
Does not specify 20 minute rated
|
|
15 Provide size, spacing, species, and grade of rafter, ceiling joist mater
Corrective Action Required
Provide size, spacing, species, and grade of rafter, ceiling joist materials and ridge and valley members. (IRC Section R802)
|
|
16 Identify location(s) of vertical supports and purlins.
Corrective Action Required
Identify location(s) of vertical supports and purlins. (IRC Section R802.5.1)
|
|
17 Specification of rafter ties or ridge beam design.
Corrective Action Required
Specification of rafter ties or ridge beam design. (IRC Section 802.3.1)
|
|
30 Identify type of protection used in unfinished areas under
Corrective Action Required
Identify type of protection used in unfinished areas under floor trusses. (IRC Section R501.3)
|
|
33 Identify braced wall locations and length of braced wall panel(s).
Corrective Action Required
Identify braced wall locations and length of braced wall panel(s). (IRC Section R602.10)
|
|
34 Specify type of wall bracing method(s) utilized.
Corrective Action Required
Specify type of wall bracing method(s) utilized. (IRC Section R602.10)
|
|
35 Specify acceptable material and size of exterior sheathing.
Corrective Action Required
Specify acceptable material and size of exterior sheathing. (IRC Section R703)
|
|
|