Permit Application Status

PRRES20203307


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20203307
Building Permit - Residential
Expired
CONATY TRUST
NEW OTHER (RESIDENTIAL)
INGROUND POOL
09/24/2020
09/29/2020
Locations
Contacts
CONATY TRUST, Address:1344 NE BRANDYWINE RD  
SWIM THINGS INC, Address:3010 W 40 HWY, Phone:(816) 224-2600  
VINCE@SWIMTHINGS.COM  
A & A ELECTRICAL INC, Address:705 SQUIRE CT, Phone:(816) 847-1902  
HOWERTON PLUMBING LLC, Address:195 NW AA HWY, Phone:(816) 694-0303  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/24/2020 09/24/2020
Dylan Eppert
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Other $301.50 $301.50 Paid 09/29/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Pool Steel/Bonding - Residential Pending
Misc
Informational
03/16/2021
- SHELL POOL SKIMMER BASKET @ DEEP END /JACUZZI DRAIN -
Misc
Corrective Action Required
03/16/2021
Perimeter surface bonding not approved. -Alternate method on north side of pool requires single bare 8awg conductor to be placed 18-24” from inside wall of pool, buried 4-6” in depth. -Deck area approved and ok to pour
Pool Final - Residential Pending
Miscellaneous Correction
Corrective Action Required
07/30/2021
-ADDRESS POOL BONDING INSPECTION NOT APPROVED **Alternate method on north side of pool requires single bare 8awg conductor to be placed 18-24” from inside wall of pool, buried 4-6” in depth. Expose this bonding conductor for verification
Pool Steel/Bonding - Residential Partial 11/18/2020 11/18/2020 11/18/2020
Misc
Informational
11/18/2020
- SHELL POOL SKIMMER BASKET @ DEEP END /JACUZZI DRAIN -
Gas Piping Inspection - Residential Failed 2/5/2021 2/5/2021 02/05/2021
Misc
Corrective Action Required
02/05/2021
-PLASTIC PE GAS LINE CAN ONLY BE INSTALLED UNDERGROUND. NO PORTION OF THE PE GAS LINE CAN BE ABOVE GROUND
Gas Piping Inspection - Residential Passed 2/23/2021 2/23/2021 02/23/2021
Misc
Resolved
02/23/2021
-PLASTIC PE GAS LINE CAN ONLY BE INSTALLED UNDERGROUND. NO PORTION OF THE PE GAS LINE CAN BE ABOVE GROUND
Pool Steel/Bonding - Residential Failed 3/16/2021 3/16/2021 03/16/2021
Misc
Informational
11/18/2020
- SHELL POOL SKIMMER BASKET @ DEEP END /JACUZZI DRAIN -
Misc
Corrective Action Required
03/16/2021
Perimeter surface bonding not approved. -Alternate method on north side of pool requires single bare 8awg conductor to be placed 18-24” from inside wall of pool, buried 4-6” in depth. -Deck area approved and ok to pour
Pool Final - Residential Failed 7/1/2021 7/1/2021 07/01/2021
Miscellaneous Correction
Corrective Action Required
07/01/2021
-ADDRESS POOL BONDING INSPECTION NOT APPROVED
Pool Final - Residential Failed 7/30/2021 07/30/2021
Miscellaneous Correction
Corrective Action Required
07/01/2021
-ADDRESS POOL BONDING INSPECTION NOT APPROVED **Alternate method on north side of pool requires single bare 8awg conductor to be placed 18-24” from inside wall of pool, buried 4-6” in depth. Expose this bonding conductor for verification
Documents & Images
Date Uploaded File Type Document Name
09/24/2020 APPROVED IN GOUND POOL
09/29/2020 Receipt Receipt for transaction:2020-006572
09/29/2020 Letter DS Building Permit
11/18/2020 Letter INSPECTION SUMMARY
11/24/2020 Letter INSPECTION SUMMARY
02/05/2021 Letter INSPECTION SUMMARY
02/23/2021 Letter INSPECTION SUMMARY
03/02/2021 Letter INSPECTION SUMMARY
03/16/2021 Letter INSPECTION SUMMARY
03/16/2021 Letter INSPECTION SUMMARY
07/01/2021 Letter INSPECTION SUMMARY
07/01/2021 Letter INSPECTION SUMMARY
07/30/2021 Letter INSPECTION SUMMARY
02/07/2022 Letter Codes 180 Day Letter
02/07/2022 Letter Codes 180 Day Letter
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home