Permit Application Status

PRRES20193591


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20193591
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW SINGLE FAMILY PARTIALLY FINISHED BASEMENT COVERED DECK
12/11/2019
12/27/2019
06/09/2020
01/07/2021
Locations
Contacts
TRUMARK HOMES, LLC, Address:424 SE MAXWELL DR, Phone:(816) 564-5613  
YANCIK@SBCGLOBAL.NET  
IMPACT ELECTRICAL SOLUTIONS LLC, Address:14 ANCHOR DRIVE, Phone:(816) 674-9345  
BLUE VALLEY HEATING & COOLING LLC, Address:P O BOX 241, Phone:(816) 867-5122  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 12/13/2019 12/26/2019
Dylan Eppert
Legal description
Corrective Action Required
12/12/2019

The legal description, including plat or phase number and lot number, and street address must be provided on the plot plan. INCORRECT STREET ADDRESS
North arrow and scale
Corrective Action Required
12/12/2019

The plot plan must be submitted on either (1) 81/2” x 11”, (2) 81/2”x 14”, or (3) 11” x 17” paper. All information on the plot plan must be drawn to scale. Scale must be 1” = 10’, 20’, or 30’; smaller scales that are multiples of the preceding scales may be used if necessary to represent large sites. All information on the plot plan must be clearly legible.) CORRECT NORTH ARROW
As-graded plot plan
Corrective Action Required
12/12/2019

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Drainage swales
Corrective Action Required
12/12/2019

Drainage swales (where required); show spot elevations within the swale as required to conform to the approved master drainage plan (if applicable), must be provide
Plot Plan Review Approved 12/23/2019 12/19/2019
Steve Conrick
Legal description
Corrective Action Required
12/19/2019

The legal description, including plat or phase number and lot number, and street address must be provided on the plot plan. INCORRECT STREET ADDRESS
North arrow and scale
Corrective Action Required
12/19/2019

The plot plan must be submitted on either (1) 81/2” x 11”, (2) 81/2”x 14”, or (3) 11” x 17” paper. All information on the plot plan must be drawn to scale. Scale must be 1” = 10’, 20’, or 30’; smaller scales that are multiples of the preceding scales may be used if necessary to represent large sites. All information on the plot plan must be clearly legible.) CORRECT NORTH ARROW
As-graded plot plan
Corrective Action Required
12/19/2019

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Drainage swales
Corrective Action Required
12/19/2019

Drainage swales (where required); show spot elevations within the swale as required to conform to the approved master drainage plan (if applicable), must be provide
Residential Plan Review Approved 12/23/2019 12/19/2019
Steve Conrick
04 Two (2) copies of construction drawings
Corrective Action Required
12/19/2019

Two (2) copies of construction drawings. (Plans to be signed and sealed by an architect or engineer registered in the State of Missouri.)
Miscellaneous Correction
Corrective Action Required
12/19/2019

ADDRESS NEEDS TO BE ON PLANS.
Residential Plan Review Rejected 12/16/2019 12/12/2019
Steve Conrick
04 Two (2) copies of construction drawings
Corrective Action Required
12/12/2019

Two (2) copies of construction drawings. (Plans to be signed and sealed by an architect or engineer registered in the State of Missouri.)
Miscellaneous Correction
Corrective Action Required
12/12/2019

ADDRESS NEEDS TO BE ON PLANS.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,089.41 $1,089.41 Paid 12/27/2019
Right of Way Permit Fee $80.00 $80.00 Paid 12/27/2019
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 12/27/2019
8331507-Sewer Connection Fee $480.00 $480.00 Paid 12/27/2019
Water Tap Fee $3,477.00 $3,477.00 Paid 12/27/2019
Water Meter Fee $425.02 $425.02 Paid 12/27/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 1/2/2020 (11:30) 1/2/2020 01/02/2020
Misc
Corrective Action Required
01/02/2020
Post site address Fix erosion control and clean up street when done Ok to pour
Underslab Plumbing Inspection - Residential Failed 1/10/2020 1/10/2020 01/10/2020
Misc
Corrective Action Required
01/10/2020
No inspection performed Fix erosion control and clean up street Post site address
Erosion Control Inspection Residential Failed 1/14/2020 1/14/2020 01/10/2020
Misc
Corrective Action Required
01/10/2020
Fix erosion control at front of lot and clean up street before any future inspections
Underslab Plumbing Inspection - Residential Passed 1/14/2020 1/14/2020 01/14/2020
Misc
Resolved
01/14/2020
Sewer Service Inspection - R Passed 1/15/2020 01/15/2020
All Rough Inspection - Residential Partial 4/10/2020 04/10/2020
Misc
Informational
04/10/2020
Inspected garage portal framing only
Piers/Caissons Inspection - Residential Failed 4/22/2020 (8:00) 4/22/2020 04/22/2020
Misc
Corrective Action Required
04/22/2020
- (2) 18 X 36 PIERS - - PLANS ON SITE SHOW 20 X 36 PIER BETWEEN THE (2) INSPECTED -
Erosion Control Inspection Residential Failed 5/14/2020 at 7:30 AM 05/14/2020
Misc
Corrective Action Required
01/10/2020
Fix erosion control at front of lot and clean up street before any future inspections
DCM5 ESC INSP DENIED
Corrective Action Required
05/14/2020
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. - REPAIR SILT FENCE -
All Rough Inspection - Residential Failed 5/14/2020 5/14/2020 05/14/2020
Misc
Informational
04/10/2020
Inspected garage portal framing only
Misc
Corrective Action Required
05/14/2020
- DENIED INSPECTION EROSION CONTROL -
Electrical Service Inspection Failed 5/14/2020 5/14/2020 05/14/2020
Misc
Corrective Action Required
05/14/2020
- NO INSPECTION MAINTAIN EROSION CONTROL -
Gas Service Inspection - Residential Failed 5/14/2020 5/14/2020 05/14/2020
Misc
Corrective Action Required
05/14/2020
- NO INSPECTION - - MAINTAIN EROSION CONTROL -
Water Service Inspection - R Passed 5/15/2020 (10:00) 5/15/2020 at 10:35 AM 05/15/2020
Gas Piping Inspection - Residential Passed 5/18/2020 05/18/2020
Gas Service Inspection - Residential Passed 5/18/2020 5/18/2020 05/18/2020
Misc
Resolved
05/18/2020
- NO INSPECTION - - MAINTAIN EROSION CONTROL -
Electrical Service Inspection Passed 5/18/2020 5/18/2020 05/18/2020
Misc
Resolved
05/18/2020
- NO INSPECTION MAINTAIN EROSION CONTROL -
All Rough Inspection - Residential Failed 5/18/2020 5/18/2020 05/18/2020
Misc
Informational
05/14/2020
Inspected garage portal framing only
Misc
Resolved
05/18/2020
- DENIED INSPECTION EROSION CONTROL -
Misc
Corrective Action Required
05/18/2020
- SEAL COAX CABLE BOTTOM PLATE BED # 2 - - SEAL BORE BOTTOM PLATE LINEN CLOSET - -VENT ALL BATH EXHAUST TO EXTERIOR CONNECT WITH METALLIC TAPE - - PROVIDE PFH PORTAL FRAME PER PLAN GARAGE DOOR DBL BOTTOM PLATE & 5/8 ANCHOR BOLTS - - TIGHTEN ANCHOR BOLTS GARAGE & BASEMENT - - PROVIDE PLUMBING NAIL GUARDS TOP PLATE AT WET BAR BASEMENT - - SEAL DWV AT FIREBLOCK BED # 3 CLOSET - - PROVIDE TWO 3" SCH 40 COLUMNS UNDER BEAM AT STAIRWAY PER PLAN -
All Rough Inspection - Residential Failed 5/21/2020 5/21/2020 05/21/2020
Misc
Informational
05/18/2020
Inspected garage portal framing only
Misc
Corrective Action Required
05/18/2020
-VENT ALL BATH EXHAUST TO EXTERIOR CONNECT WITH METALLIC TAPE - - PROVIDE PFH PORTAL FRAME PER PLAN GARAGE DOOR tighten 5/8 ANCHOR BOLTS - TIGHTEN ANCHOR BOLTS BASEMENT - at 3 window egress others covered by insulation - PROVIDE TWO 3" SCH 40 COLUMNS UNDER BEAM AT STAIRWAY PER PLAN - plans says two
All Rough Inspection - Residential Failed 5/26/2020 5/26/2020 05/26/2020
Misc
Informational
05/21/2020
Inspected garage portal framing only
Misc
Corrective Action Required
05/21/2020
- PROVIDE TWO 3" SCH 40 COLUMNS UNDER BEAM AT STAIRWAY PER PLAN - plans says two
Sidewalk Inspection Partial 6/23/2020 6/23/2020 06/23/2020
Misc
Informational
06/23/2020
Forms were placed and aggregate was present and compacted. Had them lower the hydrant valve to be level with the walk. RP 6-23-20
Driveway Inspection Partial 6/23/2020 6/23/2020 06/23/2020
Misc
Informational
06/23/2020
Forms were placed and aggregate was present and compacted. RP 6-23-20
Driveway Inspection Passed 7/3/2020 7/3/2020 07/09/2020
Misc
Informational
06/23/2020
Forms were placed and aggregate was present and compacted. RP 6-23-20
Misc
Informational
07/09/2020
Finished driveway meets LS and ADA specs. RP 7-9-20
Sidewalk Inspection Passed 7/3/2020 7/3/2020 07/09/2020
Misc
Informational
06/23/2020
Forms were placed and aggregate was present and compacted. Had them lower the hydrant valve to be level with the walk. RP 6-23-20
Misc
Informational
07/09/2020
Finished sidewalk meets LS and ADA specs. RP 7-9-20
Plot Plan Inspection Passed 12/22/2020 12/22/2020
Occupancy Inspection - Codes Residential Full C of O 1/7/2021 1/7/2021 01/07/2021
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home