Summary
PRRES20191887
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED PATIO
07/16/2019
07/19/2019
04/24/2020
Locations
Contacts
CMH PARKS INC, Address:5000 CLAYTON RD  
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
KIMBEL MECHANICAL SYSTEMS, INC, Address:1936 N SHILOH DR, Phone:(479) 756-1099  
RYAN@SUMMITHOMESKC.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 07/18/2019 07/17/2019
Kim Brennan
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
07/16/2019

Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315) No smoke detector or carbon monoxide detector shown outside of bedroom #6.
Plot Plan Review Approved 07/18/2019 07/17/2019
Steve Conrick
As-graded plot plan
Corrective Action Required
07/16/2019

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy. *Add note "AS-GRADED PLOT PLAN IS REQUIRED PRIOR TO SODDING."
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,443.53 $1,443.53 Paid 07/19/2019
Right of Way Permit Fee $80.00 $80.00 Paid 07/19/2019
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 07/19/2019
8331507-Sewer Connection Fee $600.00 $600.00 Paid 07/19/2019
Water Tap Fee $3,477.00 $3,477.00 Paid 07/19/2019
Water Meter Fee $425.02 $425.02 Paid 07/19/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 8/16/2019 (10:30) 8/16/2019 08/16/2019
Underslab Plumbing Inspection - Residential Passed 9/13/2019 9/13/2019 09/13/2019
Sewer Service Inspection - R Passed 9/18/2019 09/18/2019
Water Service Inspection - R Passed 9/19/2019 09/19/2019
All Rough Inspection - Residential Failed 11/5/2019 11/5/2019 11/05/2019
Misc
Corrective Action Required
11/05/2019
- uncover front garage portal straps - anchor bolt needed on east side of garage where edges of sill plate meet - support plumbing in garage above door entrance - solid block heat chase at top plate and going into floor joist cavity, first floor - fireblock electrical penetrations In heat chase at bottom subfloor - fire block electrical penetration through top plate, left of fire place - protect piping at bottom plate, upstairs bathroom SW corner Ok to insulate
Electrical Service Inspection Passed 11/5/2019 11/5/2019 11/05/2019
Gas Piping Inspection - Residential Passed 11/5/2019 11/5/2019 11/05/2019
All Rough Inspection - Residential Passed 11/8/2019 11/8/2019 11/08/2019
Misc
Resolved
11/08/2019
Ok to insulate
Driveway Inspection Partial 1/28/2020 1/28/2020 01/28/2020
Misc
Informational
01/28/2020
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Sidewalk Inspection Partial 1/28/2020 1/28/2020 01/28/2020
Misc
Informational
01/28/2020
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Driveway Inspection Passed 2/4/2020 02/18/2020
Misc
Resolved
02/18/2020
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Sidewalk Inspection Passed 2/4/2020 02/18/2020
Misc
Resolved
02/18/2020
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Occupancy Inspection - Codes Residential Failed 2/28/2020 2/28/2020 02/28/2020
Misc
Corrective Action Required
02/28/2020
- Submit as graded plot plan for review - Door to garage must be self closing - Access required to jacuzzi tub motor - Breaker lockout required for hardwired cooktop/hood - Main water line in basement, anti siphon required with set screw sheared off - AFCI protection required at all locations per 2017 NEC 210.12 - Dishwasher GFCI protection required NEC 210.8 - Seal all exterior penetrations - Complete final grade and place sod - Place splashblocks at all downspout and sump pump discharge locations, minimum distance to foundation 36”
Plot Plan Inspection Passed 4/20/2020 04/20/2020
Gas Service Inspection - Residential Passed 04/20/2020
Occupancy Inspection - Codes Residential Failed 4/21/2020 4/21/2020 04/20/2020
Misc
Corrective Action Required
02/28/2020
- Obtain irrigation system permit and submit backflow certification
Occupancy Inspection - Codes Residential Full C of O 4/24/2020 4/24/2020 04/24/2020
Documents & Images
Date Uploaded File Type Document Name
07/16/2019 Letter Codes Residential Plan Review
07/16/2019 Letter Codes Residential Plan Review
07/19/2019 Receipt Receipt for transaction: 2019-004909
07/19/2019 Letter DS Building Permit
07/19/2019 Plot Plan DOC071919-004
08/16/2019 Letter INSPECTION SUMMARY
09/13/2019 Letter INSPECTION SUMMARY
09/18/2019 Letter INSPECTION SUMMARY
09/19/2019 Letter INSPECTION SUMMARY
11/05/2019 Letter INSPECTION SUMMARY
11/05/2019 Letter INSPECTION SUMMARY
11/05/2019 Letter INSPECTION SUMMARY
11/08/2019 Letter INSPECTION SUMMARY
01/28/2020 Letter INSPECTION SUMMARY
01/28/2020 Letter INSPECTION SUMMARY
02/18/2020 Letter INSPECTION SUMMARY
02/18/2020 Letter INSPECTION SUMMARY
02/28/2020 Letter INSPECTION SUMMARY
04/17/2020 LOT 40 ASBUILT
04/20/2020 Letter INSPECTION SUMMARY
04/20/2020 Letter INSPECTION SUMMARY
04/20/2020 Letter INSPECTION SUMMARY
04/20/2020 Letter INSPECTION SUMMARY
04/24/2020 Letter Field Certificate of Occupancy
04/24/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home