Summary
PRRES20191609
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED PATIO
06/20/2019
06/24/2019
01/23/2020
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
KIMBEL MECHANICAL SYSTEMS, INC, Address:1936 N SHILOH DR, Phone:(479) 756-1099  
RYAN@SUMMITHOMESKC.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 06/24/2019 06/21/2019
Steve Conrick
Residential Plan Review Approved 06/24/2019 06/20/2019
Kim Brennan
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $930.82 $930.82 Paid 06/24/2019
Right of Way Permit Fee $80.00 $80.00 Paid 06/24/2019
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 06/24/2019
8331507-Sewer Connection Fee $360.00 $360.00 Paid 06/24/2019
Water Tap Fee $3,409.00 $3,409.00 Paid 06/24/2019
Water Meter Fee $408.37 $408.37 Paid 06/24/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Not Ready 7/9/2019 at 3:30 PM 07/09/2019
Footing Inspection - Residential Passed 7/10/2019 (8:45) 7/10/2019 at 9:01 AM 07/10/2019
Sewer Service Inspection - R Passed 8/5/2019 at 1:30 PM 08/05/2019
Water Service Inspection - R Passed 8/9/2019 8/9/2019 at 2:46 PM 08/09/2019
Underslab Plumbing Inspection - Residential Passed 8/12/2019 8/12/2019 at 8:00 AM 08/12/2019
Piers/Caissons Inspection - Residential Passed 9/13/2019 (9:00) 9/13/2019 09/13/2019
All Rough Inspection - Residential Failed 10/8/2019 10/8/2019 10/08/2019
Misc
Corrective Action Required
10/08/2019
** Garage braced wall panels exterior straps are missing fasteners ** Master bath vent fan duct has come off of vent.
Electrical Service Inspection Passed 10/8/2019 10/8/2019 10/08/2019
Gas Piping Inspection - Residential Passed 10/8/2019 10/8/2019 10/08/2019
All Rough Inspection - Residential Failed 10/11/2019 10/11/2019 10/11/2019
Misc
Partial Correction
10/11/2019
** Garage braced wall panels exterior straps are missing fasteners ** Master bath vent fan duct has come off of vent.
Misc
Corrective Action Required
10/11/2019
** Garage braced wall panels exterior straps are missing fasteners
All Rough Inspection - Residential Passed 10/15/2019 10/15/2019 10/15/2019
Misc
Resolved
10/15/2019
** Garage braced wall panels exterior straps are missing fasteners ** Master bath vent fan duct has come off of vent.
Misc
Resolved
10/15/2019
** Garage braced wall panels exterior straps are missing fasteners
Driveway Inspection Passed 11/27/2019 11/27/2019 12/02/2019
Misc
Informational
12/02/2019
The approach was formed and rock was installed and compacted on 11/27. When I came back today the concrete had been poured and everything appeared to be up the specification.
Occupancy Inspection - Codes Residential Failed 1/14/2020 1/14/2020 01/14/2020
Misc
Corrective Action Required
01/14/2020
- Laundry room GFCI outlet required - Disposal outlet not working properly - Support gas line to code - Ductwork support loose on north side of basement. Needs to be reinstalled. - Two locking devices required on sliding glass door - Sump pump discharge 3’ from foundation - 3 GFCI outlets required for garage. Contact Mark Harding building inspection manager to resolve. - Replace broken splash block on north side - Secure AC electrical whip within 12” from disconnect - Grading on east side by patio within 6” from siding - Floor outlet by kitchen bring up to code with combustible material
Occupancy Inspection - Codes Residential Full C of O 1/23/2020 1/23/2020 01/23/2020
Misc
Resolved
01/23/2020
Documents & Images
Date Uploaded File Type Document Name
06/24/2019 Receipt Receipt for transaction: 2019-004055
06/24/2019 Letter Codes Building Permit
06/26/2019 Plot Plan DOC062519-06252019160444
07/09/2019 Letter INSPECTION SUMMARY
07/10/2019 Letter INSPECTION SUMMARY
08/05/2019 Letter INSPECTION SUMMARY
08/09/2019 Letter INSPECTION SUMMARY
08/12/2019 Letter INSPECTION SUMMARY
09/13/2019 Letter INSPECTION SUMMARY
10/08/2019 Letter INSPECTION SUMMARY
10/08/2019 Letter INSPECTION SUMMARY
10/08/2019 Letter INSPECTION SUMMARY
10/11/2019 Letter INSPECTION SUMMARY
10/15/2019 Letter INSPECTION SUMMARY
12/02/2019 Letter DE-Daily Inspection Summary
01/14/2020 Letter INSPECTION SUMMARY
01/23/2020 Letter Codes Final Certificate of Occupancy
01/23/2020 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home