Summary
PRRES20183477
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE FINISHED AND UNFINISHED BASEMENT
10/09/2018
11/07/2018
11/04/2019
Locations
Contacts
SPELLERBERG ENTERPRISES LLC, Address:613 NE VIEWPARK DR, Phone:(816) 550-5535  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
O'CONNELL ELECTRIC LLC, Address:11017 S ALLEY JACKSON RD, Phone:(816) 547-4706  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
SPELLERBERGENTERPRISES@GMAIL.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 10/31/2018 10/30/2018
Steve Conrick
Residential Plan Review Approved 10/11/2018 10/09/2018
Brandon Kalwei
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $918.20 $918.20 Paid 11/07/2018
Right of Way Permit Fee $80.00 $80.00 Paid 11/07/2018
8331507-Sewer Connection Fee $360.00 $360.00 Paid 11/07/2018
Water Tap Fee $3,409.00 $3,409.00 Paid 11/07/2018
Water Meter Fee $408.37 $408.37 Paid 11/07/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 11/8/2018 (11:30) 11/8/2018 at 12:40 PM 11/08/2018
Water Service Inspection - R Passed 12/6/2018 (1:00) 12/6/2018 at 2:30 PM 12/06/2018
Sewer Service Inspection - R Passed 12/13/2018 (11:15) 12/13/2018 at 2:15 PM 12/13/2018
Underslab Plumbing Inspection - Residential Passed 12/17/2018 12/17/2018 at 7:55 AM 12/17/2018
Electrical Service Inspection Passed 4/9/2019 at 10:45 AM 04/09/2019
Gas Piping Inspection - Residential Passed 4/9/2019 at 11:00 AM 04/09/2019
Gas Service Inspection - Residential Passed 4/9/2019 04/09/2019
Misc
Resolved
04/09/2019
1. Fire block heat flue at ceiling where pan does not cover at ceiling 1st fl 2. Fire stop nm electrical penetrations in mudroom north of garage entry door at top plate. 3. Attach bath fan in front guest bath 1st fl. 4. Fire stop nm electrical penetrations right of sliding glass doors 1st fl top and bottom plates. 5. Fire block fir down space from stud spaces at west side of stairs. 6. Install steel support post at east end of basement.
All Rough Inspection - Residential Failed 4/9/2019 4/9/2019 at 11:10 AM 04/09/2019
Misc
Corrective Action Required
04/09/2019
1. Fire block heat flue at ceiling where pan does not cover at ceiling 1st fl 2. Fire stop nm electrical penetrations in mudroom north of garage entry door at top plate. 3. Attach bath fan in front guest bath 1st fl. 4. Fire stop nm electrical penetrations right of sliding glass doors 1st fl top and bottom plates. 5. Fire block fir down space from stud spaces at west side of stairs. 6. Install steel support post at east end of basement. 7. Install security blocking at basement exterior door
All Rough Inspection - Residential Partial 4/12/2019 4/12/2019 04/12/2019
Misc
Corrective Action Required
04/12/2019
-Install column post in basement, east side -Okay to insulate
Piers/Caissons Inspection - Residential Passed 5/15/2019 at 12:55 PM 05/15/2019
Driveway Inspection Partial 5/29/2019 (P.M.) 5/29/2019 05/29/2019
Misc
Informational
05/29/2019
5-29-19 The drive approach is formed up and aggregate is compacted. They will be pouring tomorrow 5-20-19.
Driveway Inspection Passed 07/16/2019
Misc
Informational
05/29/2019
5-29-19 The drive approach is formed up and aggregate is compacted. They will be pouring tomorrow 5-20-19.
Misc
Informational
07/16/2019
7-16-19 The driveway is poured and meets spec.
Erosion Control Inspection Residential Passed 10/31/2019
Occupancy Inspection - Codes Residential Failed 10/31/2019 10/31/2019 at 3:20 PM 10/31/2019
Misc
Corrective Action Required
10/31/2019
NEC 314-20; IRC E3906.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE AT KITCHEN BACKSPLASH.
Misc
Corrective Action Required
10/31/2019
CHECK ALL ELECTRICAL RECEPTACLES TO ENSURE ALL ARE MOUNTED SOLID TO BOX. SEVERAL FOUND TO BE LOOSE SIDE-TO-SIDE. USE YOKE SPACERS OR BOX EXTENDERS WHERE NEEDED.
Misc
Corrective Action Required
10/31/2019
NEC 422.31B CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VOLT-AMPS OR 1/8 HORSEPOWER: IF TO SERVE AS DISCONNECT MUST BE LOCKABLE IF APPLIANCE IS NOT WITHIN SIGHT OF PANELBOARD. INSTALL LOCK-OUT DEVICE ON KITCHEN RANGE CIRCUIT BREAKER.
Misc
Corrective Action Required
10/31/2019
SEAL EXTERIOR LIGHT FIXTURES TO WALL. IRC R703.1: OPENINGS AT EXTERIOR WALLS: SEAL HOLES, PENETRATIONS, ANNULAR SPACES IN EXTERIOR WALL (PIPE, CONDUIT, CABLES…)
Misc
Corrective Action Required
10/31/2019
NEC 350.30; IRC 3802.1: LIQUIDTIGHT FLEXIBLE NON-METALLIC ELECTRICAL WHIP MUST BE SECURED TO STRUCTURE WITHIN 12" OF ENTRY TO A/C DISCONNECT ENCLOSURE. RECOMMEND SHORTENING WHIP TO ABOVE GROUND TO PREVENT DAMAGE.
All Rough Inspection - Residential Passed 11/04/2019
Misc
Resolved
11/04/2019
-Install column post in basement, east side -Okay to insulate
Occupancy Inspection - Codes Residential Full C of O 11/4/2019 11/4/2019 at 9:50 AM 11/04/2019
Misc
Resolved
11/04/2019
NEC 314-20; IRC E3906.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE AT KITCHEN BACKSPLASH.
Misc
Resolved
11/04/2019
CHECK ALL ELECTRICAL RECEPTACLES TO ENSURE ALL ARE MOUNTED SOLID TO BOX. SEVERAL FOUND TO BE LOOSE SIDE-TO-SIDE. USE YOKE SPACERS OR BOX EXTENDERS WHERE NEEDED.
Misc
Resolved
11/04/2019
NEC 422.31B CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VOLT-AMPS OR 1/8 HORSEPOWER: IF TO SERVE AS DISCONNECT MUST BE LOCKABLE IF APPLIANCE IS NOT WITHIN SIGHT OF PANELBOARD. INSTALL LOCK-OUT DEVICE ON KITCHEN RANGE CIRCUIT BREAKER.
Misc
Resolved
11/04/2019
SEAL EXTERIOR LIGHT FIXTURES TO WALL. IRC R703.1: OPENINGS AT EXTERIOR WALLS: SEAL HOLES, PENETRATIONS, ANNULAR SPACES IN EXTERIOR WALL (PIPE, CONDUIT, CABLES…)
Misc
Resolved
11/04/2019
NEC 350.30; IRC 3802.1: LIQUIDTIGHT FLEXIBLE NON-METALLIC ELECTRICAL WHIP MUST BE SECURED TO STRUCTURE WITHIN 12" OF ENTRY TO A/C DISCONNECT ENCLOSURE. RECOMMEND SHORTENING WHIP TO ABOVE GROUND TO PREVENT DAMAGE.
Plot Plan Inspection Passed 11/4/2019 11/04/2019
Documents & Images
Date Uploaded File Type Document Name
11/07/2018 Receipt Receipt for transaction: 2018-007155
11/07/2018 Letter Codes Building Permit
11/08/2018 Letter Inspection Summary
12/06/2018 Letter INSPECTION SUMMARY
12/13/2018 Letter INSPECTION SUMMARY
12/17/2018 Letter INSPECTION SUMMARY
04/09/2019 Letter INSPECTION SUMMARY
04/09/2019 Letter INSPECTION SUMMARY
04/09/2019 Letter INSPECTION SUMMARY
04/09/2019 Letter INSPECTION SUMMARY
04/09/2019 Letter INSPECTION SUMMARY
04/12/2019 Letter INSPECTION SUMMARY
05/15/2019 Letter INSPECTION SUMMARY
05/29/2019 Letter INSPECTION SUMMARY
07/16/2019 Letter INSPECTION SUMMARY
10/31/2019 Letter INSPECTION SUMMARY
11/04/2019 Letter Field Certificate of Occupancy
11/05/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home