Summary
PRRES20171816
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW SINGLE FAMILY COVERED DECK
06/02/2017
06/08/2017
12/03/2017
05/16/2018
Locations
Contacts
CMH PARKS INC, Address:5000 CLAYTON RD  
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 06/09/2017 06/07/2017
Jonathon Hilton
Residential Plan Review Approved 06/09/2017 06/07/2017
Jonathon Hilton
Plot Plan Review Approved 06/06/2017 06/07/2017
Nick Lightner
Spot elevations
Resolved
06/07/2017

Spot elevations and/or drainage flow arrows shall be provided throughout the lot. *SE corner of the lot has a -2% slope toward the house.
As-graded plot plan
Resolved
06/07/2017

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy. *Please provide in a bubble " AS-GRADED PLOT PLAN IS REQUIRED PRIOR TO SODDING"
Residential Plan Review Approved 06/06/2017 06/02/2017
Jonathon Hilton
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,126.65 $1,126.65 Paid 06/08/2017
8331507-Sewer Connection Fee $600.00 $600.00 Paid 06/08/2017
Water Tap Fee $3,310.00 $3,310.00 Paid 06/08/2017
Water Meter Fee $405.36 $405.36 Paid 06/08/2017
Right of Way Permit Fee $75.00 $75.00 Paid 06/08/2017
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 7/13/2017 (11:15) 7/13/2017 07/13/2017
Sewer Service Inspection - R Passed 7/28/2017 (11:30) 7/28/2017 07/28/2017
Erosion Control Inspection Residential Failed 07/28/2017
Misc
Corrective Action Required
07/28/2017
PROTECT THE STOCK IN THE REAR FROM EROSION DISCHARGE. NO FURTHER INSPECTIONS UNTIL COMPLIANT.
Water Service Inspection - R Passed 7/31/2017 7/31/2017 07/31/2017
Erosion Control Inspection Residential Failed 8/3/2017 08/03/2017
Misc
Corrective Action Required
07/28/2017
PROTECT THE STOCK IN THE REAR FROM EROSION DISCHARGE. NO FURTHER INSPECTIONS UNTIL COMPLIANT.
Underslab Plumbing Inspection - Residential Not Ready 8/3/2017 8/3/2017 08/03/2017
Misc
Corrective Action Required
08/03/2017
INSPECTION DENIED - EROSION CONTROL
Erosion Control Inspection Residential Failed 8/7/2017 08/07/2017
Misc
Corrective Action Required
08/03/2017
PROTECT THE STOCK IN THE REAR FROM EROSION DISCHARGE. *Discussed with Builder, on-site, what needs to be done; will have it completed by 8/8/17
Underslab Plumbing Inspection - Residential Passed 8/7/2017 8/7/2017 08/07/2017
Misc
Resolved
08/07/2017
INSPECTION DENIED - EROSION CONTROL
Erosion Control Inspection Residential Partial 8/9/2017 08/09/2017
Misc
Partial Correction
08/09/2017
Erosion control compliant. Maintain.
Erosion Control Inspection Residential Partial 10/16/2017 at 11:37 AM 10/16/2017
Misc
Partial Correction
08/09/2017
Maintain rear property erosion control
All Rough Inspection - Residential Failed 10/16/2017 10/16/2017 at 10:15 AM 10/16/2017
Misc
Corrective Action Required
10/16/2017
1. Truss hanger over 1st floor ne bedroom. 2. Master bedroom rear wall, not framed per detail S 4.1. 3. Flash plumbing vent master bath. 4. Security block walkout door. 5. Missing Double floor joist basement above far north post. See floor joist layout. 6. Firestop above foyer closet and around fireblocking for garage fur out. Okay to insulate.
Electrical Service Inspection Passed 10/16/2017 10/16/2017 at 11:21 AM 10/16/2017
Gas Piping Inspection - Residential Passed 10/16/2017 10/16/2017 at 11:11 AM 10/16/2017
Gas Service Inspection - Residential Passed 10/16/2017 10/16/2017 at 11:01 AM 10/16/2017
All Rough Inspection - Residential Failed 10/20/2017 10/20/2017 at 10:15 AM 10/20/2017
Misc
Corrective Action Required
10/16/2017
3. Flash plumbing vent master bath. 4. Security block walkout door. Okay to insulate.
All Rough Inspection - Residential Passed 10/24/2017 10/24/2017 at 8:45 AM 10/24/2017
Misc
Resolved
10/24/2017
3. Flash plumbing vent master bath. 4. Security block walkout door. Okay to insulate.
Driveway Inspection Partial 11/16/2017 11/16/2017 at 1:45 PM 11/16/2017
Informational
11/16/2017
John DiMauro 11/16/2017 3:38 PM Forms are up and rock is compacted. The curb has a significant crack in it and the concrete crew is going to replace the section of damaged curb.
Driveway Inspection Partial 11/27/2017 at 8:35 AM 11/27/2017
Informational
11/27/2017
John DiMauro 11/27/2017 8:40 AM There is still a section of the driveway and the curb that needs to be poured.
Occupancy Inspection - Codes Residential Not Ready 1/22/2018 1/22/2018 at 9:40 AM 01/22/2018
Misc
Corrective Action Required
01/22/2018
-CLEAN STREET -REAR EROSION CONROL NOT COMPLIANT INSPECTION DENIED
Occupancy Inspection - Codes Residential Failed 1/25/2018 1/25/2018 at 12:55 PM 01/25/2018
Misc
Corrective Action Required
01/22/2018
-COMPLETE DECK GUARDS, STAIRS -SECURITY SCREWS 1ST FLOOR DECK DOOR -FINAL GRADE, SOD, SPLASHBLOCKS, ESTABLISH VEGETATION ADJOINING LOTS
Occupancy Inspection - Codes Residential Not Ready 1/29/2018 1/29/2018 at 1:55 PM 01/29/2018
Misc
Corrective Action Required
01/25/2018
-COMPLETE DECK GUARDS, STAIRS -SECURITY SCREWS 1ST FLOOR DECK DOOR -FINAL GRADE, SOD, SPLASHBLOCKS, ESTABLISH VEGETATION ADJOINING LOTS
Occupancy Inspection - Codes Residential Not Ready 1/30/2018 1/30/2018 at 9:30 AM 01/30/2018
Misc
Corrective Action Required
01/29/2018
-COMPLETE DECK GUARDS, STAIRS -SECURITY SCREWS 1ST FLOOR DECK DOOR -FINAL GRADE, SOD, SPLASHBLOCKS, ESTABLISH VEGETATION ADJOINING LOTS
Occupancy Inspection - Codes Residential Temporary C of O 1/31/2018 1/31/2018 at 11:15 AM 01/31/2018
Misc
Corrective Action Required
01/30/2018
-FINAL GRADE, SOD, SPLASHBLOCKS, ESTABLISH VEGETATION ADJOINING LOTS
Occupancy Inspection - Codes Residential Full C of O 5/16/2018 5/16/2018 at 9:20 AM 05/16/2018
Misc
Corrective Action Required
01/31/2018
-FINAL GRADE, SOD, SPLASHBLOCKS, ESTABLISH VEGETATION ADJOINING LOTS
Documents & Images
Date Uploaded File Type Document Name
06/06/2017 Letter Codes Residential Plan Review
06/08/2017 Receipt Receipt for transaction: 2017-003635
06/08/2017 Letter Codes Building Permit
06/09/2017 Plot Plan DOC060917-007
06/15/2017 Engineer Report/Study DOC061517-012
07/13/2017 Letter Inspection Summary
07/28/2017 Letter Inspection Summary
07/31/2017 Letter Inspection Summary
08/03/2017 Letter Inspection Summary
08/07/2017 Letter Inspection Summary
08/09/2017 Letter Inspection Summary
10/16/2017 Letter Inspection Summary
10/20/2017 Letter Inspection Summary
10/24/2017 Letter Inspection Summary
11/01/2017 Engineer Report/Study DOC110117-007
11/16/2017 Letter DE-Daily Inspection Summary
11/27/2017 Letter DE-Daily Inspection Summary
01/22/2018 Letter Inspection Summary
01/25/2018 Letter Inspection Summary
01/30/2018 Letter Inspection Summary
01/31/2018 Letter Codes Temporary Certificate of Occupancy
05/16/2018 Letter Field Certificate of Occupancy
05/18/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home