Summary
PRRES20151852
Building Permit - Residential
Certificate of Occupancy
JOHN KNOX VILLAGE
NEW 3 OR 4 FAMILY
3 PLEX - COVERED DECKS - UNFINISHED BASEMENTS *FLOOR TRUSSES
08/12/2015
09/01/2015
02/08/2016
06/29/2016
Locations
Contacts
LARRY HARKRADER CONSTRUCTION, Address:401 NW MURRAY RD, Phone:(816) 607-7191  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 08/21/2015 08/27/2015
Mike Weisenborn
Plot Plan Review (P&D) Approved 08/26/2015
Ron Seyl
Plot Plan Review Rejected 08/19/2015
James Fletchall
Residential Plan Review Approved 08/14/2015 08/12/2015
Tara Mitchell
Residential Plan Review Rejected 08/14/2015 08/12/2015
Tara Mitchell
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New 3 or 4 Family $1,770.14 $1,770.14 Paid 09/01/2015
8331507-Sewer Connection Fee $1,080.00 $1,080.00 Paid 09/01/2015
Outstanding Fees Amount Paid Owing Date Paid


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Partial 9/10/2015 (11:30) 9/10/2015 at 12:00 AM 09/10/2015
Misc
Partial Correction
09/10/2015
OK TO POUR WHEN READY WALL FOOTINGS & ISOLATED FOOTINGS AT UNIT "A" INCLUDING GARAGE. UFER GROUNDING JUMPER IS IN PLACE AT UNIT "A" SOUTH END. SOILS ENGINEER AGREED OK TO POUR AFTER SOFT MATERIAL REMOVED.
Footing Inspection - Residential Passed 9/15/2015 (1:00) 9/15/2015 at 12:00 AM 09/15/2015
Misc
Resolved
09/15/2015
OK TO POUR WHEN READY WALL FOOTINGS & ISOLATED FOOTINGS AT UNIT "A" INCLUDING GARAGE. UFER GROUNDING JUMPER IS IN PLACE AT UNIT "A" SOUTH END. SOILS ENGINEER AGREED OK TO POUR AFTER SOFT MATERIAL REMOVED.
Sewer Service Inspection - R Passed 10/2/2015 (1:00) 10/2/2015 at 12:00 AM 10/02/2015
Underslab Plumbing Inspection - Residential Passed 10/5/2015 (8:00 to 5:00) 10/2/2015 at 12:00 AM 10/02/2015
Water Service Inspection - R Passed 10/5/2015 (2:45) 10/5/2015 at 12:00 AM 10/05/2015
All Rough Inspection - Residential Partial 10/8/2015 at 12:00 AM 10/08/2015
Misc
Partial Correction
10/08/2015
INSPECTED SILL PLATE ANCHOR BOLTS IN ADVANCE OF THEIR BEING COVERED BY FRAMING. STRESSED TO CLINT HARKRADER TO ENSURE ALL NUTS ARE TORQUED BEFORE COVERING.
Underslab Plumbing Inspection - Residential Passed 12/2/2015 12/2/2015 at 12:00 AM 12/02/2015
Gas Piping Inspection - Residential Partial 12/9/2015 12/9/2015 at 12:00 AM 12/09/2015
Misc
Partial Correction
12/09/2015
GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. + VISUAL INSPECTION OK AT: UNIT "A";
All Rough Inspection - Residential Partial 12/9/2015 12/9/2015 at 12:00 AM 12/09/2015
Misc
Resolved
12/09/2015
INSPECTED SILL PLATE ANCHOR BOLTS IN ADVANCE OF THEIR BEING COVERED BY FRAMING. STRESSED TO CLINT HARKRADER TO ENSURE ALL NUTS ARE TORQUED BEFORE COVERING.
Misc
Partial Correction
12/09/2015
ROUGH-IN OF FRAMING; IN-WALL + ABOVE-CEILING SYSTEMS: OK TO COVER WHEN READY AT: UNIT "A" EXCEPT BASEMENT* AFTER ON ELECTRICAL SHIELD PLATE IS INSTALLED AND ONE DAMAGED ELECTRICAL BOX IS REPLACED -- BOTH POINTED-OUT; *TGI DRAWING REQUIRED FOR FLOOR JOISTS; SUPPORT PEX AT 32" MAX INTERVALS
Underslab Plumbing Inspection - Residential Partial 12/23/2015 12/23/2015 12/23/2015
Misc
Partial Correction
12/23/2015
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: GARAGE FLOOR DRAIN @ UNIT C (NORTH); GARAGE FLOOR DRAIN @ UNIT B (CENTER); NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Electrical Service Inspection Partial 1/5/2016 (8:00 to 5:00) 1/5/2016 01/05/2016
Misc
Partial Correction
01/05/2016
ELECTRICAL SERVICE RELEASED CONTINGENT ON COMPLETION OF BONDING OF SERVICE EQUIPMENT.
Underslab Plumbing Inspection - Residential Passed 1/6/2016 1/6/2016 01/06/2016
Misc
Resolved
01/06/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT: GARAGE FLOOR DRAIN @ UNIT C (NORTH); GARAGE FLOOR DRAIN @ UNIT B (CENTER); NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Gas Piping Inspection - Residential Partial 1/7/2016 1/7/2016 01/07/2016
Misc
Partial Correction
12/09/2015
GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. + VISUAL INSPECTION OK AT: UNIT "A" (NORTH); UNIT "B" (CENTER);
All Rough Inspection - Residential Partial 1/7/2016 (8:00 to 5:00) 1/7/2016 01/07/2016
Misc
Partial Correction
12/09/2015
OK TO COVER WHEN READY AT: UNIT "A" (NORTH); UNIT "B" (CENTER); *TGI DRAWING REQUIRED FOR FLOOR JOISTS; SUPPORT PEX AT 32" MAX INTERVALS
All Rough Inspection - Residential Failed 1/29/2016 1/29/2016 01/29/2016
Misc
Partial Correction
01/07/2016
OK TO COVER WHEN READY AT: UNIT "C" (NORTH); UNIT "B" (CENTER); *TGI DRAWING REQUIRED FOR FLOOR JOISTS; SUPPORT PEX AT 32" MAX INTERVALS
Misc
Corrective Action Required
01/29/2016
UNIT "A" (SOUTH): 1) COMPLETE NAILING OF STUD SHOES -- SEE KITCHEN, LAUNDRY,.. 2) INTERNAL BEND DIAMETER OF GAS CONNECTOR UNDER FIREPLACE IS SMALLER THAN MINIMUM 1-1/2" ALLOWED BY MANUFACTURER (SEE YELLOW TAG THEREON). 3) IRC R407.3 POST BASE PLATES NOT SECURED TO BASEMENT SLAB 4) TGI DRAWING REQUIRED FOR FLOOR JOISTS; CHECK TO ENSURE BLOCKING IF REQUIRED
All Rough Inspection - Residential Partial 2/2/2016 2/2/2016 02/02/2016
Misc
Partial Correction
01/29/2016
OK TO COVER WHEN READY AT: UNIT "C" (NORTH); UNIT "B" (CENTER); UNIT "A" (SOUTH)
Misc
Partial Correction
02/02/2016
UNIT "A" (SOUTH): 2) INTERNAL BEND DIAMETER OF GAS CONNECTOR UNDER FIREPLACE IS SMALLER THAN MINIMUM 1-1/2" ALLOWED BY MANUFACTURER (SEE YELLOW TAG THEREON). 3) IRC R407.3 POST BASE PLATES NOT SECURED TO BASEMENT SLAB
Gas Piping Inspection - Residential Passed 2/2/2016 2/2/2016 02/02/2016
Misc
Resolved
02/02/2016
GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. + VISUAL INSPECTION OK AT: UNIT "C" (NORTH); UNIT "B" (CENTER); UNIT "A" (SOUTH)
Occupancy Inspection - Codes Residential Temporary C of O 4/14/2016 (8:00 to 5:00) 4/14/2016 04/14/2016
Misc
Corrective Action Required
04/14/2016
FINISH LANDSCAPING TO BE COMPLETED + SPLASHBLOCKS.
Misc
Corrective Action Required
04/14/2016
SEAL ALL PENETRATIONS OF EXTERIOR WALLS.
Occupancy Inspection - Codes Residential Temporary C of O 5/10/2016 05/10/2016
Misc
Corrective Action Required
04/14/2016
FINISH LANDSCAPING TO BE COMPLETED + SPLASHBLOCKS.
Misc
Corrective Action Required
04/14/2016
SEAL ALL PENETRATIONS OF EXTERIOR WALLS.
Occupancy Inspection - Codes Residential Full C of O 6/29/2016 6/29/2016 06/29/2016
Misc
Resolved
06/29/2016
FINISH LANDSCAPING TO BE COMPLETED + SPLASHBLOCKS.
Misc
Resolved
06/29/2016
SEAL ALL PENETRATIONS OF EXTERIOR WALLS.
Documents & Images
Date Uploaded File Type Document Name
09/01/2015 Letter Codes Building Permit
09/01/2015 Receipt Receipt for transaction: 2015-005177
09/10/2015 Letter Inspection Summary
09/15/2015 Letter Inspection Summary
10/02/2015 Letter Inspection Summary
10/05/2015 Letter Inspection Summary
12/02/2015 Letter Inspection Summary
12/09/2015 Letter Inspection Summary
12/23/2015 Letter Inspection Summary
01/05/2016 Letter Inspection Summary
01/06/2016 Letter Inspection Summary
01/07/2016 Letter Inspection Summary
01/29/2016 Letter Inspection Summary
02/02/2016 Letter Inspection Summary
04/14/2016 Letter Codes Temporary Certificate of Occupancy
05/10/2016 Letter Codes Temporary Certificate of Occupancy
06/29/2016 Letter Field Certificate of Occupancy
06/30/2016 Letter Codes Final Certificate of Occupancy
06/30/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home