Review Type |
Outcome |
Est. Completion Date |
Completed |
Sprinkler Plan Review
|
Released for Construction
|
|
09/20/2016
|
|
Joe Dir
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
FIELD AND ACCEPTANCE TESTING OF THE SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
|
|
|
Final Development Plan Review
|
Approved
|
03/16/2016
|
08/26/2016
|
|
Chris Hughey
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
08/22/2016
|
|
Joe Dir
|
|
Misc
Corrective Action Required
PROVIDE MANUFACTERS SPECS ON ALL DEVICES TO BE INSTALLED EMAIL TO joe.dir@cityofls.net
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
ACCEPTANCE TESTING OF THE SYSTEM WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE TESTING CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
|
|
Misc
Corrective Action Required
PLANS SHOW PROJECT ADDRESS AS 1220 SE BROADWAY. CORREDT PROJECT ADDRESS IS 1440 SE BROADWAY (INFORMATION PURPOSES)
|
|
|
Building Plan Review
|
Approved with Conditions
|
06/20/2016
|
07/14/2016
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
|
|
Engineered truss package
Copies of the engineered metal building package were not provided at the time of permit application.
Action required: Provide engineered building package or request deferral.
5/19/16 - comment not addressed
6/16/16 - defer as requested
7/14/16 - received
|
|
Plan Submittal 2012 Codes
All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit.
Action required: Update code references on sheet A-1 to reflect correct year of ICC/ANSI A117.1
5/19/16 - plan unchanged
6/16/16 - plan not submitted. changed by hand because I gave up trying
|
|
Misc
2012 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions)
Action required: Specify compliant materials at Electrical Service Room and Fire Sprinkler Room.
5/19/16 - Plans not revised.
6/16/16 - plans revised
|
|
Plumb - Minimum number of fixtures 403.1
2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Action required: Provide mop sink.
5/19/16 - unable to locate on plans
|
|
Misc
Additional information required to complete review.
Provide the following information:
-
-
- Clarify size of water meter. 1" shown on civil plans, while supply into building is 2"
5/19/16 - comment not addressed
6/16/16 - comment not addressed on civil drawings
7/14/16 - updated to 1.5" displacement to achieve min 48gpm
-
- Specify/clarify plumbing fixture ED-1 in shop area.
5/19/16 - comment not addressed
6/16/16 - unable to find any reference to what ED-1 is on drawings. Please clarify.
7/14/16 - clarified in letter to be floor drains
|
|
|
Licensed Contractors
|
Approved
|
06/13/2016
|
06/16/2016
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
06/20/2016
|
06/14/2016
|
|
Joe Dir
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 901.2 Construction documents.
The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required: Provide sprinkler plans for review.
|
|
Alarms connected to automatic sprinkler system
Corrective Action Required
2012 IFC 907.1.2 Fire alarm shop drawings.
Shop drawings for fire alarm systems shall be submitted for review and approval prior to system installation, and shall include, but not be limited to, all of the following:
1. A floor plan that indicates the use of all rooms.
2. Locations of alarm-initiating devices.
3. Locations of alarm notification appliances, including candela ratings for visible alarm notification appliances.
4. Location of fire alarm control unit, transponders and notification power supplies.
5. Annunciators.
6. Power connection.
7. Battery calculations.
8. Conductor type and sizes.
9. Voltage drop calculations.
10. Manufacturers’ data sheets indicating model numbers and listing information for equipment, devices and materials.
11.Details of ceiling height and construction.
12. The interface of fire safety control functions.
13. Classification of the supervising station.
Action required: Provide shop drawings for review and approval.
|
|
Knox box required
Corrective Action Required
2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Action required: A Knox box is required to be installed 6'AFF, over the FDC.The box may be ordered at knoxbox.com.
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
901.5.1 Occupancy.
It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
|
|
Misc
Corrective Action Required
2012 IFC 509.1 Identification.
Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location shall be constructed of durable materials, permanently installed and readily visible.
Action Required: Label sprinkler and mechanical rooms.
|
|
Hazardous material identification
Corrective Action Required
2012 IFC 5001.5.2 Hazardous Materials Inventory Statement (HMIS).
Where required by the fire code official , an application for a permit shall include an HMIS, such as Superfund Amendments and Reauthorization Act of 1986 (SARA) Title III, Tier II Report or other approved statement. The HMIS shall include the following information:
1. Product name.
2. Component.
3. Chemical Abstract Service (CAS) number.
4. Location where stored or used.
5. Container size.
6. Hazard classification.
7. Amount in storage.
8. Amount in use-closed systems.
9. Amount in use-open systems.
Action required: Provide an inventory statement of materials stored and used in the facility.
|
|
Misc
Corrective Action Required
B] 1008.1.9 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
NO KEY CYLINDER LOCKS ON THE EGRESS SIDE OF ANY MARKED EXIT.
|
|
Misc
Corrective Action Required
B] 1008.1.9.8 Access-controlled egress doors.
The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria:
1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor.
2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors.
3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds.
4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset.
5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset.
6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public.
[B] 1008.1.9.9 Electromagnetically locked egress doors.
Doors in the means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2, and doors to tenant spaces in Group A, B, E, M, R-1 or R-2, shall be permitted to be electromagnetically locked if equipped with listed hardware that incorporates a built-in switch and meet the requirements below:
1. The listed hardware that is affixed to the door leaf has an obvious method of operation that is readily operated under all lighting conditions.
2. The listed hardware is capable of being operated with one hand.
3. Operation of the listed hardware directly interrupts the power to the electromagnetic lock and unlocks the door immediately.
4. Loss of power to the listed hardware automatically unlocks the door.
5. Where panic or fire exit hardware is required by Section 1008.1.10, operation of the listed panic or fire exit hardware also releases the electromagnetic lock.
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 1440 ON THE BUILDING READABLE FROM THE ADDRESSED ROADWAY (BROADWAY)
|
|
|
Building Plan Review
|
Rejected
|
05/19/2016
|
05/19/2016
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered metal building package were not provided at the time of permit application.
Action required: Provide engineered building package or request deferral.
5/19/16 - comment not addressed
|
|
Plan Submittal 2012 Codes
Corrective Action Required
All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit.
Action required: Update code references on sheet A-1 to reflect correct year of ICC/ANSI A117.1
5/19/16 - plan unchanged
|
|
Misc
Corrective Action Required
2012 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions)
Action required: Specify compliant materials at Electrical Service Room and Fire Sprinkler Room.
5/19/16 - Plans not revised.
|
|
Misc
Screening of ground mounted equipment
Unified Development Ordinance Article 7, Section 7.180.F
Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened.
Action required: Vinyl fencing not permitted as screening material.
5/19/16 - approved per Jennifer Thompson
|
|
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Action required: Provide mop sink.
5/19/16 - unable to locate on plans
|
|
Accessibility - Turning space 603.2.1
ICC A117.1-2009 Section 603.2.1 Turning Space. A turning space complying with Section 304 shall be provided within the room. The required turning space shall not be provided within a toilet compartment.
603.2.2 Door Swing. Doors shall not swing into the clear floor space or clearance for any fixture. (see code for exceptions)
Action required: At office area women's restroom, modify door swing or alter design to provide turning space that is not impeded by door swing.
|
|
Accessibility - Water closet location 604.2
ICC A117.1-2009 604.2 – Location. The water closet shall be located with a wall or partition to the rear and to one side. The centerline of the water closet shall be 16 inches minimum and 18 inches maximum from the side wall or partition. Water closets located in ambulatory accessible compartments specified in Section 604.10 shall have the centerline of the water closet 17 inches minimum and 19 inches maximum from the side wall or partition.
Action required: Relocate toilets to comply.
|
|
Misc
2011 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 1200 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates or other devices that are normally latched but open under simple pressure.
Action required: Door at Electric service room to swing outward and be equipped with panic hardware.
|
|
Misc
2012 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods:
1. Extending below the frost line of the locality;
2. Constructing in accordance with ASCE 32; or
3. Erecting on solid rock.
(see code section for exceptions)
Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character.
Action required: Footings and perimeter column pads must extend to minimum 36" frost depth. Modify General Foundation Note #2 on sheet S1, Footing Schedule on sheet S2, and Details/Sections on sheet S3.
|
|
Misc
Corrective Action Required
Additional information required to complete review.
Provide the following information:
- Clarify construction of ceiling at Employee Information/Punch area and similar locations out of office area but under mezzanine.
5/19/16 - mechanical plans not updated
-
- Clarify size of water meter. 1" shown on civil plans, while supply into building is 2"
5/19/16 - comment not addressed
-
- Specify/clarify plumbing fixture ED-1 in shop area.
5/19/16 - comment not addressed
|
|
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible.
ICC A117.1-2009 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor.
Action required: Specify counter height in break room to demonstrate compliance.
|
|
Misc
2012 IPC 904.1 Required vent extension.
The vent system serving each building drain shall have not less than one vent pipe that extends to the outdoors.
Action required: Specify size, location, etc. of vents through roof.
|
|
Plumb - Cleanouts - Building sewer 708.3.2
2012 IPC 708.3 Where required. Cleanouts shall be located in accordance with Sections 708.3.1 through 708.3.6.
2012 IPC 708.3.4 Base of stack. A cleanout shall be provided at the base of each waste or soil stack.
Actin required: Modify plans and risers to demonstrate compliance.
|
|
Misc
2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space.
Action required: Complete outside air information in RTU schedule.
|
|
Mech - Duct detectors - Return air systems 606.2.1
2012 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances.
Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4.
Action required: Provide smoke detectors at all return air systems that exceed 2,000 CFM.
|
|
|
Licensed Contractors
|
Approved
|
05/12/2016
|
05/19/2016
|
|
Joe Frogge
|
|
LC - MEP Subs
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
05/19/2016
|
05/13/2016
|
|
Joe Dir
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 901.2 Construction documents.
The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required: Provide sprinkler plans for review.
|
|
Alarms connected to automatic sprinkler system
Corrective Action Required
2012 IFC 907.1.2 Fire alarm shop drawings.
Shop drawings for fire alarm systems shall be submitted for review and approval prior to system installation, and shall include, but not be limited to, all of the following:
1. A floor plan that indicates the use of all rooms.
2. Locations of alarm-initiating devices.
3. Locations of alarm notification appliances, including candela ratings for visible alarm notification appliances.
4. Location of fire alarm control unit, transponders and notification power supplies.
5. Annunciators.
6. Power connection.
7. Battery calculations.
8. Conductor type and sizes.
9. Voltage drop calculations.
10. Manufacturers’ data sheets indicating model numbers and listing information for equipment, devices and materials.
11.Details of ceiling height and construction.
12. The interface of fire safety control functions.
13. Classification of the supervising station.
Action required: Provide shop drawings for review and approval.
|
|
Knox box required
Corrective Action Required
2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Action required: A Knox box is required to be installed 6'AFF, over the FDC.The box may be ordered at knoxbox.com.
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
901.5.1 Occupancy.
It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
|
|
Misc
Corrective Action Required
2012 IFC 509.1 Identification.
Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location shall be constructed of durable materials, permanently installed and readily visible.
Action Required: Label sprinkler and mechanical rooms.
|
|
Hazardous material identification
Corrective Action Required
2012 IFC 5001.5.2 Hazardous Materials Inventory Statement (HMIS).
Where required by the fire code official , an application for a permit shall include an HMIS, such as Superfund Amendments and Reauthorization Act of 1986 (SARA) Title III, Tier II Report or other approved statement. The HMIS shall include the following information:
1. Product name.
2. Component.
3. Chemical Abstract Service (CAS) number.
4. Location where stored or used.
5. Container size.
6. Hazard classification.
7. Amount in storage.
8. Amount in use-closed systems.
9. Amount in use-open systems.
Action required: Provide an inventory statement of materials stored and used in the facility.
|
|
Misc
Corrective Action Required
B] 1008.1.9 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
NO KEY CYLINDER LOCKS ON THE EGRESS SIDE OF ANY MARKED EXIT.
|
|
Misc
Corrective Action Required
B] 1008.1.9.8 Access-controlled egress doors.
The entrance doors in a means of egress in buildings with an occupancy in Groups A, B, E, I-2, M, R-1 or R-2, and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 or R-2, are permitted to be equipped with an approved entrance and egress access control system, listed in accordance with UL 294, which shall be installed in accordance with all of the following criteria:
1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor.
2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors.
3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds.
4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset.
5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset.
6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public.
[B] 1008.1.9.9 Electromagnetically locked egress doors.
Doors in the means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2, and doors to tenant spaces in Group A, B, E, M, R-1 or R-2, shall be permitted to be electromagnetically locked if equipped with listed hardware that incorporates a built-in switch and meet the requirements below:
1. The listed hardware that is affixed to the door leaf has an obvious method of operation that is readily operated under all lighting conditions.
2. The listed hardware is capable of being operated with one hand.
3. Operation of the listed hardware directly interrupts the power to the electromagnetic lock and unlocks the door immediately.
4. Loss of power to the listed hardware automatically unlocks the door.
5. Where panic or fire exit hardware is required by Section 1008.1.10, operation of the listed panic or fire exit hardware also releases the electromagnetic lock.
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
POST THE NUMERIC ADDRESS OF 1440 ON THE BUILDING READABLE FROM THE ADDRESSED ROADWAY (BROADWAY)
|
|
|
Special Inspections Review
|
Approved
|
|
04/12/2016
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Rejected
|
03/16/2016
|
03/21/2016
|
|
Jim Eden
|
|
Misc
Corrective Action Required
A hydrant has been provided that meets the 300 foot rule, but the FDC is not shown to determine if the 100 foot rule has been met. It is recommended that the new hydrant be moved closer to the south end of the building to keep it accessible, or provide a NO PARKING FIRE LANE sign.
|
|
Construction documents for fire alarm systems
Corrective Action Required
2012 901.2 Construction documents.
The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required: Provide sprinkler plans for review.
|
|
Alarms connected to automatic sprinkler system
Corrective Action Required
2012 IFC 907.1.2 Fire alarm shop drawings.
Shop drawings for fire alarm systems shall be submitted for review and approval prior to system installation, and shall include, but not be limited to, all of the following:
1. A floor plan that indicates the use of all rooms.
2. Locations of alarm-initiating devices.
3. Locations of alarm notification appliances, including candela ratings for visible alarm notification appliances.
4. Location of fire alarm control unit, transponders and notification power supplies.
5. Annunciators.
6. Power connection.
7. Battery calculations.
8. Conductor type and sizes.
9. Voltage drop calculations.
10. Manufacturers’ data sheets indicating model numbers and listing information for equipment, devices and materials.
11.Details of ceiling height and construction.
12. The interface of fire safety control functions.
13. Classification of the supervising station.
Action required: Provide shop drawings for review and approval.
|
|
Knox box required
Corrective Action Required
2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Action required: A Knox box is required to be installed 6'AFF, over the FDC.The box may be ordered at knoxbox.com.
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
901.5.1 Occupancy.
It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
|
|
Misc
Corrective Action Required
The fire main comes into the building on the east side, but the sprinkler room is shown on the west side. The plumping plan shows the main comig in from the west side of the building. It is not recommended to run a main under the building.
Action required: Clarify the location of the sprinkler riser/room, and the fire main.
|
|
Misc
Corrective Action Required
The location of the HVAC units are shown as ground mounted units, listed as roof top units, and not shown on the civil drawings.
Action required: Please clarify.
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required: Show the locations of the fire extinguishers.
|
|
Misc
Corrective Action Required
Indicate the use of the mezzanine.
|
|
Misc
Corrective Action Required
The Door and Frame schedule calls out Door 16 as being a 2'0" door. It also does not indicate type of hardware sets going on the doors.
Action required: Make corrections.
|
|
Misc
Corrective Action Required
2012 IFC 509.1 Identification.
Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location shall be constructed of durable materials, permanently installed and readily visible.
Action Required: Label sprinkler and mechanical rooms.
|
|
Hazardous material identification
Corrective Action Required
2012 IFC 5001.5.2 Hazardous Materials Inventory Statement (HMIS).
Where required by the fire code official , an application for a permit shall include an HMIS, such as Superfund Amendments and Reauthorization Act of 1986 (SARA) Title III, Tier II Report or other approved statement. The HMIS shall include the following information:
1. Product name.
2. Component.
3. Chemical Abstract Service (CAS) number.
4. Location where stored or used.
5. Container size.
6. Hazard classification.
7. Amount in storage.
8. Amount in use-closed systems.
9. Amount in use-open systems.
Action required: Provide an inventory statement of materials stored and used in the facility.
|
|
Misc
Corrective Action Required
2012 IFC [B] 1013.2 Where required.
Guards shall be located along open-sided walking surfaces, including mezzanines, equipment platforms, stairs, ramps and landings that are located more than 30 inches (762 mm) measured vertically to the floor or grade below at any point within 36 inches (914 mm) horizontally to the edge of the open side. Guards shall be adequate in strength and attachment in accordance with Section 1607.8 of the International Building Code.
Action required: Provide a guard around the mezzanine.
|
|
|
Building Plan Review
|
Rejected
|
03/16/2016
|
03/10/2016
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
|
|
Misc
2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions)
Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
4/12/16 - received
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered metal building package were not provided at the time of permit application.
Action required: Provide engineered building package or request deferral.
|
|
Plan Submittal 2012 Codes
Corrective Action Required
All plans submitted for review on or after January 1, 2014 shall be designed to the requirements of the 2012 International Building Code, 2012 International Mechanical Code, 2012 International Plumbing Code, 2012 International Fuel Gas Code, 2012 International Fire Code, 2011 National Electric Code and the ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit.
Action required: Update code references on sheet A-1 to reflect correct year of ICC/ANSI A117.1
|
|
Misc
Corrective Action Required
2012 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions)
Action required: Specify compliant materials at Electrical Service Room and Fire Sprinkler Room.
|
|
Misc
Corrective Action Required
Screening of ground mounted equipment
Unified Development Ordinance Article 7, Section 7.180.F
Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened.
Action required: Vinyl fencing not permitted as screening material.
|
|
Plumb - Minimum number of fixtures 403.1
Corrective Action Required
2012 IPC 403.1 – Minimum number of fixtures. Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 403.1. types of occupancies not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Occupancy classification shall be determined in accordance with the International Building Code.
Action required: Provide mop sink.
|
|
Accessibility - Turning space 603.2.1
Corrective Action Required
ICC A117.1-2009 Section 603.2.1 Turning Space. A turning space complying with Section 304 shall be provided within the room. The required turning space shall not be provided within a toilet compartment.
603.2.2 Door Swing. Doors shall not swing into the clear floor space or clearance for any fixture. (see code for exceptions)
Action required: At office area women's restroom, modify door swing or alter design to provide turning space that is not impeded by door swing.
|
|
Accessibility - Water closet location 604.2
Corrective Action Required
ICC A117.1-2009 604.2 – Location. The water closet shall be located with a wall or partition to the rear and to one side. The centerline of the water closet shall be 16 inches minimum and 18 inches maximum from the side wall or partition. Water closets located in ambulatory accessible compartments specified in Section 604.10 shall have the centerline of the water closet 17 inches minimum and 19 inches maximum from the side wall or partition.
Action required: Relocate toilets to comply.
|
|
Misc
Corrective Action Required
2011 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 1200 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic bars, pressure plates or other devices that are normally latched but open under simple pressure.
Action required: Door at Electric service room to swing outward and be equipped with panic hardware.
|
|
Misc
Corrective Action Required
2012 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods:
1. Extending below the frost line of the locality;
2. Constructing in accordance with ASCE 32; or
3. Erecting on solid rock.
(see code section for exceptions)
Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character.
Action required: Footings and perimeter column pads must extend to minimum 36" frost depth. Modify General Foundation Note #2 on sheet S1, Footing Schedule on sheet S2, and Details/Sections on sheet S3.
|
|
Misc
Corrective Action Required
Additional information required to complete review.
Provide the following information:
- Clarify construction of ceiling at Employee Information/Punch area and similar locations out of office area but under mezzanine.
- Clarify construction of walls at mezzanine level. (currently specified to extend above lay-in ceiling that is not there)
- Clarify size of water meter. 1" shown on civil plans, while supply into building is 2"
- Clarify how air returns to AHU-1.
- Specify/clarify plumbing fixture ED-1 in shop area.
|
|
Bldg - Accessibility - Kitchens and kitchenettes 1109.4
Corrective Action Required
2012 IBC 1109.4 – Kitchens and kitchenettes. Where kitchens and kitchenettes are provided in accessible spaces or rooms, they shall be accessible.
ICC A117.1-2009 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor.
Action required: Specify counter height in break room to demonstrate compliance.
|
|
Misc
Corrective Action Required
2012 IPC 904.1 Required vent extension.
The vent system serving each building drain shall have not less than one vent pipe that extends to the outdoors.
Action required: Specify size, location, etc. of vents through roof.
|
|
Plumb - Cleanouts - Building sewer 708.3.2
Corrective Action Required
2012 IPC 708.3 Where required. Cleanouts shall be located in accordance with Sections 708.3.1 through 708.3.6.
2012 IPC 708.3.4 Base of stack. A cleanout shall be provided at the base of each waste or soil stack.
Actin required: Modify plans and risers to demonstrate compliance.
|
|
Misc
Corrective Action Required
2012 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. Ventilation supply systems shall be designed to deliver the required rate of outdoor airflow to the breathing zone within each occupiable space.
Action required: Complete outside air information in RTU schedule.
|
|
Mech - Duct detectors - Return air systems 606.2.1
Corrective Action Required
2012 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances.
Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4.
Action required: Provide smoke detectors at all return air systems that exceed 2,000 CFM.
|
|
|
Licensed Contractors
|
Rejected
|
03/16/2016
|
03/10/2016
|
|
Joe Frogge
|
|
LC - MEP Subs
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|