Permit Application Status

PRCOM20251415


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20251415
Building Permit - Commercial
Issued
NEW MULTI-FAMILY
THE REUNION AT BLACKWELL - BUILDING 32, TYPE C - 4 PLEX PLAN REVIEW COMPLETED UNDER PRCOM20250089
04/09/2025
06/25/2025
Locations
Contacts
Avital Homes, LLC, Address:7500 W 151st Street, #23100, Phone:(816) 914-7128  
RED DOG ELECTRIC SERVICES, Address:PO BOX 1, Phone:(913) 208-4816  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
COLLINS WEBB ARCHITECTURE LLC, Address:307 SW MARKET ST, Unit A, Phone:(816) 249-2270  
Doug Jenson - Avital Homes, Phone:(816) 266-0685  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 04/14/2025 03/31/2025
Mike Weisenborn
Building Plan Review Approved with Conditions 04/14/2025 03/31/2025
Mike Weisenborn
Miscellaneous Correction
Corrective Action Required
04/03/2025

Construction of the attached living unit structure has been released. Sanitary and water service connections cannot be made until substantial completion has been issued for the infrastructure.
Licensed Contractors Approved 04/14/2025 03/31/2025
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
Water Tap Fee $10,595.00 $10,595.00 Paid 05/22/2025
Water Meter Fee $1,066.76 $1,066.76 Paid 05/22/2025
Sanitary Sewer Development Fee $6,101.00 $6,101.00 Paid 05/22/2025
Residential Excise Tax Fee $2,480.64 $2,480.64 Paid 05/22/2025
Valuation Fee for New 3 or 4 Family $4,451.71 $4,451.71 Paid 05/22/2025
Not Ready Inspection Fee $75.00 $75.00 Paid 04/01/2026
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Piers/Caissons Inspection - Commercial Pending
Erosion Control Inspection Pending
Erosion Control Inspection Pending
Footing Inspection - Commercial Pending
Piers/Caissons Inspection - Commercial Pending
Underslab Plumbing Inspection - Commercial Pending
Water Service Inspection Pending
Gas Piping Inspection - Commercial Pending
Gas Service Inspection - Commercial Pending
Above Ceiling Inspection Pending
Rated Assembly Inspection Pending
THE FOLLOWING AREAS ARE APPROVED
Informational
01/20/2026
-1st layer sheet rock at separation walls okay to cover -2nd layer screw pattern in ceiling space and behind dead spaces and vanities -mud and tape in ceiling space and behind furr out walls -screw pattern on gb and separation walls
Occupancy Inspection - Engineering Pending
Occupancy Inspection - Codes Commercial Pending
Miscellaneous Correction
Corrective Action Required
04/01/2026
-fix addresses
Miscellaneous Correction
Corrective Action Required
04/01/2026
-clean the trash out of the garage for access to outlets for inspection
Driveway Inspection Pending 4/2/2026 4/2/2026
Misc
Corrective Action Required
03/26/2026
3/24/26 Tyler S Dw does not have 4" of clean rock. Fail. 3-26-26 Dustin A, Dw has been formed and compacted. Approved to pour. this is for 624-630
Footing Inspection - Commercial Partial 6/13/2025 6/13/2025 06/13/2025
Misc
Informational
06/13/2025
footing-okay to pour
Footing Inspection - Commercial Partial 6/16/2025 6/16/2025 06/16/2025
Misc
Informational
06/13/2025
- footings okay -stem wall okay
Underslab Plumbing Inspection - Commercial Passed 7/11/2025 7/11/2025 07/11/2025
Misc
Informational
07/11/2025
624,626,628,630 ok
Underslab Electrical Inspection - Commercial Passed 7/11/2025 07/11/2025
Miscellaneous Correction
Informational
07/11/2025
624,626,628,630 ok
Footing Inspection - Commercial Passed 7/16/2025 7/16/2025 07/16/2025
Misc
Resolved
07/16/2025
- footings okay -stem wall okay
Sewer Service Inspection Passed 7/23/2025 7/23/2025 07/23/2025
Misc
Informational
07/23/2025
4-23-25 Dustin A, Sewer connection is installed per city specs
Rated Assembly Inspection Failed 9/17/2025 9/17/2025 09/17/2025
Misc
Corrective Action Required
09/17/2025
Exterior nailing inspection only -missing sheathing above W windows -missing nails E front corner area(check throughout)
Rated Assembly Inspection Failed 9/22/2025 9/22/2025 09/22/2025
Misc
Corrective Action Required
09/22/2025
Exterior nailing inspection only -missing nails E front corner area(check throughout)
Rated Assembly Inspection Partial 9/23/2025 9/23/2025 09/23/2025
Misc
Resolved
09/23/2025
Exterior nailing inspection only - okay to cover
Water Service Inspection Passed 10/16/2025
Misc
Informational
10/16/2025
10-16-25 Dustin A, water service is installed to city specs.
All Rough Inspection - Commercial Failed 11/10/2025 11/10/2025 11/10/2025
Misc
Corrective Action Required
11/10/2025
Partial inspection only. Address before reinspection Throughout -provide putty packs at electrical boxes in separation of walls -fire block vertically, horizontally every 10’(ensure no gaps) -truss hangers are not to plans -trusses on site do not match plans. (Installed “A’s” on wrong side) -trusses missing bracing -hold down bolts not tight at htt4
All Rough Inspection - Commercial Failed 11/17/2025 11/17/2025 11/17/2025
Misc
Resolved
11/17/2025
Partial inspection only. Address before reinspection Throughout -provide putty packs at electrical boxes in separation of walls -fire block vertically, horizontally every 10’(ensure no gaps) -truss hangers are not to plans -trusses on site do not match plans. (Installed “A’s” on wrong side) -trusses missing bracing -hold down bolts not tight at htt4
Misc
Corrective Action Required
11/17/2025
Throughout -fire block vertically, horizontally every 10’(ensure no gaps) -truss hangers are not to plans -trusses missing bracing -support bath vents -secure electrical in attic space 624 -but for bolt at htt4 in rear not tight 626 -plumbing running in separation wall for bath vanity -seal top plate penetration laundry 628 -fireblock wall to ceiling space at rear bedroom -remove sheet rock from walls in garage for inspection 630
All Rough Inspection - Commercial Failed 12/5/2025 12/5/2025 12/05/2025
Misc
Corrective Action Required
11/17/2025
Truss layout plans onsite are for type B building -truss hangers are not to plans -trusses missing bracing 624 626 628 -fireblock wall to ceiling space at rear bedroom(see trusses below is all top plate/rear wall) -remove sheet rock from walls in garage for inspection 630
All Rough Inspection - Commercial Passed 12/9/2025 12/9/2025 12/09/2025
Misc
Resolved
12/09/2025
-trusses missing bracing (first truss check B1A , check throughout 624 626 628 -fireblock wall to ceiling space at rear bedroom(see trusses below is all top plate/rear wall) -remove sheet rock from walls in garage for inspection 630
Electrical Service Inspection Failed 12/15/2025 12/15/2025 12/15/2025
Misc
Corrective Action Required
12/15/2025
-no more than one conductor per lug in panel -copper main bonding jumper shall be minimum #4
Electrical Service Inspection Passed 12/18/2025 12/18/2025 12/18/2025
Rated Assembly Inspection Partial 12/29/2025 12/29/2025 12/29/2025
Misc
Informational
12/29/2025
1st layer sheet rock at separation walls okay to cover
Rated Assembly Inspection Partial 1/5/2026 1/5/2026 01/05/2026
Misc
Informational
12/29/2025
-1st layer sheet rock at separation walls okay to cover -2nd layer screw pattern in ceiling space and behind dead spaces and vanities
Rated Assembly Inspection Partial 1/12/2026 1/12/2026 01/12/2026
THE FOLLOWING AREAS ARE APPROVED
Informational
01/05/2026
-1st layer sheet rock at separation walls okay to cover -2nd layer screw pattern in ceiling space and behind dead spaces and vanities -mud and tape in ceiling space and behind furr out walls
Rated Assembly Inspection Partial 1/20/2026 1/20/2026 01/20/2026
THE FOLLOWING AREAS ARE APPROVED
Informational
01/12/2026
-1st layer sheet rock at separation walls okay to cover -2nd layer screw pattern in ceiling space and behind dead spaces and vanities -mud and tape in ceiling space and behind furr out walls -screw pattern on gb and separation walls
Driveway Inspection Failed 3/24/2026 3/24/2026 03/24/2026
Misc
Corrective Action Required
03/24/2026
3/24/26 Tyler S Dw does not have 4" of clean rock. Fail.
Driveway Inspection Partial 3/26/2026 3/26/2026 03/26/2026
Misc
Corrective Action Required
03/24/2026
3/24/26 Tyler S Dw does not have 4" of clean rock. Fail. 3-26-26 Dustin A, Dw has been formed and compacted. Approved to pour. this is for 624-630
Occupancy Inspection - Codes Commercial Not Ready 3/30/2026 03/30/2026
Miscellaneous Correction
Corrective Action Required
03/30/2026
-fix addresses
Occupancy Inspection - Engineering Temporary C of O 3/30/2026 3/30/2026 03/30/2026
Occupancy Inspection - Codes Commercial Failed 4/1/2026 04/01/2026
Miscellaneous Correction
Corrective Action Required
03/30/2026
-fix addresses
Miscellaneous Correction
Corrective Action Required
04/01/2026
-clean the trash out of the garage for access to outlets for inspection
Documents & Images
Date Uploaded File Type Document Name
05/22/2025 Receipt Receipt for transaction:2025-003748
05/22/2025 Letter DS Building Permit
06/13/2025 Letter INSPECTION SUMMARY
06/16/2025 Letter INSPECTION SUMMARY
07/11/2025 Letter INSPECTION SUMMARY
07/11/2025 Letter INSPECTION SUMMARY
07/16/2025 Letter INSPECTION SUMMARY
03/31/2025 Approved Plans Approved plans V1
03/06/2025 Approved Plans Approved plans V2
07/23/2025 Letter INSPECTION SUMMARY
09/17/2025 Letter INSPECTION SUMMARY
09/22/2025 Letter INSPECTION SUMMARY
09/23/2025 Letter INSPECTION SUMMARY
10/16/2025 Letter INSPECTION SUMMARY
10/17/2025 Approved Plans Approved Bldg C Trusses
10/17/2025 Approved Plans Building C truss Seals All C buildngs_STAND REVIEWED
11/05/2025 Approved Plans Approved G111
11/10/2025 Letter INSPECTION SUMMARY
11/12/2025 Approved Plans Approved Truss repair
11/17/2025 Approved Plans Truss repair doc
11/17/2025 Letter INSPECTION SUMMARY
12/05/2025 Letter INSPECTION SUMMARY
12/08/2025 Approved Plans Approved E200 revision
12/09/2025 Letter INSPECTION SUMMARY
12/15/2025 Letter INSPECTION SUMMARY
12/18/2025 Letter INSPECTION SUMMARY
12/29/2025 Letter INSPECTION SUMMARY
01/05/2026 Letter INSPECTION SUMMARY
01/12/2026 Letter INSPECTION SUMMARY
01/20/2026 Approved Plans Approved Individual truss repair
01/20/2026 Letter INSPECTION SUMMARY
02/09/2026 Approved Plans REUNION GRADING PLA
03/24/2026 Letter INSPECTION SUMMARY
03/24/2026 Letter INSPECTION SUMMARY
03/26/2026 Letter INSPECTION SUMMARY
03/30/2026 Letter INSPECTION SUMMARY
03/30/2026 Letter INSPECTION SUMMARY
04/01/2026 Receipt Receipt for transaction:2026-001928
04/01/2026 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home