Permit Application Status

PRCOM20245976


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20245976
Building Permit - Commercial
Issued
CITY OF LEES SUMMIT MISSOURI
ALTERATION COMMERCIAL
INSTALLATION OF HIGH PILE RACK STORAGE SYSTEM
11/14/2024
12/06/2024
Locations
Contacts
North Oak Safety Storage LLC, Address:1120 NW Eagle Ridge Blvd.  
CLAYTON@SAFETYMINISTORAGE.COM  
CITY OF LEES SUMMIT MISSOURI, Address:220 SE GREEN ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 01/15/2025 01/16/2025
Craig Hill
Building Plan Review Approved 11/26/2024 01/08/2025
Joe Frogge
Licensed Contractors Approved 11/28/2024 12/06/2024
Joe Frogge
LC - General Contractor
Resolved
12/06/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Provide the company name of the licensed contractor and the name, email address & phone number for the on-site contact.
Fire Plan Review Approved 12/06/2024 12/03/2024
Craig Hill
Building Plan Review Approved 12/06/2024 11/25/2024
Joe Frogge
Alarm Plan Review Pending
Craig Hill
Sprinkler Plan Review Pending
Craig Hill
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $552.81 $552.81 Paid 12/06/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Inspection - Commercial Pending
Misc
Corrective Action Required
12/23/2024
-Provide two 1/2" anchors per base plate per plan -Install safety pins for all racks -Several installed racks are not shown on the plan
Final Inspection - Commercial Failed 12/23/2024 12/23/2024
Misc
Corrective Action Required
12/23/2024
-Provide two 1/2" anchors per base plate per plan -Install safety pins for all racks -Several installed racks are not shown on the plan
Documents & Images
Date Uploaded File Type Document Name
11/14/2024 Application Form APPLICATION FORM
11/25/2024 Plans 24-1119-12-JOHNSON STORAGE AND MOVING FINALS
11/25/2024 Engineer Report/Study 24-1119-12-JOHNSON STORAGE AND MOVING CALCS
12/06/2024 Approved Plans Approved Racking plans
12/06/2024 Receipt Receipt for transaction:2024-009382
12/06/2024 Letter DS Building Permit
12/23/2024 Letter INSPECTION SUMMARY
01/07/2025 Drawing Updated floor plan
01/08/2025 Updated stamped racking plans
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home