Permit Application Status

PRCOM20244457


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20244457
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW TENANT FINISH
CHICKEN SALAD CHICK - NEW TENANT FINISH FOR DINE IN AND CARRY OUT FOOD
08/22/2024
10/01/2024
12/04/2024
Locations
Contacts
CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
Big Sky Construction Group, LLC., Address:7829 Meadow Chase Drive  
Brandon Pitrone - Big Sky Construction Group, Address:7829 Meadow Chase Drive, Phone:(740) 507-7359  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
QUESTEC MECHANICAL INC, Address:1390 E BOONE INDUSTRIAL DR, SUITE 260, Phone:(573) 875-0260  
Jared Bussey Architect, Address:1604 28th Ave South, Phone:(205) 533-3563  
METALCRAFT INC, Address:5138 MERRIAM DR., Phone:(913) 707-8824  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 10/30/2024 10/29/2024
Craig Hill
Sprinkler Plan Review Released for Construction 10/25/2024 10/23/2024
Craig Hill
Licensed Contractors Approved 09/09/2024 09/17/2024
Joe Frogge
LC - MEP Subs
Resolved
09/17/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 9/9/24 - Not addressed.
Fire Plan Review Approved with Conditions 09/16/2024 09/09/2024
Joe Frogge
Posting of occupant load
Corrective Action Required
09/09/2024

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inspection.
Construction documents for fire alarm systems
Corrective Action Required
09/09/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide plans for review and approval.
Address numbers required
Corrective Action Required
09/09/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide unit numbers on all doors. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
09/09/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler modification plans for review and approval.
Miscellaneous Correction
Corrective Action Required
09/09/2024

5307.3.2 Gas detection system. Where ventilation is not provided in accordance with Section 5307.3.1, a gas detection system shall be provided in rooms or indoor areas and in below-grade outdoor locations with insulated carbon dioxide systems. Carbon dioxide sensors shall be provided within 12 inches (305 mm) of the floor in the area where the gas is expected to accumulate or other approved locations. The system shall be designed as follows: 1. Activates an audible and visible supervisory alarm at a normally attended location upon detection of a carbon dioxide concentration of 5,000 ppm (9000 mg/m3). 2. Activates an audible and visible alarm within the room or immediate area where the system is installed upon detection of a carbon dioxide concentration of 30,000 ppm (54 000 mg/m3). Provide gas detection in the space. Verified at inpection.
Building Plan Review Approved with Conditions 09/16/2024 09/09/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
09/09/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $14,825.25 9/9/24 - Not addressed.
Health Dept Inspection
Corrective Action Required
09/09/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 9/9/24 - Not addressed.
NEC Article 210.8 (B) Other than dwelling units GFCI
Resolved
09/09/2024

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in kitchen will be GFCI protected.
IBC 1109.12.9 Point of sale and service counters - accessibility
Corrective Action Required
09/09/2024

2018 IBC 1109.12.3 Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Comment is informational. To be verified at inspections. 9/9/24 - Not addressed.
Health Department Review Approved 09/05/2024
Joe Frogge
Building Plan Review Rejected 09/04/2024 08/29/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
08/29/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $14,825.25
Health Dept Review
Resolved
09/05/2024

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
08/29/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
NEC Article 210.8 (B) Other than dwelling units GFCI
Corrective Action Required
08/29/2024

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in kitchen will be GFCI protected.
IBC 1109.12.9 Point of sale and service counters - accessibility
Corrective Action Required
08/29/2024

2018 IBC 1109.12.3 Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Comment is informational. To be verified at inspections.
Licensed Contractors Rejected 09/04/2024 08/29/2024
Joe Frogge
LC - MEP Subs
Corrective Action Required
08/29/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 09/04/2024 08/28/2024
Jim Eden
Posting of occupant load
Corrective Action Required
08/27/2024

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inspection.
Construction documents for fire alarm systems
Corrective Action Required
08/27/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide plans for review and approval.
Address numbers required
Corrective Action Required
08/27/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide unit numbers on all doors. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
08/27/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler modification plans for review and approval.
Miscellaneous Correction
Corrective Action Required
08/27/2024

5307.3.2 Gas detection system. Where ventilation is not provided in accordance with Section 5307.3.1, a gas detection system shall be provided in rooms or indoor areas and in below-grade outdoor locations with insulated carbon dioxide systems. Carbon dioxide sensors shall be provided within 12 inches (305 mm) of the floor in the area where the gas is expected to accumulate or other approved locations. The system shall be designed as follows: 1. Activates an audible and visible supervisory alarm at a normally attended location upon detection of a carbon dioxide concentration of 5,000 ppm (9000 mg/m3). 2. Activates an audible and visible alarm within the room or immediate area where the system is installed upon detection of a carbon dioxide concentration of 30,000 ppm (54 000 mg/m3). Provide gas detection in the space. Verified at inpection.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,500.00 $1,500.00 Paid 10/01/2024
7232302-Commercial License Tax Fee $14,825.25 $14,825.25 Paid 11/22/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 12/04/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 10/2/2024 10/02/2024
Misc
Corrective Action Required
10/02/2024
*Inspection denied -Provide City approved stamped plans for inspection
Underslab Electrical Inspection - Commercial Passed 10/03/2024
Underslab Plumbing Inspection - Commercial Passed 10/3/2024 10/3/2024 10/03/2024
Misc
Resolved
10/03/2024
*Inspection denied -Provide City approved stamped plans for inspection
In-wall Inspection Partial 10/14/2024 10/14/2024 10/14/2024
Misc
Corrective Action Required
10/14/2024
-Complete DWV -Secure Pex lines 48" vertical max spacing -Protect all DWV within 1.25" at top track **OK TO 1 SIDE
In-wall Inspection Failed 10/15/2024 10/15/2024 10/15/2024
Misc
Corrective Action Required
10/14/2024
-Secure Pex lines 48" vertical max spacing-not done -Protect all DWV within 1.25"-missing at bottom track 2 locations **OK TO 1 SIDE
In-wall Inspection Passed 10/16/2024 10/16/2024 10/16/2024
Misc
Resolved
10/16/2024
-Secure Pex lines 48" vertical max spacing-not done -Protect all DWV within 1.25"-missing at bottom track 2 locations **OK TO 1 SIDE
Above Ceiling Inspection Partial 10/25/2024 10/25/2024 10/25/2024
Misc
Informational
10/25/2024
-Hard lids approved
Above Ceiling Inspection Failed 11/4/2024 11/4/2024 11/04/2024
Misc
Informational
10/25/2024
-Hard lids approved
Misc
Corrective Action Required
11/04/2024
11/4/24 Not ready. Complete all MEPs
Above Ceiling Inspection Partial 11/7/2024 11/7/2024 11/07/2024
Misc
Informational
11/04/2024
-Hard lids approved
Misc
Corrective Action Required
11/04/2024
-Label firewall per code -Seal penetrations in firewall above cooler *ok for tile in other areas-do not cover inspection items
Above Ceiling Inspection Failed 11/15/2024 11/15/2024 11/15/2024
Misc
Informational
11/07/2024
-Hard lids approved
Misc
Corrective Action Required
11/07/2024
-Seal penetrations in firewall above cooler *ok for tile in other areas-do not cover inspection items
Above Ceiling Inspection Passed 11/19/2024 11/19/2024 11/19/2024
Misc
Resolved
11/19/2024
-Hard lids approved
Misc
Resolved
11/19/2024
-Seal penetrations in firewall above cooler *ok for tile in other areas-do not cover inspection items
Verify Final Inspection (Final) Complete 11/21/2024 11/21/2024
Occupancy Inspection - Codes Commercial Failed 11/25/2024 11/25/2024
Misc
Corrective Action Required
11/25/2024
-No TCO can be granted without a TCO on the shell building -Complete corrections for all other departments -Jackson County Health Department approval required
Occupancy Inspection - Health Failed 11/25/2024 11/25/2024
Sprinkler - Flow Test Passed 11/25/2024
Sprinkler - Hydrostatic Test Passed 11/25/2024
Alarm Test Passed 11/25/2024
Occupancy Inspection - Fire Passed 11/25/2024 11/25/2024
Occupancy Inspection - Health Passed 12/2/2024 12/2/2024 12/02/2024
Occupancy Inspection - Codes Commercial Failed 12/2/2024 12/2/2024 12/02/2024
Misc
Corrective Action Required
11/25/2024
-No TCO can be granted without a TCO on the shell building
Occupancy Inspection - Codes Commercial Full C of O 12/04/2024
Misc
Resolved
12/04/2024
-No TCO can be granted without a TCO on the shell building
Documents & Images
Date Uploaded File Type Document Name
08/22/2024 Application Form APPLICATION
08/22/2024 Plans 60-24 CSC Lees Summit CONSTRUCTION DOCUMENTS 8-19-24
08/27/2024 Letter License Tax Bill
08/29/2024 Letter DS P/R Corrections Document
09/05/2024 Letter Jackson Cty Health approval
09/08/2024 Drawing E200-Power Plan
09/09/2024 Approved Plans Approved construction plans
10/01/2024 Receipt Receipt for transaction:2024-008049
10/02/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter DS Building Permit
10/03/2024 Letter INSPECTION SUMMARY
10/11/2024 19320 Chicken Salad Chick FP Submittal
10/14/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/16/2024 Fire Alarm Submittal_1020 NW Pryor Road Suite A_Chicken Salad Chick (1)
10/16/2024 Letter INSPECTION SUMMARY
10/23/2024 Letter Fire (Sprinkler) Plan Review
10/25/2024 Letter INSPECTION SUMMARY
10/29/2024 Fire Alarm Submittal_1020 NW Pryor Road Suite A_Chicken Salad Chick (1) RFC
10/29/2024 Letter Fire (Alarm) Plan Review Notice
11/04/2024 Letter INSPECTION SUMMARY
11/07/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/19/2024 Letter INSPECTION SUMMARY
11/22/2024 Receipt Receipt for transaction:2024-009111
11/25/2024 Letter INSPECTION SUMMARY
11/25/2024 Letter INSPECTION SUMMARY
11/26/2024 Jackson County Health inspection
12/02/2024 Letter INSPECTION SUMMARY
12/02/2024 Letter INSPECTION SUMMARY
12/04/2024 Letter Codes Final Certificate of Occupancy
12/04/2024 Letter Field Certificate of Occupancy
12/04/2024 Receipt Receipt for transaction:2024-009301
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home