Permit Application Status

PRCOM20242672


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20242672
Building Permit - Commercial
Certificate of Occupancy
NEW TENANT FINISH
MAGIC NOODLE 2 - TENANT FINISH FOR RESTAURANT
05/28/2024
08/14/2024
01/07/2025
01/29/2025
Locations
Contacts
STEPHEN MASLAN & COMPANY, Address:8011 PASEO, Phone:(816) 444-6260  
smaslan1950@gmail.com, Address:smaslan1950@gmail.com  
ATLAS MECHANICAL SERVICES INC, Address:26015 RA HWY, Phone:(913) 708-4695  
ACES ELECTRIC LLC, Address:1550 S 94TH ST, Phone:(913) 485-3681  
KMZC PLUMBING, Address:301 W WEA, Phone:(913) 238-2583  
CORNERSTONE ARCHITECT LLC, Address:8117 ROBERTS RD, Phone:(816) 838-3472  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 10/14/2024 10/14/2024
Craig Hill
Alarm Plan Review Released for Construction 10/14/2024 10/14/2024
Craig Hill
Alarms connected to automatic sprinkler system
Corrective Action Required
10/14/2024

2018 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
Alarm testing.
Corrective Action Required
10/14/2024

2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation. Call (816) 969-1300 to schedule alarm test.
Licensed Contractors Approved 08/09/2024 08/13/2024
Joe Frogge
LC - General Contractor
Resolved
08/13/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact which is where inspection reports will be sent. 7/9/2024 - Not addressed. 8/8/2024 - Not addressed.
LC - MEP Subs
Resolved
08/13/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 7/9/2024 - Not addressed. 8/8/2024 - Not addressed.
Fire Plan Review Approved with Conditions 08/09/2024 08/08/2024
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
08/02/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm modification plans for review and approval.
Address numbers required
Corrective Action Required
08/02/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The address shall be posted on the front and rear doors. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
08/02/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler and hood suppression plans for review and approval.
Miscellaneous Correction
Corrective Action Required
08/02/2024

Provide hood system plans.
Miscellaneous Correction
Corrective Action Required
08/02/2024

5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1. Provide gas detection for the CO2 beverage system. Verified at inspection.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
08/02/2024

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Provide a K -class extinguisher under the manual pull for the hood system (not shown).
Portable fire extinguishers - general
Corrective Action Required
08/02/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one 2A, 10B,C fire extinguisher (not shown).
Type I hood - Where required
Corrective Action Required
08/02/2024

Plans for the kitchen hood are not included. Provide detailed plans of Type I hood. 2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Posting of occupant load
Corrective Action Required
08/02/2024

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
08/02/2024

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Building Plan Review Approved with Conditions 08/09/2024 08/08/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
08/02/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $15,105.75 7/9/2024 - Acknowledged in letter.
Health Dept Inspection
Corrective Action Required
08/02/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 7/9/2024 - Acknowledged in letter.
IBC 1606.2 Design dead load - structural
Resolved
08/08/2024

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new mechanical equipment. 7/9/2024 - Acknowledged in letter. Not yet received.
Fire Plan Review Rejected 07/09/2024 07/11/2024
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
07/01/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm modification plans for review and approval.
Address numbers required
Corrective Action Required
07/01/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The address shall be posted on the front and rear doors. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
07/01/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler and hood suppression plans for review and approval.
Miscellaneous Correction
Corrective Action Required
07/01/2024

Provide hood system plans.
Miscellaneous Correction
Corrective Action Required
07/01/2024

5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1. Provide gas detection for the CO2 beverage system. Verified at inspection.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
07/01/2024

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Provide a K -class extinguisher under the manual pull for the hood system (not shown).
Portable fire extinguishers - general
Corrective Action Required
07/01/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one 2A, 10B,C fire extinguisher (not shown).
Type I hood - Where required
Corrective Action Required
07/11/2024

Plans for the kitchen hood are not included. Provide detailed plans of Type I hood. 2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Posting of occupant load
Corrective Action Required
07/11/2024

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
07/11/2024

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Fire Plan Review Approved with Conditions 06/07/2024 07/10/2024
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
06/08/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm modification plans for review and approval.
Address numbers required
Resolved
07/10/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The address shall be posted on the front and rear doors. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
06/08/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler and hood suppression plans for review and approval.
Miscellaneous Correction
Corrective Action Required
06/08/2024

Provide hood system plans.
Miscellaneous Correction
Corrective Action Required
06/08/2024

5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1. Provide gas detection for the CO2 beverage system. Verified at inspection.
Portable fire extinguishers for commercial cooking equipment.
Resolved
07/10/2024

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Provide a K -class extinguisher under the manual pull for the hood system (not shown).
Portable fire extinguishers - general
Resolved
07/10/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of one 2A, 10B,C fire extinguisher (not shown).
Licensed Contractors Rejected 07/09/2024 07/09/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
07/01/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact which is where inspection reports will be sent. 7/9/2024 - Not addressed.
LC - MEP Subs
Corrective Action Required
07/01/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 7/9/2024 - Not addressed.
Building Plan Review Rejected 07/09/2024 07/09/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
07/01/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $15,105.75 7/9/2024 - Acknowledged in letter.
Health Dept Review
Resolved
07/03/2024

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
07/01/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 7/9/2024 - Acknowledged in letter.
IMC 507.2.6 Clearances for Type I hood
Resolved
07/09/2024

2018 IMC 507.2.6 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exceptions: 1. Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. 2. Type I hoods listed and labeled for clearances less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. Action required: Type 1 hood not allowed to be attached to wall as shown as it is built with wood studs.
IBC 1606.2 Design dead load - structural
Corrective Action Required
07/09/2024

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new mechanical equipment. 7/9/2024 - Acknowledged in letter. Not yet received.
IMC 602.2.1 Materials within plenums
Resolved
07/09/2024

2018 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: Specify compliant DWV pipe material. PVC not allowed in plenum.
IMC 506.5.3 Grease fan mounting hinge
Resolved
07/09/2024

2018 IMC 506.5.3 Exhaust fan mounting. Up-blast fans serving Type I hoods and installed in a vertical or horizontal position shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning and shall be equipped with a means of restraint to limit the swing of the fan on its hinge. The ductwork shall extend not less than 18 inches above the roof surface. Action required: Provide verification that grease fans are hinged for maintenance.
Health Department Review Approved 07/03/2024
Joe Frogge
Building Plan Review Rejected 06/07/2024 06/07/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
06/07/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $15,105.75
Health Dept Review
Corrective Action Required
06/07/2024

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
06/07/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
IMC 507.2.6 Clearances for Type I hood
Corrective Action Required
06/07/2024

2018 IMC 507.2.6 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exceptions: 1. Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. 2. Type I hoods listed and labeled for clearances less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. Action required: Type 1 hood not allowed to be attached to wall as shown as it is built with wood studs.
IBC 1606.2 Design dead load - structural
Corrective Action Required
06/07/2024

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new mechanical equipment.
IMC 602.2.1 Materials within plenums
Corrective Action Required
06/07/2024

2018 IMC 602.2.1 Materials within plenums. Except as required by Sections 602.2.1.1 through 602.2.1.5, materials within plenums shall be noncombustible or shall be listed and labeled as having a flame spread index of not more than 25 and a smoke-developed index of not more than 50 when tested in accordance with ASTM E84 or UL 723. (see code section for exceptions) Action required: Specify compliant DWV pipe material. PVC not allowed in plenum.
IMC 506.5.3 Grease fan mounting hinge
Corrective Action Required
06/07/2024

2018 IMC 506.5.3 Exhaust fan mounting. Up-blast fans serving Type I hoods and installed in a vertical or horizontal position shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning and shall be equipped with a means of restraint to limit the swing of the fan on its hinge. The ductwork shall extend not less than 18 inches above the roof surface. Action required: Provide verification that grease fans are hinged for maintenance.
Licensed Contractors Rejected 06/07/2024 06/07/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
06/07/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
06/07/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $800.00 $800.00 Paid 08/13/2024
7232302-Commercial License Tax Fee $15,105.75 $15,105.75 Paid 01/17/2025
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 12/09/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 12/09/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 8/26/2024 8/26/2024 08/26/2024
Miscellaneous Correction
Corrective Action Required
08/26/2024
Provide pressure test at 5psi or 10’ water column
Underslab Plumbing Inspection - Commercial Passed 8/27/2024 8/27/2024 08/27/2024
Miscellaneous Correction
Resolved
08/27/2024
Provide pressure test at 5psi or 10’ water column
In-wall Inspection Failed 8/26/2024 9/19/2024 09/19/2024
Misc
Corrective Action Required
09/19/2024
Complete all MEPs
Hood/Duct Inspection Partial 9/19/2024 09/19/2024
Misc
Informational
09/19/2024
(3) 10' straight sections inspected on the ground-Lighttest ok
Misc
Corrective Action Required
09/19/2024
In-wall Inspection Failed 9/23/2024 09/23/2024
Misc
Corrective Action Required
09/19/2024
Complete all MEPs
In-wall Inspection Partial 9/25/2024 9/25/2024 09/25/2024
Misc
Corrective Action Required
09/23/2024
Secure PEX per code **OK to 1 side
Hood/Duct Inspection Partial 10/2/2024 10/02/2024
Misc
Informational
09/19/2024
(3) 10' straight sections inspected on the ground-Light test ok (2) of (3) inspected 10' sections 2 layers of wrap approved through truss space only
Misc
Corrective Action Required
09/19/2024
Rated Assembly Inspection Partial 10/2/2024 10/02/2024
Misc
Corrective Action Required
10/02/2024
-1st layer patches at fire wall ok
In-wall Inspection Not Ready 10/7/2024 10/7/2024 10/07/2024
Misc
Corrective Action Required
09/25/2024
Secure PEX per code **OK to 1 side
Hood/Duct Inspection Partial 10/10/2024 10/10/2024 10/10/2024
Misc
Informational
10/02/2024
-Light test approved
Misc
Corrective Action Required
10/02/2024
In-wall Inspection Passed 10/11/2024
Misc
Resolved
10/11/2024
Secure PEX per code **OK to 1 side
Rated Assembly Inspection Partial 10/11/2024 10/11/2024
Misc
Resolved
10/11/2024
-1st AND 2nd layer patches at fire wall ok *Seal penetrations
Hood/Duct Inspection Partial 10/11/2024 10/11/2024
Misc
Informational
10/10/2024
-Light test approved 1st layer wrap
Misc
Corrective Action Required
10/10/2024
Above Ceiling Inspection Partial 10/11/2024 10/11/2024
Misc
Corrective Action Required
10/11/2024
-Hard lids at bathrooms and corridor approved
Above Ceiling Inspection Partial 10/15/2024 10/15/2024 10/15/2024
Misc
Corrective Action Required
10/11/2024
-Hard lids approved to cover
Gas Service Inspection - Commercial Passed 11/25/2024 11/25/2024 11/25/2024
Above Ceiling Inspection Not Ready 11/25/2024 11/25/2024 11/25/2024
Misc
Informational
11/25/2024
-Hard lids approved to cover
Miscellaneous Correction
Corrective Action Required
11/25/2024
11/25/24 -Not ready. Remove all tile and complete meps for inspection
Hood/Duct Inspection Passed 12/13/2024 12/13/2024 12/13/2024
Misc
Resolved
12/13/2024
-Light test approved 1st layer wrap
Misc
Resolved
12/13/2024
Above Ceiling Inspection Failed 12/13/2024 12/13/2024 12/13/2024
Misc
Informational
12/12/2024
-Hard lids approved to cover
Miscellaneous Correction
Corrective Action Required
12/12/2024
-Close all open J boxes -Secure all mc within 12" of boxes -Support all mc and lv from grid -Seal all penetrations in firewall -Label firewall per code -Complete condensate line
Above Ceiling Inspection Passed 12/17/2024 12/17/2024 12/17/2024
Misc
Resolved
12/17/2024
-Hard lids approved to cover
Miscellaneous Correction
Resolved
12/17/2024
-Close all open J boxes -Secure all mc within 12" of boxes -Support all mc and lv from grid -Seal all penetrations in firewall -Label firewall per code -Complete condensate line
Alarm Test Passed 01/15/2025
Alternate Protection Systems Inspection Passed 01/15/2025
Rated Assembly Inspection Passed 01/21/2025
Occupancy Inspection - Codes Commercial Failed 1/22/2025 1/22/2025 01/22/2025
Misc
Corrective Action Required
01/22/2025
-Complete corrections for LSFD -Obtain Jackson County Health Department approval -Provide backflow devices for ice machine and carbonated beverage machines -Provide proper air gap at drains to floor -Sinks in restrooms not to be above 34" -Mirrors in restrooms to be max 40" to reflective surface -Provide GFCI protection at all kitchen receptacles
Occupancy Inspection - Fire Failed 1/22/2025 1/22/2025 01/22/2025
Occupancy Inspection - Codes Commercial Failed 1/28/2025 1/28/2025 01/28/2025
Misc
Corrective Action Required
01/22/2025
-Obtain Jackson County Health Department approval-Upload document to portal -Provide backflow devices for carbonated beverage machine-Must be ASSE 1022
Occupancy Inspection - Codes Commercial Full C of O 1/29/2025 1/29/2025 01/29/2025
Misc
Resolved
01/29/2025
-Obtain Jackson County Health Department approval-Upload document to portal -Provide backflow devices for carbonated beverage machine-Must be ASSE 1022
Documents & Images
Date Uploaded File Type Document Name
05/28/2024 Application Form APPLICATION
05/28/2024 Plans Full Drawing Set - Magic Noodles 2 @ Lee Summit
05/30/2024 Email RE_ LT Q - PRCOM20242672
05/30/2024 Letter License Tax Bill
06/10/2024 Letter DS P/R Corrections Document
06/30/2024 Plans City Comments - Magic Noodles 2 @ Lee Summit
06/30/2024 Letter Cover Letter - Magic Noodle 2
06/30/2024 Specifications Hood System - Larkin
06/30/2024 Specifications 0-Clearance Hood
07/03/2024 Letter Jackson Cty Health approval
07/11/2024 Letter DS P/R Corrections Document
08/02/2024 Letter Cover Letter 2 - Magic Noodle 2
08/02/2024 Plans City Comments 2- Magic Noodles 2 @ Lee Summit
08/08/2024 Approved Plans Engineer's truss repair design
08/09/2024 Approved Plans Approved construction plans
08/13/2024 Receipt Receipt for transaction:2024-006842
08/14/2024 Letter DS Building Permit
08/26/2024 Letter INSPECTION SUMMARY
08/27/2024 Letter INSPECTION SUMMARY
08/27/2024 Letter INSPECTION SUMMARY
09/19/2024 Letter INSPECTION SUMMARY
09/19/2024 Letter INSPECTION SUMMARY
09/23/2024 Letter INSPECTION SUMMARY
09/25/2024 Letter INSPECTION SUMMARY
09/30/2024 19290 Magic Noodles FP Submittal
09/30/2024 Magic Noodle 2 FA 9 18 24 PE Stamp
09/30/2024 Magic Noodle 2 Battery Calc PE Stamp
10/02/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/10/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/14/2024 Letter Fire (Sprinkler) Plan Review
10/14/2024 Letter Fire (Alarm) Plan Review Notice
10/15/2024 Letter INSPECTION SUMMARY
11/25/2024 Letter INSPECTION SUMMARY
11/25/2024 Letter INSPECTION SUMMARY
12/09/2024 Receipt Receipt for transaction: 2024-009393
12/13/2024 Letter INSPECTION SUMMARY
12/13/2024 Letter INSPECTION SUMMARY
12/13/2024 Letter INSPECTION SUMMARY
12/17/2024 Letter INSPECTION SUMMARY
01/17/2025 Receipt Receipt for transaction: 2025-000316
01/21/2025 Letter INSPECTION SUMMARY
01/22/2025 Letter INSPECTION SUMMARY
01/28/2025 Letter INSPECTION SUMMARY
01/28/2025 Letter health department approval
01/29/2025 Letter Field Certificate of Occupancy
01/29/2025 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home