Review Type |
Outcome |
Est. Completion Date |
Completed |
Licensed Contractors
|
Approved
|
10/23/2023
|
10/30/2023
|
|
Joe Frogge
|
|
LC - MEP Subs
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. (Switch Electric not licensed with us) neither is Interstate Elec
|
|
|
Fire Plan Review
|
Approved with Conditions
|
10/23/2023
|
10/25/2023
|
|
Joe Frogge
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Provide a minimum three 2A, 40B,C fire extinguishers. place two near the office and garage exits and the third with 30 feet of travel near any cutting ,welding or grinding areas. Verified at inspection.
|
|
Miscellaneous Correction
Corrective Action Required
2311.2.2 Waste oil, motor oil and other Class IIIB liquids.Waste oil, motor oil and other Class IIIB liquids
shall be stored in approved tanks or containers, which are allowed to be stored and dispensed from inside repair garages.
Verified at inspection.
|
|
Miscellaneous Correction
Corrective Action Required
2311.2.1 Cleaning of parts. Cleaning of parts shall be
conducted in listed and approved parts-cleaning machines in accordance with Chapter 57.
|
|
Miscellaneous Correction
Corrective Action Required
2311.3 Sources of ignition. Sources of ignition shall not be located within 18 inches (457 mm) of the floor and shall comply with Chapters 3 and 35.
2311.3.1 Equipment. Appliances and equipment installed
in a repair garage shall comply with the provisions of the
International Building Code, the International Mechanical
Code and NFPA 70.
For information, since the water heater and furnces are not shown. Verified at inspection.
|
|
MISC
Corrective Action Required
For information only- The servicing of alaternative fueled vehicles shall meet the requirements of the International Fire Code and International Building Code.
|
|
|
Building Plan Review
|
Approved with Conditions
|
10/23/2023
|
10/25/2023
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process.
Action required: Comment is for informational purposes. After credit for previous warehouse occupant the fee will be $9,124.50
|
|
|
Zoning Review
|
Approved
|
10/23/2023
|
10/25/2023
|
|
Joe Frogge
|
|
Corrective Action Required
Approved for minor auto repair only. Major auto repair will require a SUP.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
10/23/2023
|
10/23/2023
|
|
Jim Eden
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Provide a minimum three 2A, 40B,C fire extinguishers. place two near the office and garage exits and the third with 30 feet of travel near any cutting ,welding or grinding areas. Verified at inspection.
|
|
Miscellaneous Correction
Corrective Action Required
2311.2.2 Waste oil, motor oil and other Class IIIB liquids.Waste oil, motor oil and other Class IIIB liquids
shall be stored in approved tanks or containers, which are allowed to be stored and dispensed from inside repair garages.
Verified at inspection.
|
|
Miscellaneous Correction
Corrective Action Required
2311.2.1 Cleaning of parts. Cleaning of parts shall be
conducted in listed and approved parts-cleaning machines in accordance with Chapter 57.
|
|
Miscellaneous Correction
Corrective Action Required
2311.3 Sources of ignition. Sources of ignition shall not be located within 18 inches (457 mm) of the floor and shall comply with Chapters 3 and 35.
2311.3.1 Equipment. Appliances and equipment installed
in a repair garage shall comply with the provisions of the
International Building Code, the International Mechanical
Code and NFPA 70.
For information, since the water heater and furnces are not shown. Verified at inspection.
|
|
MISC
Corrective Action Required
For information only- The servicing of alaternative fueled vehicles shall meet the requirements of the International Fire Code and International Building Code.
|
|
|
Building Plan Review
|
Approved with Conditions
|
10/23/2023
|
10/18/2023
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process.
Action required: Comment is for informational purposes. After credit for previous warehouse occupant the fee will be $9,124.50
|
|
|