Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved with Conditions
|
08/09/2023
|
08/08/2023
|
|
Jim Eden
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Make sure the address is posted along with a B.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THe paint booths shall have documentation of a current annual inspection.
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Verified at inspection.
|
|
Miscellaneous Correction
Corrective Action Required
Correct the occupancy classification from B to S1.
|
|
|
Building Plan Review
|
Approved
|
08/09/2023
|
08/04/2023
|
|
Joe Frogge
|
|
Misc
Where will relocated sheds end up? Where are the foundation designs? How will they be anchored?
Action required: Provide designs and/or clarifications. Also, Planning staff is assessing situation as potential Final Development Plan submittal.
8/4/23 - sheds to remain unchanged. legal non-conforming
|
|
Misc
Additional information required at new exterior door.
Actions required:
- Provide header detail
- Proved landing at exterior side
8/4/23 - per architect wall is not load bearing and exterior is asphalt
|
|
Planning - Screening of ground mounted equipment
Unified Development Ordinance Article 8, Section 8.180.F
Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened.
Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section. (ref: condensing unit CU-1)
8/4/23- per architect there are no new ground mounted equipment
|
|
Planning - Screening of rooftop equipment
Unified Development Ordinance Article 8, Section 8.180.E
Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director.
Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section. (ref: exhaust fan EF-1)
8/4/23- per architect this is just a replacement
|
|
Miscellaneous Correction
More information required for plumbing services.
Action required: Specify location and type of connection of new water and sewer services. Detail indicates new water meter? This may trigger Engineering Review and/of Final Development Plan.
8/4/23- per architect this is all private on site
|
|
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Action required: Provide receptacles within 25' of new condensing unit and roof mounted ventilation fan.
8/4/23- per architect there is no new equipment
|
|
|
Licensed Contractors
|
Approved
|
08/09/2023
|
08/04/2023
|
|
Joe Frogge
|
|
|
Zoning Review
|
Approved
|
08/09/2023
|
08/02/2023
|
|
Joe Frogge
|
|
sheds are legal non-conforming so may stay in place. If relocated they must be approved and be on footings or similar approved foundations.
|
Fire Plan Review
|
Approved with Conditions
|
07/13/2023
|
07/18/2023
|
|
Jim Eden
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Make sure the address is posted along with a B.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
THe paint booths shall have documentation of a current annual inspection.
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Verified at inspection.
|
|
Miscellaneous Correction
Corrective Action Required
Correct the occupancy classification from B to S1.
|
|
|
Building Plan Review
|
Rejected
|
07/13/2023
|
07/10/2023
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
Where will relocated sheds end up? Where are the foundation designs? How will they be anchored?
Action required: Provide designs and/or clarifications. Also, Planning staff is assessing situation as potential Final Development Plan submittal.
|
|
Misc
Corrective Action Required
Additional information required at new exterior door.
Actions required:
- Provide header detail
- Proved landing at exterior side
|
|
Planning - Screening of ground mounted equipment
Corrective Action Required
Unified Development Ordinance Article 8, Section 8.180.F
Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened.
Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section. (ref: condensing unit CU-1)
|
|
Planning - Screening of rooftop equipment
Corrective Action Required
Unified Development Ordinance Article 8, Section 8.180.E
Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director.
Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section. (ref: exhaust fan EF-1)
|
|
Miscellaneous Correction
Corrective Action Required
More information required for plumbing services.
Action required: Specify location and type of connection of new water and sewer services. Detail indicates new water meter? This may trigger Engineering Review and/of Final Development Plan.
|
|
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Action required: Provide receptacles within 25' of new condensing unit and roof mounted ventilation fan.
|
|
|
Licensed Contractors
|
Approved
|
07/13/2023
|
06/30/2023
|
|
Joe Frogge
|
|
|