Permit Application Status

PRCOM20226036


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20226036
Building Permit - Commercial
Final Completion
SUMMIT DEVELOPMENT CO
ALTERATION COMMERCIAL
CONSTRUCTION OF WALL TO SEPARATE SPRINKLER RISER ROOM FROM TENANT SPACE TO ACCOMMODATE STATE REGULATIONS
12/08/2022
02/23/2023
04/29/2024
Locations
Contacts
KSJ CONSTRUCTION, Address:6703 HWY JJ, Phone:(209) 585-5868  
JEROME JANTZ, Address:33433 ALMOND RD, Phone:(209) 585-5868  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
WESTHUES ELECTRIC INC, Address:PO BOX 18220, Phone:(816) 356-5223  
SUMMIT DEVELOPMENT CO, Address:4622 PENNSYLVANIA AVE STE 700  
DONALDSON MECHANICAL INC, Address:934 SE 7TH TER, Unit B, Phone:(816) 246-9500  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 12/20/2022 12/20/2022
Ben Hicks
Installation acceptance testing
Corrective Action Required
12/20/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Provide as built sprinkler updates for coverage new area. Verified at inspection.
Building Plan Review Approved 12/20/2022 12/13/2022
Joe Frogge
Licensed Contractors Rejected 12/08/2022 12/13/2022
Joe Frogge
LC - General Contractor
Resolved
12/20/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Resolved
02/06/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $50.00 $50.00 Paid 02/08/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 4/10/2024 04/10/2024
Misc
Corrective Action Required
04/10/2024
-Drawings need to be updated to reflect materials used in wall next to riser room.
Miscellaneous Inspection Failed 4/16/2024 04/16/2024
Misc
Informational
04/16/2024
-Performed miscellaneous inspection on 4/10/24 determined per Joe Frogge that incorrect materials were used as separation wall between sprinkler riser room and retail space. Drawings revised, submitted and approved. Waiting on replacement wall to be built per new specs.
In-wall Inspection Passed 4/25/2024 4/25/2024 04/25/2024
Misc
Corrective Action Required
04/10/2024
-Drawings need to be updated to reflect materials used in wall next to riser room.
Documents & Images
Date Uploaded File Type Document Name
12/08/2022 Application Form Application for Permit - GRD Kirksville, LLC - 12-8-2022
12/08/2022 Plans GRD LEES SUMMIT COMBINED
12/20/2022 Letter Fire Building Plan Review
12/20/2022 Approved Plans old - GRD LEES SUMMIT COMBINED
01/19/2023 Approved Plans approved - GRD-LEESUMMIT-ADDENDUM-01
02/08/2023 Receipt Receipt for transaction:2023-000753
07/13/2023 Letter Codes 140 Day Letter
08/22/2023 Letter Codes 180 Day Letter
04/10/2024 Letter INSPECTION SUMMARY
04/11/2024 Drawing GRD LEES SUMMIT-A-400 - REVISED 4-10-24
04/11/2024 Approved Plans Approved revised A-400
04/16/2024 Letter DS Building Permit
04/16/2024 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home