Permit Application Status

PRCOM20220752


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20220752
Building Permit - Commercial
Certificate of Occupancy
MIDWEST DIVISION LSH LLC
NEW TENANT FINISH
TENANT FINISH FOR MEDICAL CLINIC LEES SUMMIT MEDICAL CENTER - MOB #2302 DR ARTIGO INFUSION CENTER
03/01/2022
04/07/2022
08/19/2022
Locations
Contacts
BGS CONSTRUCTION, Address:34607 E COLBERN RD, Phone:(816) 566-0351  
Luke Sweeney, Address:lukebgskc@gmail.com, Phone:(816) 896-3662  
PRO PLATINUM LLC, Address:6116 ALDEN RD, Phone:(913) 908-3512  
CLAYCO ELECTRIC COMPANY, Address:319 E 11TH AVE, Phone:(816) 221-0593  
SLOCUM & SONS PLUMBING, Address:3804 S MARSHALL CT, Phone:(816) 373-4817  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
MIDWEST DIVISION LSH LLC, Address:PO BOX 80610  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 05/04/2022
Jim Eden
Installation acceptance testing
Corrective Action Required
05/04/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required- A visual inspection will be completed at the alarm test or occupancy inspection.
Licensed Contractors Approved 03/11/2022 04/06/2022
Joe Frogge
LC - MEP Subs
Resolved
04/06/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
LC - General Contractor
Resolved
04/06/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact which is where inspection reports will be sent.
Building Plan Review Approved 03/11/2022 03/09/2022
Joe Frogge
Fire Plan Review Approved with Conditions 03/11/2022 03/08/2022
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
03/08/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required- Provide shop drawings for the addition or relocation of notification appliances.
Construction documents - Fire protection systems
Corrective Action Required
03/08/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Provide shop drawings for alterations to the sprinkler system.
Installation acceptance testing
Corrective Action Required
03/08/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required- Schedule alarm testing befotre regular business hours. Call (816) 969-1300 to schedule a test.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $760.00 $760.00 Paid 04/07/2022
8331507-Sewer Connection Fee $90.00 $90.00 Paid 04/07/2022
7232302-Commercial Excise Tax Fee $3,165.00 $3,165.00 Paid 04/07/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 05/19/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 05/19/2022
Outstanding Fees Amount Paid Owing Date Paid
9110080-Not Ready Inspection Fee $75.00 $0.00 $75.00 Not Paid


$75.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 5/9/2022 5/9/2022 05/09/2022
Misc
Corrective Action Required
05/09/2022
-Complete electrical
In-wall Inspection Not Ready 5/10/2022 5/10/2022 05/10/2022
Misc
Corrective Action Required
05/09/2022
**5/10/22-NOT READY -Complete electrical
In-wall Inspection Partial 5/13/2022 5/13/2022 05/13/2022
Misc
Corrective Action Required
05/10/2022
-Missing bonding screw and jumper at metallic cut in box in stairwell wall
In-wall Inspection Not Ready 5/18/2022 5/18/2022 05/18/2022
Misc
Corrective Action Required
05/13/2022
-Missing bonding screw and jumper at metallic cut in box in stairwell wall-5/18/22 still no corrections made
In-wall Inspection Passed 5/20/2022 5/20/2022 05/20/2022
Misc
Resolved
05/20/2022
-Missing bonding screw and jumper at metallic cut in box in stairwell wall-5/18/22 still no corrections made
Above Ceiling Inspection Failed 7/11/2022 7/11/2022 07/11/2022
Miscellaneous Correction
Corrective Action Required
07/11/2022
7/11/22 No access -Doors locked, called Luke at 816-896-3662, no answer. -RESCHEDULE WHEN CONTRACTOR WILL BE ON SITE WITH PLANS AND ACCESS
Above Ceiling Inspection Failed 7/13/2022 07/13/2022
Miscellaneous Correction
Corrective Action Required
07/11/2022
7/11/22 No access -Doors locked, called Luke at 816-896-3662, no answer. -RESCHEDULE WHEN CONTRACTOR WILL BE ON SITE WITH PLANS AND ACCESS. 7/13 called no answer- borders installed, open J boxes, penetrations in fire rated walls. recall for inspeciton, remove all borders , secure all MC within 12" of boxes, support per code. check plans on water line not being insulated. , label all plumbing. light fixtures handing above ceiling. NO INSPECTION.
Misc
Corrective Action Required
07/13/2022
Above Ceiling Inspection Failed 7/18/2022 07/18/2022
Miscellaneous Correction
Corrective Action Required
07/13/2022
INSPECTION INCOMPLETE- REMOVE BORDERS BEFORE ANY FURTHER INSPECTION -COMPLETE ELECTRICAL AND PLUMBING -ENSURE ALL MC IS SPPORTED AND SECURED -LAND ALL ELECTRICAL AND LOW VOLT IN BOXES -REMOVE ALL TEMP LIGHTING -INSULATE WATER LINES PER CODE -LABEL ALL DWV PER -SUPPORT ALL LIGHTS AT OPPOSITE CORNERS -SEAL ALL PENETRATIONS IN FIRE BARRIERS
Misc
Corrective Action Required
07/13/2022
Above Ceiling Inspection Partial 8/5/2022 8/5/2022 08/05/2022
Miscellaneous Correction
Corrective Action Required
07/18/2022
APPROVED EXCEPT AS NOTED: -REMOVE TEMP LIGHTING, SEAL CONDUIT PENETRATION AND SUPPORT LOW VOLTAGE IN BATHROOM AND PREP ROOM *OK FOR BORDERS
Misc
Corrective Action Required
07/18/2022
Above Ceiling Inspection Passed 8/8/2022 8/8/2022 08/08/2022
Miscellaneous Correction
Resolved
08/08/2022
APPROVED EXCEPT AS NOTED: -REMOVE TEMP LIGHTING, SEAL CONDUIT PENETRATION AND SUPPORT LOW VOLTAGE IN BATHROOM AND PREP ROOM *OK FOR BORDERS
Misc
Resolved
08/08/2022
Occupancy Inspection - Codes Commercial Failed 8/16/2022 8/16/2022 08/16/2022
Misc
Corrective Action Required
08/16/2022
-Provide address -Service counter in lobby to be max 34" aff -Provide accessible restroom signage -Mirror in restroom to be max 40" to reflective surface -Grab bar behind toilet to be max 6" from side wall and min 42" from side wall -Restroom walls to have non absorbant finish at all walls within 2' of sink or toilet to min 48" aff -Provide panel labels and panel schedules in electrical room -Complete all corrections for Fire Department
Alarm Test Not Ready 8/16/2022 08/16/2022
Occupancy Inspection - Codes Commercial Failed 8/18/2022 8/18/2022 08/18/2022
Misc
Corrective Action Required
08/16/2022
-Switch signs for communications and electrical room to right room -Provide accessible restroom signage
Alarm Test Passed 8/18/2022 08/18/2022
Occupancy Inspection - Fire Passed 8/18/2022 8/18/2022 08/18/2022
Corrective Action Required
08/18/2022
All life safety was appropriate. Okay to occupy with approval form codes.
Occupancy Inspection - Codes Commercial Full C of O 8/19/2022 08/19/2022
Misc
Resolved
08/19/2022
-Switch signs for communications and electrical room to right room -Provide accessible restroom signage
Documents & Images
Date Uploaded File Type Document Name
03/01/2022 Application Form Commercial Permit Application 2021 - LSMC #2302
03/01/2022 Plans 2302 Infusion Full Set 01-07-2022
03/08/2022 Letter Fire Building Plan Review
03/09/2022 Plans old - 2302 Infusion Full Set 01-07-2022
04/06/2022 Letter License Tax Bill
04/07/2022 Receipt Receipt for transaction:2022-001936
04/07/2022 Letter DS Building Permit
05/09/2022 Letter INSPECTION SUMMARY
05/09/2022 Letter Fire (Sprinkler) Plan Review
05/10/2022 Letter INSPECTION SUMMARY
05/13/2022 Letter INSPECTION SUMMARY
05/18/2022 Letter INSPECTION SUMMARY
05/19/2022 Plans 2302 Infusion Full Set 05-18-2022
05/19/2022 Approved Plans approved - 2302 Infusion Full Set 05-18-2022
05/19/2022 Receipt Receipt for transaction:2022-003705
05/20/2022 Letter INSPECTION SUMMARY
06/29/2022 Sealed - Energize_Lee's Summit MOB Suite 2302 Fire Alarm FA01
06/29/2022 Letter Fire (Alarm) Plan Review Notice
07/11/2022 Letter INSPECTION SUMMARY
07/13/2022 Letter INSPECTION SUMMARY
07/18/2022 Letter INSPECTION SUMMARY
08/05/2022 Letter INSPECTION SUMMARY
08/08/2022 Letter INSPECTION SUMMARY
08/16/2022 Letter INSPECTION SUMMARY
08/18/2022 Letter INSPECTION SUMMARY
08/19/2022 Letter Codes Final Certificate of Occupancy
08/19/2022 Letter Field Certificate of Occupancy
08/19/2022 Letter Fire Loss Reduction Form
08/18/2022 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home