Review Type |
Outcome |
Est. Completion Date |
Completed |
Licensed Contractors
|
Approved
|
03/14/2022
|
03/15/2022
|
|
Development Center
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Provide an email address for the on-site contact which is where inspection reports will be sent.
|
|
LC - MEP Subs
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company name of licensed electrical contractor.
|
|
|
Building Plan Review
|
Approved with Conditions
|
03/14/2022
|
03/15/2022
|
|
Joe Frogge
|
|
Health Dept Review
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is for informational purposes.
3/10/22 - acknowledged in letter
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is for informational purposes.
3/10/22 - acknowledged in letter
|
|
Code analysis required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Action required: Include 2nd floor in code analysis.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
03/14/2022
|
03/13/2022
|
|
Jim Eden
|
|
Misc
Corrective Action Required
If the addition of the bar causes a need to adjust sprinkler head coverage or relocate alarm notification appliances. Have the appropriate fire protection contractor make adjustments and provide "as builts". All other conditions will be verified at inspection, including documentation of current inspections of the alarm and sprinkler systems.
|
|
Posting of occupant load
2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required- Repost the adjusted occupant load for the first floor. Verified at inspection.
|
|
Direction of swing
Corrective Action Required
2018 IFC 1010.1.2.1 Direction of swing. Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy.
Action required- Confirm the direction of front door swing.
|
|
|
Building Plan Review
|
Rejected
|
03/02/2022
|
02/25/2022
|
|
Joe Frogge
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is for informational purposes.
|
|
Code analysis required
Corrective Action Required
A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed.
Action required: Include 2nd floor in code analysis.
|
|
|
Licensed Contractors
|
Rejected
|
03/02/2022
|
02/25/2022
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Provide an email address for the on-site contact which is where inspection reports will be sent.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
03/02/2022
|
02/23/2022
|
|
Jim Eden
|
|
Posting of occupant load
Corrective Action Required
2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required- Repost the adjusted occupant load for the first floor. Verified at inspection.
|
|
Misc
Corrective Action Required
If the addition of the bar causes a need to adjust sprinkler head coverage or relocate alarm notification appliances. Have the appropriate fire protection contractor make adjustments and provide "as builts". All other conditions will be verified at inspection, including documentation of current inspections of the alarm and sprinkler systems.
|
|
|