Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved
|
02/24/2022
|
02/22/2022
|
|
Jim Eden
|
|
Portable fire extinguishers - general
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required- Provide a minimum of one 2A;10B;C fire extinguisher in the cabinet provided. Verified at inspection.
|
|
Miscellaneous Correction
The code reiview indicates a fire alarm system is provided, what will be provided?
|
|
Misc
List the 2018 International Fire Code adopted by the City of Lee's Summit with local amendments as a referenced code .
|
|
Miscellaneous Correction
[BE] 1011.7.3 Enclosures under interior stairways. The
walls and soffits within enclosed usable spaces under
enclosed and unenclosed stairways shall be protected by 1-hour fire-resistance- rated construction or the fire-resistance rating of the stairway enclosure, whichever is greater. Access to the enclosed space shall not be directly from within the stairway enclosure.
Action required- Any enclosures under the stairs (STR 108) shall be rated construction. Confirm location of the storage room in relation to the stairs.
|
|
Miscellaneous Correction
|
|
Address numbers required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Action required- Unit numbers shall be posted on the fron and rear doors. Verified at inspection.
|
|
|
Licensed Contractors
|
Approved
|
02/24/2022
|
02/16/2022
|
|
Joe Frogge
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Provide an email address for the on-site contact which is where inspection reports will be sent.
|
|
LC - MEP Subs
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
2/16/22 -
|
|
|
Building Plan Review
|
Approved
|
02/24/2022
|
02/16/2022
|
|
Joe Frogge
|
|
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2.
Action required: Provide minimum 18" clearance at latch side of doors out of restrooms.
|
|
ICC A117.1 902.4 Dining and work surfaces
ICC A117.1 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor.
Action required: Modify Cafe Island to comply.
|
|
|
Building Plan Review
|
Rejected
|
02/14/2022
|
02/10/2022
|
|
Joe Frogge
|
|
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2.
Action required: Provide minimum 18" clearance at latch side of doors out of restrooms.
|
|
ICC A117.1 902.4 Dining and work surfaces
Corrective Action Required
ICC A117.1 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor.
Action required: Modify Cafe Island to comply.
|
|
|
Licensed Contractors
|
Rejected
|
02/14/2022
|
02/10/2022
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Provide an email address for the on-site contact which is where inspection reports will be sent.
|
|
LC - MEP Subs
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|
Fire Plan Review
|
Rejected
|
02/14/2022
|
02/08/2022
|
|
Jim Eden
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required- Provide a minimum of one 2A;10B;C fire extinguisher in the cabinet provided. Verified at inspection.
|
|
Miscellaneous Correction
Corrective Action Required
The code reiview indicates a fire alarm system is provided, what will be provided?
|
|
Misc
Corrective Action Required
List the 2018 International Fire Code adopted by the City of Lee's Summit with local amendments as a referenced code .
|
|
Miscellaneous Correction
Corrective Action Required
[BE] 1011.7.3 Enclosures under interior stairways. The
walls and soffits within enclosed usable spaces under
enclosed and unenclosed stairways shall be protected by 1-hour fire-resistance- rated construction or the fire-resistance rating of the stairway enclosure, whichever is greater. Access to the enclosed space shall not be directly from within the stairway enclosure.
Action required- Any enclosures under the stairs (STR 108) shall be rated construction. Confirm location of the storage room in relation to the stairs.
|
|
Miscellaneous Correction
Corrective Action Required
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Action required- Unit numbers shall be posted on the fron and rear doors. Verified at inspection.
|
|
|