Summary
PRCOM20220431
Building Permit - Commercial
Certificate of Occupancy
NEW TENANT FINISH
TENANT FINISH FOR OFFICE
02/02/2022
03/22/2022
08/09/2022
08/18/2022
Locations
Contacts
Monarch Build, LLC, Address:8100 Newton Street Ste 300, Phone:(913) 942-2400  
david.adams@monarch.build, Address:david.adams@monarch.build  
HENRY MILLER MECHANICAL LLC, Address:6609 ROYAL ST, SUITE 104, Phone:(816) 883-8818  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
PRO DESIGN CONTRACTORS LLC, Address:918 E WARREN ST, Phone:(913) 308-6900  
CLOCKWORK, Address:423 DELAWARE STREET #102, Phone:(816) 807-3787  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 02/24/2022 02/22/2022
Jim Eden
Portable fire extinguishers - general
Resolved
02/22/2022

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required- Provide a minimum of one 2A;10B;C fire extinguisher in the cabinet provided. Verified at inspection.
Miscellaneous Correction
Resolved
02/22/2022

The code reiview indicates a fire alarm system is provided, what will be provided?
Misc
Resolved
02/22/2022

List the 2018 International Fire Code adopted by the City of Lee's Summit with local amendments as a referenced code .
Miscellaneous Correction
Resolved
02/22/2022

[BE] 1011.7.3 Enclosures under interior stairways. The walls and soffits within enclosed usable spaces under enclosed and unenclosed stairways shall be protected by 1-hour fire-resistance- rated construction or the fire-resistance rating of the stairway enclosure, whichever is greater. Access to the enclosed space shall not be directly from within the stairway enclosure. Action required- Any enclosures under the stairs (STR 108) shall be rated construction. Confirm location of the storage room in relation to the stairs.
Miscellaneous Correction
Resolved
02/22/2022

Address numbers required
Resolved
02/22/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required- Unit numbers shall be posted on the fron and rear doors. Verified at inspection.
Licensed Contractors Approved 02/24/2022 02/16/2022
Joe Frogge
LC - General Contractor
Resolved
02/16/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Provide an email address for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Resolved
02/16/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 2/16/22 -
Building Plan Review Approved 02/24/2022 02/16/2022
Joe Frogge
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Resolved
02/16/2022

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clearance at latch side of doors out of restrooms.
ICC A117.1 902.4 Dining and work surfaces
Resolved
02/16/2022

ICC A117.1 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor. Action required: Modify Cafe Island to comply.
Building Plan Review Rejected 02/14/2022 02/10/2022
Joe Frogge
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
02/10/2022

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clearance at latch side of doors out of restrooms.
ICC A117.1 902.4 Dining and work surfaces
Corrective Action Required
02/10/2022

ICC A117.1 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor. Action required: Modify Cafe Island to comply.
Licensed Contractors Rejected 02/14/2022 02/10/2022
Joe Frogge
LC - General Contractor
Corrective Action Required
02/10/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Provide an email address for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
02/10/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 02/14/2022 02/08/2022
Jim Eden
Portable fire extinguishers - general
Corrective Action Required
02/08/2022

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required- Provide a minimum of one 2A;10B;C fire extinguisher in the cabinet provided. Verified at inspection.
Miscellaneous Correction
Corrective Action Required
02/08/2022

The code reiview indicates a fire alarm system is provided, what will be provided?
Misc
Corrective Action Required
02/08/2022

List the 2018 International Fire Code adopted by the City of Lee's Summit with local amendments as a referenced code .
Miscellaneous Correction
Corrective Action Required
02/08/2022

[BE] 1011.7.3 Enclosures under interior stairways. The walls and soffits within enclosed usable spaces under enclosed and unenclosed stairways shall be protected by 1-hour fire-resistance- rated construction or the fire-resistance rating of the stairway enclosure, whichever is greater. Access to the enclosed space shall not be directly from within the stairway enclosure. Action required- Any enclosures under the stairs (STR 108) shall be rated construction. Confirm location of the storage room in relation to the stairs.
Miscellaneous Correction
Corrective Action Required
02/08/2022

Address numbers required
Corrective Action Required
02/08/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required- Unit numbers shall be posted on the fron and rear doors. Verified at inspection.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,394.68 $1,394.68 Paid 03/07/2022
8331507-Sewer Connection Fee $150.00 $150.00 Paid 03/17/2022
7232302-Commercial Excise Tax Fee $3,090.00 $3,090.00 Paid 03/22/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Failed 3/24/2022 3/24/2022 03/24/2022
Misc
Corrective Action Required
03/24/2022
Unit (A) - no presure - trap wier cannot rise then fall in s pattern, lower traps.
Misc
Corrective Action Required
03/24/2022
Underslab Plumbing Inspection - Commercial Failed 3/24/2022 3/24/2022 03/24/2022
Misc
Corrective Action Required
03/24/2022
Unit (A) - no presure - trap wier cannot rise then fall in s pattern, lower traps.
Underslab Plumbing Inspection - Commercial Passed 3/25/2022 3/25/2022 03/25/2022
Misc
Resolved
03/25/2022
Rated Assembly Inspection Partial 4/13/2022 4/13/2022 04/13/2022
Miscellaneous Correction
Corrective Action Required
04/13/2022
Framed out bathroom in unit A south end of building. Studs rock against ceiling and fire caulked under stairs.
Rated Assembly Inspection Partial 4/15/2022 4/15/2022 04/15/2022
Miscellaneous Correction
Informational
04/15/2022
-Framed out bathroom in unit A south end of building. Studs rock against ceiling and fire caulked under stairs. - 4/15/22 inspection of fist layer (shaft liner) and fire caulk on ceiling of bathroom building A
Rated Assembly Inspection Partial 4/20/2022 4/20/2022 04/20/2022
Miscellaneous Correction
Informational
04/15/2022
-Framed out bathroom in unit A south end of building. Studs rock against ceiling and fire caulked under stairs. - 4/15/22 inspection of fist layer (shaft liner) and fire caulk on ceiling of bathroom building A - 4/20/22 inspected second layer of rock screw pattern on ceiling of bathroom building A
In-wall Inspection Partial 4/22/2022 4/22/2022 04/22/2022
Miscellaneous Correction
Corrective Action Required
04/22/2022
Partial 4/22/22 in wall inspection building A. - room 104. ,105,106,107,108,109,110 on plans
In-wall Inspection Partial 5/2/2022 5/2/2022 05/02/2022
Miscellaneous Correction
Corrective Action Required
04/22/2022
Partial 4/22/22 in wall inspection building A. - room 104. ,105,106,107,108,109,110 on plans 5/2/22 in wall inspection building A room 100, 101, 102, 103 floor cuts for island incomplete.
Above Ceiling Inspection Partial 5/13/2022 5/13/2022 05/13/2022
Misc
Corrective Action Required
05/13/2022
Unit A bathrooms, East pass West partial pass , re inspection required
Above Ceiling Inspection Passed 6/7/2022 6/7/2022 06/07/2022
Misc
Informational
06/07/2022
Unit A bathrooms, East pass West pass South pass
Occupancy Inspection - Fire Failed 6/24/2022 6/24/2022 06/24/2022
Corrective Action Required
06/24/2022
Address needed on ront and back doors. Exterior emergency egress lighting was not operational and failed.
Underslab Electrical Inspection - Commercial Passed 6/24/2022 06/24/2022
Misc
Resolved
06/24/2022
Unit (A) - no presure - trap wier cannot rise then fall in s pattern, lower traps.
Misc
Resolved
06/24/2022
In-wall Inspection Passed 6/24/2022 06/24/2022
Miscellaneous Correction
Resolved
06/24/2022
Partial 4/22/22 in wall inspection building A. - room 104. ,105,106,107,108,109,110 on plans 5/2/22 in wall inspection building A room 100, 101, 102, 103 floor cuts for island incomplete.
Occupancy Inspection - Codes Commercial Failed 6/24/2022 6/24/2022 06/24/2022
Misc
Corrective Action Required
06/24/2022
- No TCO until shell is approved - Post address - obtain an Irrigation permit and submit a back flow certification A - bathroom sink max 34” ADA compliant - Provide handy-cap mirror - Label panel - Missing outlet covers - Complete lighting - Label electrical panel
Occupancy Inspection - Planning Passed 7/1/2022 07/01/2022
Rated Assembly Inspection Passed 7/1/2022 07/01/2022
Miscellaneous Correction
Resolved
07/01/2022
-Framed out bathroom in unit A south end of building. Studs rock against ceiling and fire caulked under stairs. - 4/15/22 inspection of fist layer (shaft liner) and fire caulk on ceiling of bathroom building A - 4/20/22 inspected second layer of rock screw pattern on ceiling of bathroom building A
Occupancy Inspection - Codes Commercial Temporary C of O 7/1/2022 7/1/2022 07/01/2022
Misc
Corrective Action Required
06/24/2022
- obtain an Irrigation permit and submit a back flow certification EXPIRATION OF TCO 9/30/2022
Occupancy Inspection - Fire Passed 7/1/2022 7/1/2022 07/01/2022
Corrective Action Required
07/01/2022
All life safety was appropriate. Okay to occupy with approval form codes.
Occupancy Inspection - Codes Commercial Full C of O 8/18/2022 08/18/2022
Misc
Resolved
08/18/2022
- obtain an Irrigation permit and submit a back flow certification EXPIRATION OF TCO 9/30/2022
Documents & Images
Date Uploaded File Type Document Name
02/02/2022 Application Form 420 longview comm app
02/02/2022 Plans BOX DEV CO Office_Permit Set_CLOCKWORK
02/02/2022 Letter License Tax Bill
02/10/2022 Letter DS P/R Corrections Document
02/15/2022 Letter Box Dev Co Office City Review Comments
02/15/2022 Drawing A001
02/15/2022 Plans BOX DEV CO Office_Permit Set_CLOCKWORK REV1
02/23/2022 Approved Plans approved - BOX DEV CO Office_Permit Set_CLOCKWORK
03/07/2022 Receipt Receipt for transaction:2022-001203
03/17/2022 Receipt Receipt for transaction:2022-001469
03/22/2022 Receipt Receipt for transaction: 2022-001574
03/22/2022 Letter DS Building Permit
03/24/2022 Letter INSPECTION SUMMARY
03/24/2022 Letter INSPECTION SUMMARY
03/25/2022 Letter INSPECTION SUMMARY
04/05/2022 Plans Box Dev - PRCOM20220431
04/05/2022 Approved Plans approved revisions - Box Dev - PRCOM20220431
04/13/2022 Letter INSPECTION SUMMARY
04/15/2022 Letter INSPECTION SUMMARY
04/20/2022 Letter INSPECTION SUMMARY
04/22/2022 Letter INSPECTION SUMMARY
05/02/2022 Letter INSPECTION SUMMARY
05/13/2022 Letter INSPECTION SUMMARY
06/07/2022 Letter INSPECTION SUMMARY
06/24/2022 Letter INSPECTION SUMMARY
06/24/2022 Letter INSPECTION SUMMARY
06/24/2022 Letter INSPECTION SUMMARY
06/24/2022 Letter Fire Loss Reduction Form
06/24/2022 Letter Fire Loss Reduction Form
07/01/2022 Letter INSPECTION SUMMARY
07/01/2022 Letter Codes Temporary Certificate of Occupancy
07/01/2022 Letter Fire Loss Reduction Form
07/21/2022 Letter INSPECTION SUMMARY
07/29/2022 Pro Design - Backflow Report
08/18/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home