Permit Application Status

PRCOM20216468


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20216468
Building Permit - Commercial
Certificate of Occupancy
CHANGE OF TENANT
TENANT FINISH FOR FERTILITY CLINIC
12/22/2021
05/11/2022
06/25/2022
11/30/2022
Locations
Contacts
3 SQUARE CONTRACTING INC, Address:1243 MERRIAM LANE, Phone:(913) 754-3033  
Chris Sipes, Address:chris@3squarecontracting.com, Phone:(913) 754-3033  
OVERLAND PARK MECHANICAL CO LLC, Address:16088 FOSTER, Phone:(913) 814-8200  
HENSLEY ELECTRIC INC, Address:7911 BOND STREET, Phone:(913) 441-1064  
ALLIANCE MECHANICAL CONTRACTORS, Address:305 W CEDAR , Phone:(913) 553-2600  
HJM Architects, Address:7520 Washington St, Phone:(816) 979-1663  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 06/21/2022
Jim Eden
Installation acceptance testing
Corrective Action Required
06/21/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required- Call (816) 969-1300 to schedule an alarm test. Schedule the test outside of the neighboring business's regular hours.
Sprinkler Plan Review Released for Construction 06/07/2022 06/14/2022
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
06/14/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received June 1, 2022.
Installation acceptance testing
Corrective Action Required
06/14/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing and inspection.
Licensed Contractors Approved 02/25/2022 05/03/2022
Joe Frogge
LC - General Contractor
Resolved
05/03/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact which is where inspection reports will be sent. 2/18/22 - acknowledged in letter
LC - MEP Subs
Resolved
05/03/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 2/18/22 - acknowledged in letter
Fire Plan Review Approved with Conditions 02/25/2022 02/22/2022
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
02/17/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Hazardous material identification
Corrective Action Required
02/17/2022

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection)
Address numbers required
Corrective Action Required
02/17/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Space to be addressed 455.
Construction documents - Fire protection systems
Corrective Action Required
02/17/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Illumination required
Corrective Action Required
02/17/2022

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting.
Building Plan Review Approved 02/25/2022 02/22/2022
Joe Frogge
IBC 502.1 - Address Identification
Resolved
02/18/2022

2018 IBC 502.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches high with a minimum stroke width of ½ inch. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address identification shall be maintained. Action required: This suite has been assigned the address 455 NW Murray Rd. Update your records and inform your client.
IBC 1006.2.1 Egress based on occupant load and common path of egress travel distance
Resolved
02/22/2022

2018 IBC 1006.2.1 Egress based on occupant load and common path of egress travel distance. Two exits or exit access doorways from any space shall be provided where the design occupant load or the common path of egress travel distance exceeds the values listed in Table 1006.2.1. The cumulative occupant load from adjacent rooms, areas or spaces shall be determined in accordance with Section 1004.2. (see code for special requirements for foyers, lobbies, vestibules, and care suites in I-2 occupancies) Action required: Common path of travel exceeded as designed. Once an occupant has traveled 100' two distinct exits must be available.
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Resolved
02/18/2022

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clearance at latch side of door into Toilet 122.
Fire Plan Review Rejected 01/06/2022 12/27/2021
Michael Weissenbach
Construction documents for fire alarm systems
Informational
02/22/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Hazardous material identification
Informational
02/22/2022

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection)
Address numbers required
Informational
02/22/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Space to be addressed 455.
Construction documents - Fire protection systems
Informational
02/22/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Illumination required
Corrective Action Required
12/27/2021

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting.
Building Plan Review Rejected 01/06/2022 12/22/2021
Joe Frogge
IBC 502.1 - Address Identification
Corrective Action Required
12/22/2021

2018 IBC 502.1 Address identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be a minimum of 4 inches high with a minimum stroke width of ½ inch. Where required by the fire code official, address identification shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road and the building address cannot be viewed from the public way, a monument, pole or other approved sign or means shall be used to identify the structure. Address identification shall be maintained. Action required: This suite has been assigned the address 455 NW Murray Rd. Update your records and inform your client.
IBC 1006.2.1 Egress based on occupant load and common path of egress travel distance
Corrective Action Required
12/22/2021

2018 IBC 1006.2.1 Egress based on occupant load and common path of egress travel distance. Two exits or exit access doorways from any space shall be provided where the design occupant load or the common path of egress travel distance exceeds the values listed in Table 1006.2.1. The cumulative occupant load from adjacent rooms, areas or spaces shall be determined in accordance with Section 1004.2. (see code for special requirements for foyers, lobbies, vestibules, and care suites in I-2 occupancies) Action required: Common path of travel exceeded as designed. Once an occupant has traveled 100' two distinct exits must be available.
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
12/22/2021

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" clearance at latch side of door into Toilet 122.
Licensed Contractors Rejected 01/06/2022 12/22/2021
Joe Frogge
LC - General Contractor
Corrective Action Required
12/22/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
12/22/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $2,296.80 $2,296.80 Paid 05/09/2022
$8,085.00
8331507-Sewer Connection Fee $360.00 $360.00 Paid 05/09/2022
Commercial Excise Tax Fee $4,282.50 $4,282.50 Paid 05/09/2022
$4,042.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 5/25/2022 5/25/2022 05/25/2022
Underslab Electrical Inspection - Commercial Passed 5/25/2022 05/25/2022
In-wall Inspection Partial 6/30/2022 6/30/2022 06/30/2022
Misc
Corrective Action Required
06/30/2022
AREAS BELOW APPROVED: 6/30/22 IN WALL - 117,118,119,120,122,122,123,124,125,126,114,115,109,107,106,110,105,111,104,103,112,102,101 131, 130 RESTROOM EXISTING, NO CHANGES 128 JANITOR EXISTING NO CHANGES
Above Ceiling Inspection Partial 8/12/2022 8/12/2022 08/12/2022
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
08/12/2022
HARD LIDS AT 122,127,130,131
In-wall Inspection Passed 9/28/2022 09/28/2022
Misc
Corrective Action Required
06/30/2022
AREAS BELOW APPROVED: 6/30/22 IN WALL - 117,118,119,120,122,122,123,124,125,126,114,115,109,107,106,110,105,111,104,103,112,102,101 131, 130 RESTROOM EXISTING, NO CHANGES 128 JANITOR EXISTING NO CHANGES
Above Ceiling Inspection Passed 9/28/2022 9/28/2022 09/28/2022
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
08/12/2022
HARD LIDS AT 122,127,130,131 - 103,104,105,106,108,114,117,118,119,120,121,123,124,125,126,127,128,129 OK FOR CEILING TILE 101,102,109,110,111,112,113,115,116 OPEN TO ROOF DECK
Electrical Service Inspection Passed 11/4/2022 11/4/2022 11/04/2022
Occupancy Inspection - Codes Commercial Failed 11/22/2022 11/22/2022 11/22/2022
Miscellaneous Correction
Corrective Action Required
11/22/2022
Provide hammer arrestor dishwasher Break Room #111 Provide GFCI protection dishwasher #111 Label service panels Room #133 Provide GFCI protection Draw room sink #108 Provide restroom signage patient unisex Room #122 : OK TO STOCK & TRAIN :
Alarm Test Passed 11/22/2022 11/22/2022
Occupancy Inspection - Fire Failed 11/22/2022 11/22/2022 11/22/2022
Corrective Action Required
11/22/2022
Missing two escutcheon rings.
Occupancy Inspection - Codes Commercial Failed 11/28/2022 11/28/2022 11/28/2022
Miscellaneous Correction
Corrective Action Required
11/22/2022
Provide hammer arrestor dishwasher Break Room #111 Provide GFCI protection dishwasher #111 : OK TO STOCK & TRAIN :
Occupancy Inspection - Codes Commercial Full C of O 11/30/2022 11/30/2022 11/30/2022
Miscellaneous Correction
Resolved
11/30/2022
Provide hammer arrestor dishwasher Break Room #111 Provide GFCI protection dishwasher #111 : OK TO STOCK & TRAIN :
Occupancy Inspection - Fire Passed 11/28/2022 11/28/2022 11/30/2022
Documents & Images
Date Uploaded File Type Document Name
12/22/2021 Application Form 211222-Blue Sky Fertility-Comm. Permit Application
12/22/2021 Plans 211222-Blue Sky Fertility-Permit Drawing Set
12/27/2021 Letter Fire Building Plan Review
12/27/2021 Letter DS P/R Corrections Document
02/17/2022 Letter 220217_BSLS (PRCOM20216468) - Plan Review Response
02/17/2022 Plans 220217-BSLS Rev 1 (PRCOM20216468) - Bid Set
02/23/2022 Approved Plans approved-BSLS Rev 1 (PRCOM20216468) - Bid Set
05/03/2022 Letter License Tax Bill
05/09/2022 Receipt Receipt for transaction:2022-003106
05/25/2022 Letter INSPECTION SUMMARY
05/25/2022 Letter INSPECTION SUMMARY
06/14/2022 16734 Blue Sky Fertility FP PE Stamp
06/14/2022 Letter Fire (Sprinkler) Plan Review
06/21/2022 Letter Fire (Alarm) Plan Review Notice
06/30/2022 Letter INSPECTION SUMMARY
08/12/2022 Letter INSPECTION SUMMARY
09/28/2022 Letter INSPECTION SUMMARY
09/28/2022 Letter INSPECTION SUMMARY
10/28/2022 Approved Plans approved-Revised E Drawings for PRCOM20216468
11/04/2022 Letter INSPECTION SUMMARY
11/22/2022 Letter INSPECTION SUMMARY
11/22/2022 Letter INSPECTION SUMMARY
11/28/2022 Letter INSPECTION SUMMARY
11/28/2022 Letter Fire Loss Reduction Form
11/30/2022 Letter Codes Final Certificate of Occupancy
11/30/2022 Letter Field Certificate of Occupancy
01/13/2023 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home