Permit Application Status

PRCOM20215071


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20215071
Building Permit - Commercial
Certificate of Occupancy
TOWNSEND SUMMIT LLC
NEW TENANT FINISH
NEW PIZZA RESTAURANT
09/28/2021
12/21/2021
09/12/2022
03/15/2022
Locations
Contacts
mitchell3573@gmail.com, Address:mitchell3573@gmail.com  
BDH Construction LLC, Address:949 Egg Harbor Road  
OLIPHANTS HEATING & COOLING INC, Address:208 WOLLARD BLVD, Phone:(816) 470-6444  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
HOWERTON PLUMBING LLC, Address:195 NW AA HWY, Phone:(816) 694-0303  
INTERPLAN LLC, Address:1 East 22nd Street, Suite 40, Phone:(630) 932-2336  
TOWNSEND SUMMIT LLC, Address:230 SCHILLNG CIR STE 120  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 03/03/2022
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
03/03/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. REceived 3/3/2022
Alarm testing.
Corrective Action Required
03/03/2022

2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation. Call (816) 969-1300 to schedule a test before regular business hours of the other tenants.
Miscellaneous Correction
Corrective Action Required
03/03/2022

Remove the exterior horn/strobe from the outdoor seating area. Verified at inspection.
Duct smoke detectors
Corrective Action Required
03/03/2022

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Action required- The duct detectors shall also shut down the HVAC. Verified at inspection.
Miscellaneous Correction
Corrective Action Required
03/03/2022

The alarm system is not required to be connected to the door locks.
Sprinkler Plan Review Released for Construction 01/18/2022 01/18/2022
Jim Eden
Construction documents - Fire protection systems
Informational
01/18/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received January 13, 2022. Thank you.
Installation acceptance testing
Informational
01/18/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required- A visual inspection will be completed at the same time as the occupancy inspection.
Licensed Contractors Approved 10/29/2021 12/16/2021
Joe Frogge
LC - General Contractor
Resolved
12/16/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact. 10/25/21 - BDH not currently licensed with us.
LC - MEP Subs
Resolved
12/16/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/25/21 - acknowledged in letter.
Building Plan Review Approved with Conditions 10/29/2021 10/27/2021
Joe Frogge
Health Dept Review
Resolved
10/27/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 10/25/21 - acknowledged in letter.
Health Dept Inspection
Corrective Action Required
10/22/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 10/25/21 - acknowledged in letter.
Health Department Review Approved 10/27/2021
Joe Frogge
Fire Plan Review Approved with Conditions 10/29/2021 10/25/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
10/22/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signage at 99 in the interior and 45 on the exterior patio.
Construction documents for fire alarm systems
Corrective Action Required
10/22/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Address numbers required
Corrective Action Required
10/22/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address all exterior doors.
Construction documents - Fire protection systems
Corrective Action Required
10/22/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
10/22/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Miscellaneous Correction
Resolved
10/25/2021

Action Required) 2018 IFC 5307.3 Provide specs on tank for CO2. If over 100 pounds gas detection will be required.
Illumination required
Resolved
10/25/2021

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting at the exits.
Building Plan Review Rejected 10/05/2021 10/05/2021
Joe Frogge
Health Dept Review
Corrective Action Required
10/05/2021

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
10/05/2021

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Licensed Contractors Rejected 10/08/2021 10/05/2021
Joe Frogge
LC - General Contractor
Corrective Action Required
10/05/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
LC - MEP Subs
Corrective Action Required
10/05/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 10/08/2021 09/29/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
09/29/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signage at 99 in the interior and 45 on the exterior patio.
Construction documents for fire alarm systems
Corrective Action Required
09/29/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Address numbers required
Corrective Action Required
09/29/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address all exterior doors.
Construction documents - Fire protection systems
Corrective Action Required
09/29/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
09/29/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Miscellaneous Correction
Corrective Action Required
09/29/2021

Action Required) 2018 IFC 5307.3 Provide specs on tank for CO2. If over 100 pounds gas detection will be required.
Illumination required
Corrective Action Required
09/29/2021

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting at the exits.
Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $300.00 $300.00 Paid 12/21/2021
Valuation Fee for New Tenent Finish $1,600.00 $1,600.00 Paid 12/21/2021
Commercial Excise Tax Fee $12,862.50 $12,862.50 Paid 03/10/2022
Outstanding Fees Amount Paid Owing Date Paid
Not Ready Inspection Fee $50.00 $0.00 $50.00 Not Paid


$50.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 1/7/2022 01/07/2022
Underslab Electrical Inspection - Commercial Passed 1/11/2022 1/11/2022 01/11/2022
In-wall Inspection Failed 2/2/2022 2/2/2022 02/02/2022
Miscellaneous Correction
Corrective Action Required
02/02/2022
NO CITY APPROVED PLANS ON SITE
Hood/Duct Inspection Failed 2/2/2022 2/2/2022 02/02/2022
Miscellaneous Correction
Corrective Action Required
02/02/2022
NO CITY APPROVED PLANS ON SITE
In-wall Inspection Passed 2/3/2022 2/3/2022 02/03/2022
Above Ceiling Inspection Partial 2/4/2022 2/4/2022 02/03/2022
Misc
Corrective Action Required
02/03/2022
Soffits and lid at dining ok -Connect bath exhaust at hard lids
Hood/Duct Inspection Passed 2/3/2022 2/3/2022 02/03/2022
Miscellaneous Correction
Resolved
02/03/2022
Above Ceiling Inspection Partial 2/4/2022 2/4/2022 02/04/2022
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
02/03/2022
Soffits and lid at dining ok - hard lids restrooms & water heater room ok to cover -
Above Ceiling Inspection Partial 3/2/2022 03/02/2022
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
02/04/2022
Soffits and lid at dining ok - hard lids restrooms & water heater room ok to cover -
Miscellaneous Correction
Corrective Action Required
03/02/2022
- FIRE CAULK CONDUIT FOR PHONE CABLES WEST WALL NEAR REAR OF KITCHEN PROVIDE ACCESS TO THIS AREA - OK TO DROP CEILING TILE OTHER AREAS
Alarm Test Passed 03/08/2022
Above Ceiling Inspection Passed 3/15/2022 03/15/2022
THE FOLLOWING AREAS ARE APPROVED
Resolved
03/15/2022
Soffits and lid at dining ok - hard lids restrooms & water heater room ok to cover -
Miscellaneous Correction
Resolved
03/15/2022
Final Electrical Inspection - Commercial Passed 3/15/2022 03/15/2022
Final Plumbing Inspection - Commercial Passed 3/15/2022 03/15/2022
Occupancy Inspection - Codes Commercial Full C of O 3/15/2022 3/15/2022 03/15/2022
Verify Final Inspection (Final) Complete 3/15/2022 03/15/2022
Occupancy Inspection - Fire Passed 3/15/2022 3/15/2022 03/15/2022
Sprinkler - Flow Test Not Ready 03/16/2022
Documents & Images
Date Uploaded File Type Document Name
09/28/2021 Application Form Commercial Permit Application
09/28/2021 Application Form License Tax Application
09/28/2021 Plans MOD Lees Summit_AMEP_IssueForPermit_09_20_21
09/28/2021 Letter Menu
09/29/2021 Letter Fire Building Plan Review
10/05/2021 Letter DS P/R Corrections Document
10/22/2021 Letter Comment Response Letter
10/22/2021 CUTSHEET OF BULK TANK - Gahanna
10/22/2021 NUC02 Tank Sizes
10/22/2021 Plans MOD Lees Summit_All Flatened_10_22_21
10/25/2021 Letter Fire Building Plan Review
10/27/2021 Email New Food Establishment Plan Review - Approved FTG_0001906
10/27/2021 Approved Plans approved - MOD Lees Summit_All Flatened_10_22_21
12/16/2021 Letter License Tax Bill
12/21/2021 Receipt Receipt for transaction: 2021-009425
12/21/2021 Letter DS Building Permit
01/07/2022 Letter INSPECTION SUMMARY
01/11/2022 Letter INSPECTION SUMMARY
01/18/2022 Letter Fire (Sprinkler) Plan Review
02/02/2022 Letter INSPECTION SUMMARY
02/02/2022 Letter INSPECTION SUMMARY
02/02/2022 Plans MOD Lees Summit_All Rev 4_01_05_22
02/02/2022 Approved Plans approved - MOD Lees Summit_All Rev 4_01_05_22
02/03/2022 Letter INSPECTION SUMMARY
02/03/2022 Letter INSPECTION SUMMARY
02/03/2022 Letter INSPECTION SUMMARY
02/04/2022 Letter INSPECTION SUMMARY
03/02/2022 Letter INSPECTION SUMMARY
03/03/2022 Plans 22-076_FA FA11 (1)
03/03/2022 Specifications 5495 Power Supply
03/03/2022 Specifications Ceiling Device
03/03/2022 Specifications Power Supply
03/03/2022 Specifications Wall
03/03/2022 Letter Fire (Alarm) Plan Review Notice
03/08/2022 Letter Fire Loss Reduction Form
03/10/2022 Receipt Receipt for transaction:2022-001302
03/10/2022 Engineer Report/Study MOD Pizza TAB_REPORT
03/15/2022 Letter Codes Final Certificate of Occupancy
03/15/2022 Letter Field Certificate of Occupancy
03/15/2022 Letter INSPECTION SUMMARY
03/15/2022 Letter INSPECTION SUMMARY
03/15/2022 Letter INSPECTION SUMMARY
03/15/2022 Letter Fire Loss Reduction Form
03/17/2022 Health Inspection Report
03/24/2022 Letter Fire Loss Reduction Form
03/28/2022 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home