Permit Application Status

PRCOM20214854


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20214854
Building Permit - Commercial
Certificate of Occupancy
VAAP RAINTREE LLC
CHANGE OF TENANT
CHANGE OF TENANT FOR MARTIAL ARTS GYM
09/17/2021
11/16/2021
04/11/2022
01/20/2022
Locations
Contacts
LONGBOW CONTRACTING, Address:914 SW GEORGETOWN DR, Phone:(816) 352-9271  
jeremy.brown2264@gmail.com, Address:jeremy.brown2264@gmail.com  
DAVID BALES, Address:17505 E 163RD, Phone:(816) 537-7511  
TRADEMARK PLUMBING LLC, Address:611 NW 105TH RD, Phone:(816) 824-5846  
HILL HEATING AND COOLING LLC, Address:19905 PEPPERTREE RD, Phone:(913) 475-2166  
THE GAMBLE COMPANY, LLC, Address:3500 S MIZE RIDGE CT, Phone:(816) 809-8748  
VAAP RAINTREE LLC, Address:5007 W 147TH ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 10/25/2021 11/15/2021
Joe Frogge
LC - MEP Subs
Resolved
11/15/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 10/18/21 - acknowledged in letter
Building Plan Review Approved 10/25/2021 11/09/2021
Joe Frogge
IBC 602.1 Type of Construction - general
Resolved
10/18/2021

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update Building Data to show correct construction type which is 5B.
IPC 403.1 Minimum number of fixtures
Resolved
10/18/2021

2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Provide mop sink. (also specify compliant wall finish materials - see finish comment below.)
IBC 1209.2 Finish materials
Resolved
10/18/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish materials at toilets and mop sink. If paint is used it must be epoxy based.
Misc
Resolved
10/18/2021

Inadequate information to complete review. Provide the following: - Complete hvac and plumbing designs. - Emergency and exit lighting plan. 10/18/21 - hvac existing to remain per arch
IMC 403.2 Outdoor air required
Resolved
11/09/2021

2018 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. (see code for exception) Action required: Revise drawings to show outside air calculations as well as method of delivery. 10/18/21 - Per architect, hvac is existing and compliant when installed. New type of occupancy has increased outside air requirements. Calculations and design required.
IBC 1109.12.9 Point of sale and service counters - accessibility
Resolved
10/18/2021

2018 IBC 1109.12.3 Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Reception desk must have at least 3 linear feet of counter that is maximum 36" tall. To be field verified.
Fire Plan Review Approved with Conditions 10/25/2021 10/18/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
10/18/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signage at 116.
Construction documents for fire alarm systems
Corrective Action Required
10/18/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Address numbers required
Corrective Action Required
10/18/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address all exterior doors.
Construction documents - Fire protection systems
Corrective Action Required
10/18/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
10/18/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
10/18/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide two 2A10BC Fire Extinguishers.
Misc
Resolved
10/18/2021

(Action Required) 1.Provide a plan for emergency/exit lighting for the space. 2.Construction type is VB.
Panic and fire exit hardware
Corrective Action Required
10/18/2021

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. (Verified At Inspection) Provide panic hardware for the exit doors.
Building Plan Review Rejected 10/20/2021 10/13/2021
Joe Frogge
IBC 602.1 Type of Construction - general
Corrective Action Required
10/13/2021

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update Building Data to show correct construction type which is 5B.
IPC 403.1 Minimum number of fixtures
Corrective Action Required
10/13/2021

2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Provide mop sink. (also specify compliant wall finish materials - see finish comment below.)
IBC 1209.2 Finish materials
Corrective Action Required
10/13/2021

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish materials at toilets and mop sink. If paint is used it must be epoxy based.
Misc
Corrective Action Required
10/13/2021

Inadequate information to complete review. Provide the following: - Complete hvac and plumbing designs. - Emergency and exit lighting plan.
IMC 403.2 Outdoor air required
Corrective Action Required
10/13/2021

2018 IMC 403.2 Outdoor air required. The minimum outdoor airflow rate shall be determined in accordance with Section 403.3. (see code for exception) Action required: Revise drawings to show outside air calculations as well as method of delivery.
IBC 1109.12.9 Point of sale and service counters - accessibility
Corrective Action Required
10/13/2021

2018 IBC 1109.12.3 Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Reception desk must have at least 3 linear feet of counter that is maximum 36" tall. To be field verified.
Licensed Contractors Rejected 10/20/2021 10/13/2021
Joe Frogge
LC - MEP Subs
Corrective Action Required
10/13/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 10/20/2021 10/11/2021
Michael Weissenbach
Posting of occupant load
Corrective Action Required
10/11/2021

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signage at 116.
Construction documents for fire alarm systems
Corrective Action Required
10/11/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Address numbers required
Corrective Action Required
10/11/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection) Address all exterior doors.
Construction documents - Fire protection systems
Corrective Action Required
10/11/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
10/11/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
10/11/2021

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide two 2A10BC Fire Extinguishers.
Misc
Corrective Action Required
10/11/2021

(Action Required) 1.Provide a plan for emergency/exit lighting for the space. 2.Construction type is VB.
Panic and fire exit hardware
Corrective Action Required
10/11/2021

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. (Verified At Inspection) Provide panic hardware for the exit doors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $74.00 $74.00 Paid 11/15/2021
$14,280.00
8331507-Sewer Connection Fee $60.00 $60.00 Paid 11/15/2021
7232302-Commercial License Tax Fee $9,255.00 $9,255.00 Paid 01/13/2022
$7,140.00
Outstanding Fees Amount Paid Owing Date Paid


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Above Ceiling Inspection Passed 12/22/2021 12/22/2021 12/22/2021
Misc
Corrective Action Required
12/22/2021
-OPEN CEILING AT FRONT MAT AREA TO BE INSPECTED AT FINAL -COMPLETE GRID AND SECURE MC OFF GRID AT BREAKROOM -MECH ROOM CHECK AT FINAL, DATA BEING REMOVED ALL OTHER AREAS OK
In-wall Inspection Passed 12/22/2021 12/22/2021 12/22/2021
Occupancy Inspection - Codes Commercial Failed 1/19/2022 1/19/2022 01/19/2022
Misc
Corrective Action Required
01/19/2022
SEE FIRE INSPECTION REPORT FOR CORRECTIONS -REMOVE OR TERMINATE OPEN MC ABOVE SERVICE PANEL IN MECH ROOM , ADD COVER PLATE ON J BOX ABOVE MECH STORAGE ROOM AND SECURE MC OFF CEILING GRID - COVER PLATES ON SWITCHES -HAVE PLUMBER PULL PERMIT FOR ADDITONAL WORK BEING DONE IN BREAK ROOM
Occupancy Inspection - Fire Failed 1/19/2022 1/19/2022 01/19/2022
Corrective Action Required
01/19/2022
Add exit sign to West door. Change duck detection to come in as a supervisory and not a general alarm. Fire sprinkler system is out of date by almost two years. Add fire extinguisher to back hall.
Occupancy Inspection - Codes Commercial Full C of O 1/20/2022 1/20/2022 01/20/2022
Misc
Resolved
01/20/2022
Occupancy Inspection - Fire Passed 1/20/2022 01/20/2022
Documents & Images
Date Uploaded File Type Document Name
09/17/2021 Application Form K2LMA Comm App form
09/17/2021 Application Form K2LMA LT form
10/11/2021 Plans KARATE STUDIO SEALED-091621
10/11/2021 Letter License Tax Bill
10/11/2021 Letter Fire Building Plan Review
10/13/2021 Letter DS P/R Corrections Document
10/18/2021 Letter KARATE STUDIO NARRATIVE-101421
10/18/2021 Plans KARAKE STUDIO SEALED 10-14-21-101421
10/18/2021 Letter Fire Building Plan Review
11/09/2021 Letter NARRATIVE - MEP CALCULATIONS-110621
11/09/2021 Approved Plans approved - KARAKE STUDIO DRAWINGS SEALED-110621
11/15/2021 Receipt Receipt for transaction:2021-008757
11/16/2021 Letter DS Building Permit
11/19/2021 Letter License Tax Bill
11/19/2021 Email LT info
12/22/2021 Letter INSPECTION SUMMARY
12/22/2021 Letter INSPECTION SUMMARY
01/13/2022 Receipt Receipt for transaction: 2022-000249
01/19/2022 Letter INSPECTION SUMMARY
01/19/2022 Letter Fire Loss Reduction Form
01/20/2022 Letter Field Certificate of Occupancy
01/20/2022 Letter Codes Final Certificate of Occupancy
01/20/2022 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home