Permit Application Status

PRCOM20214669


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20214669
Building Permit - Commercial
Withdrawn
STAR ACQUISITIONS & DEVELOPMENT LLC
NEW SHELL BUILDING
NEW SHELL BUILDING WITH DRIVE-THRU FOR FUTURE TENANTS
09/07/2021
03/07/2022
05/23/2022
Locations
Contacts
  
  
  
  
  
SCHARHAG ARCHITECTS, Address:6247 BROOKSIDE BLVD STE 204, Phone:(816) 656-5055  
STAR ACQUISITIONS & DEVELOPMENT LLC, Address:244 W MILL STE 101  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 11/04/2021
Mike Weisenborn
Building Plan Review Rejected 09/21/2021 09/08/2021
Joe Frogge
Final Development Plan
Corrective Action Required
09/08/2021

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is for informational purposes.
Miscellaneous Correction
Corrective Action Required
09/08/2021

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
IBC 1015.7 Roof access - roof hatch guard
Corrective Action Required
09/08/2021

2018 IBC 1015.7 Roof access. Guards shall be provided where the roof hatch opening is located within 10 feet of a roof edge or open side of a walking surface and such edge or open side is located more than 30 inches above the floor, roof or grade below. The guard shall be constructed so as to prevent the passage of a sphere 21 inches in diameter. (see code for exception) Action required: Comment is for informational purposes. If parapets near roof hatch are not at least 42" tall additional guards would be required. To be field verified.
IMC 507.2.6 Clearances for Type I hood
Corrective Action Required
09/08/2021

2018 IMC 507.2.6 Clearances for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18”. Exceptions: 1. Clearance shall not be required from gypsum wallboard or ½ inch or thicker cementitious wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum or cementitious wallboard over an area extending not less than 18 inches in all directions from the hood. 2. Type I hoods listed and labeled for clearances less than 18 inches in accordance with UL 710 shall be installed with the clearances specified by such listings. Action required: Comment is for informational purposes. Consider non-combustible wall construction in locations likely to support Type I grease hood in future restaurant.
Licensed Contractors Rejected 09/21/2021 09/08/2021
Joe Frogge
LC - General Contractor
Corrective Action Required
09/08/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
LC - MEP Subs
Corrective Action Required
09/08/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved 09/21/2021 09/07/2021
Michael Weissenbach
Inspections

There are no inspections for this permit application.

Documents & Images
Date Uploaded File Type Document Name
09/07/2021 Application Form Douglas Rd Center Lot 3 Permit Application
09/07/2021 Plans Douglas Rd Center Lot 3 with seal 8_20_21
09/07/2021 Engineer Report/Study Douglas Rd Center Lot 3 Structural Calcuations 8_20_21
09/07/2021 Letter Fire Building Plan Review
09/08/2021 Letter DS P/R Corrections Document
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home